Mr Michael L. Prevatte
4505 Market St.
Wilmington, NC 28405
Subject: Stormwater Permit No. SW8 950613
Sleep Inn Motel
High Density Project
New Hanover County
Dear Mr. Prevatte:
Michael F. Easley, Governor
William G Ross Jr, Secretary
North Carolina Department of Environment and Natural Resources
Coleen H Sullins Director
Division of Water Quality
The Wilmington Regional Office received a complete Stormwater Management Permit Application for Sleep Inn
Motel on July 18, 2007. Staff review of the plans and specifications has determined that the project, as proposed,
will comply with the Stormwater Regulations set forth in Title 15A NCAC 2H.1000. We are forwarding Permit No.
SW8 950613 dated November 27, 2007, for the construction and continued operation of the subject project.
This permit shall be effective from the date of issuance until November 27, 2017, and shall be subject to the
conditions and limitations as specified therein Please pay special attention to the Operation and Maintenance
requirements in this permit. Failure to establish an adequate system for operation and maintenance of the
stormwater management system will result in future compliance problems.
The reissuance of this stormwater permit does not imply that the site is currently in compliance with the terms and
conditions of this state stormwater permit.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request
an adjudicatory hearing upon written request within sixty (60) days following receipt of this permit. This request
must be in the form of a written petition, conforming to Chapter 150E of the North Carolina General Statutes, and
filed with the Office of Administrative Hearings, P.O. Drawer 27447, Raleigh, NC 27611-7447. Unless such
demands are made this permit shall be final and binding.
If you have any questions, or need additional information concerning this matter,
or me at (9 0) 796-7215.
Sin rely, / A, ,
6iL�
Edward Beck
Regional Supervisor
Surface Water Protection Section
ENB/ahl: S:\WQS\STORMWATER\PERMIT\950613Ren.nov07
cc: New Hanover Building Inspections
C Wilmington Regional Office File
Central Files
please contact either Aisha Lau,
N""o��r nnCarolina
JvWura!!y
North Carolina Division of Water Quakily 127 Cardinal Drive Extension Wilmington, NC 28405 Phone (910) 796-7215 Customer Service
Wilmington Regional Office Internet. www newateiauahtv.org Fax (910) 350-2004 1-877-623-6748
An Equal OpportunitylAffirmative Action Employer— 50% Recyded110°/ Post Consumer Paper
State Stormwater Management Systems
Permit No. SW8 950613 Renewal
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
STATE STORMWATER MANAGEMENT PERMIT
HIGH DENSITY DEVELOPMENT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of
North Carolina as amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Wilmington Development Company, Inc.
Sleep Inn Motel
New Hanover County
FOR THE
construction, operation and maintenance of a wet detention pond in compliance with
the provisions of 15A NCAC 2H .1000 (hereafter referred to as the "stormwater rules')
and the approved stormwater management plans and specifications and other
supporting data as attached and on file with and approved by the Division of Water
Quality and considered a part of this permit.
This permit shall be effective from the date of issuance until November 27, 2017, and
shall be subject to the following specified conditions and limitations:
I. DESIGN STANDARDS
This permit is effective only with respect to the nature and volume of stormwater
described in the application and other supporting data.
This stormwater system has been approved for the management of stormwater
runoff as described in Section 1.6 on page 3 of this permit. The stormwater
control has been designed to handle the runoff from 81,000 square feet of
impervious area.
The tract will be limited to the amount of built -upon area indicated on page 3 of
this permit, and per approved plans.
4. All stormwater collection and treatment systems must be located in either
dedicated common areas or recorded easements. The final plats for the project
will be recorded showing all such required easements, in accordance with the
approved plans.
5. The runoff from all built -upon area within the permitted drainage area of this
project must be directed into the permitted stormwater control system.
Page 2 of 7
State Stormwater Management Systems
Permit No. SW8 950613 Renewal
The following design criteria have been provided in the wet detention pond and
must be maintained at design condition:
a.
Drainage Area, acres:
3.42
Onsite, ft :
149,000
Offsite, ft2:
0
b.
Total Impervious Surfaces, ft2:
81,000
C.
Design Storm, inches:
1
d.
Pond Depth, feet:
5
e.
TSS removal efficiency:
90%
f.
Permanent Pool Elevation, FMSL:
30
g.
Permanent Pool Surface Area, ft2:
6,744
h.
Permitted Storage Volume, ft3:
8,370 at temporary pool el
i.
Temporary Storage Elevation, FMSL:
31.1
j.
Controlling Orifice:
1.5 "0 pipe
k.
Receiving Stream/River Basin:
Spring Creek / Cape Fear
I.
Stream Index Number:
18-74-63-1
M.
Classification of Water Body:
"C, Sw "
II. SCHEDULE OF COMPLIANCE
1. The stormwater management system shall be constructed in its entirety,
vegetated and operational for its intended use prior to the construction of any
built -upon surface.
2. During construction, erosion shall be kept to a minimum and any eroded areas of
the system will be repaired immediately.
3. The permittee shall at all time provide the operation and maintenance necessary
to assure the permitted stormwater system functions at optimum efficiency. The
approved Operation and Maintenance Plan must be followed in its entirety and
maintenance must occur at the scheduled intervals including, but not limited to:
a. Semiannual scheduled inspections (every 6 months).
b. Sediment removal.
C. Mowiny and re -vegetation of slopes and the vegetated filter.
d. Immediate repair of eroded areas.
e. Maintenance of all slopes in accordance with approved plans and
specifications.
f. Debris removal and unclogging of outlet structure, orifice device, flow
spreader, catch basins and piping.
g. Access to the outlet structure must be available at all times.
4. Records of maintenance activities must be kept and made available upon
Page 3 of 7
State Stormwater Management Systems
Permit No. SW8 950613 Renewal
request to authorized personnel of DWQ. The records will indicate the date,
activity, name of person performing the work and what actions were taken.
5. The facilities shall be constructed as shown on the approved plans. This permit
shall become void unless the facilities are constructed in accordance with the
conditions of this permit, the approved plans and specifications, and other
supporting data.
6. Upon completion of construction, prior to issuance of a Certificate of Occupancy,
and prior to operation of this permitted facility, a certification must be received
from an appropriate designer for the system installed certifying that the permitted
facility has been installed in accordance with this permit, the approved plans and
specifications, and other supporting documentation. Any deviations from the
approved plans and specifications must be noted on the Certification. A
modification may be required for those deviations.
7. If the stormwater system was used as an Erosion Control device, it must be
restored to design condition prior to operation as a stormwater treatment device,
and prior to occupancy of the facility.
8. Access to the stormwater facilities shall be maintained via appropriate
easements at all times.
The permittee shall submit to the Director and shall have received approval for
revised plans, specifications, and calculations prior to construction, for any
modification to the approved plans, including, but not limited to, those listed
below:
a. Any revision to any item shown on the approved plans, including the
stormwater management measures, built -upon area, details, etc.
b. Project name change.
C. Transfer of ownership.
d. Redesign or addition to the approved amount of built -upon area or to the
drainage area.
e. Further subdivision, acquisition, lease or sale of all or part of the project
area. The project area is defined as all property owned by the permittee,
for which Sedimentation and Erosion Control Plan approval or a CAMA
Major permit was sought.
f. Filling in, altering, or piping of any vegetative conveyance shown on the
approved plan.
10. The permittee shall submit final site layout and grading plans for any permitted
future areas shown on the approved plans, prior to construction.
11. A copy of the approved plans and specifications shall be maintained on file by
the Permittee for a minimum of ten years from the date of the completion of
construction.
12. The Director may notify the permittee when the permitted site does not meet one
or more of the minimum requirements of the permit. Within the time frame
specified in the notice, the permittee shall submit a written time schedule to the
Director for modifying the site to meet minimum requirements. The permittee
shall provide copies of revised plans and certification in writing to the Director
that the changes have been made.
III. GENERAL CONDITIONS
This permit is not transferable except after notice to and approval by the Director.
In the event of a change of ownership, or a name change, the permittee must
Page 4 of 7
State Stormwater Management Systems
Permit No. SW8 950613 Renewal
submit a formal permit transfer request to the Division of Water Quality,
accompanied by a completed name/ownership change form, documentation
from the parties involved, and other supporting materials as may be appropriate.
The approval of this request will be considered on its merits and may or may not
be approved. The permittee is responsible for compliance with all permit
conditions until such time as the Division approves the transfer request.
2. Failure to abide by the conditions and limitations contained in this permit may
subject the Permittee to enforcement action by the Division of Water Quality, in
accordance with North Carolina General Statute 143-215.6A to 143-215.6C.
3. The issuance of this permit does not preclude the Permittee from complying with
any and all statutes, rules, regulations, or ordinances, which may be imposed by
other government agencies (local, state, and federal) having jurisdiction.
4. In the event that the facilities fail to perform satisfactorily, including the creation
of nuisance conditions, the Permittee shall take immediate corrective action,
including those as may be required by this Division, such as the construction of
additional or replacement stormwater management systems.
5. The permittee grants DENR Staff permission to enter the property during normal
business hours for the purpose of inspecting all components of the permitted
stormwater management facility.
6. The permit may be modified, revoked and reissued or terminated for cause. The
filing of a request for a permit modification, revocation and re -issuance or
termination does not stay any permit condition.
7. Unless specified elsewhere, permanent seeding requirements for the stormwater
control must follow the guidelines established in the North Carolina Erosion and
Sediment Control Planning and Design Manual.
8. Approved plans and specifications for this project are incorporated by reference
and are enforceable parts of the permit.
9. The permittee shall notify the Division any name, ownership or mailing address
changes within 30 days.
Permit issued this the 27th day of November, 2007.
NORTH ZLINA ENVIRONMENTAL MANAGEMENT COMMISSION
MAO
u fins, Director
Division of Water Quality
By Authority of the Environmental Management Commission
Page 5 of 7
a0F W ATF9 I le #: - — IS — �� Michael F. Easley, Governor
0. o William G. Ross Jr., Secretary
U"' r r� North Carolina Department of Environment and Natural Resources
Sw�S-lSD�1
O Y Coleen H. Sullins, P.E. Director
Division of Water Quality /
SURFACE WATER PROTECTION SECTION ✓
COASTAL STORMWATER PERMIT RENEWAL APPLICATION FORM
I. CURRENT PERMIT INFORMATION:
1 Stormwater Management Permit Number _ S W $ 9 9016013
2 Permit Holder's name W; IM,,0 A+an fleye Is DR.en fi C'o�nDaA v l`. c .
�� �—
3. Signing official's name /tit; ckr4 r C. ct/aT/rTitle: JDres i c�rit�
(person legally responsible for permit) 1
4. Mailing address Y-ToS M4rk.7 STretT City:_ [A): tMr+A actin NC
i
State.Ay,ZlpCode: 2k� 0�_Phone:9i0-749-/a2/4 FAX. 9/D-39d--9o19
(Area Code and Number) (Area Code and Number)
5 Project Name _ _ 51,ea n_i San o 1 e / y ,jam
6. Location of Project: (street address) Spa S IYI,?o �$ t .57re C/
7. Directions to Project (from nearest major intersection) b e k. n,r 5I Q-e p —In �l O & M e---ket
St" A5Hwy/?) (tear 7"Ac Co,^er &F./►'jarkefSY-g,.1)-ennoA bl:ve
II. PERMIT INFORMATION
1 Specify the type of stormwater treatment (wet pond, infiltration, etc) W P- oiei4^i':eA PO Nd
—
�. List any changes (from project that was originally approved, attach additional pages if needed)
>. Do you have a copy of the original Operation and Maintenance A, greement? Yes✓No
Applicant's Certification: /� JUL 1 S 2007
I, (pant) /r/. (��4V / /. Preyatflt- certify that the Information_included on this
permit renewal application, is to the best of my knowledge, correct and complete.
Signature:/�/•�{.t< Date: 7_/6-aoe
Submit this completed form along with an application fee of $420.00 and a copy of the
desiqner's certification to the address listed below N°nc�ly
North Carolina Division of Water Quality 127 Cardinal Drive Extension Wilmington, NC 28405 Phone (910) 796-7215 Customer service
Wilmington Regional office Internet, www ncwaterauality or F'ax (910) 350-2004 1-877-623-6748
0
L
�� ✓ ' i ��' ;° 1NILNIINGTON;DE
i , WHITEY'S�EL;BERTA' I
/c
\ WIDNMaI
LOPMENf;Co:1NC'�'''�'J�';`.
I'oR'tNN'&';RESTAURANT' %~
NC
799�1214' ; ` ,DATE ' � ✓ \ � is 025ai
.r
I�'..
r•;S':'. ;%c_,:?_. _; \vj ,.. �-/. .. ` IDOL L'AR S.6 +e.
/
:- i4Y.t
��:0;5 3;: 0 i" <2;i� -5 i;5
Date: ZZ D
Project Name:
Project No:County:
5,9
The Wilmington Regional Office of the Division of Water Quality
received your Stormwater Permit Renewal Application and fee on
/8-D''J
you will be notified if additional information is needed. If you
have any questions, please contact any member of the Stormwater
review staff in the Wilmington Regional office at (910) 796-7215.
Jo Casmer
Administrative Assistant
=` Andrew & Kuske
CONSULTING ENGINEERS, INC.
STORMWATER MAINTENANCE SYSTEM
MAINTENANCE PROCEDURES
John R. Andrew, P.E.
J. A. Kuske, P.E.
J. Phillip Norris, P.E.
SLEEP INN MOTEL '""'t
A&K PROJECT NO. 94263 j,
1. RESPONSIBLE PARTY
A. The project will be built and maintained by: Jt,I N 1 2 1995
U
Wilmington Development Company, Inc.
4505 Market Street D E M
Wilmington, NC 28405 Patoj iq Lv-- � gi50
910-799-1214
2. DETENTION POND AND COLLECTION SYSTEM
A. The detention pond will be checked after every major storm event to insure that the
outlet structure is working properly and is not clogged with debris. Remove any accumulated
sediment or debris. Any signs of erosion or deterioration of the pond side slopes or any other feature
must be repaired before the next storm event.
B. The depth of the pond will be checked every six months to determine the depth of the
permanent pool. The pond will be cleaned out when silt deposits reduce the depth of the permanent
pool below 3.75 feet. The side slopes of the pond shall be mowed as required to maintain a grass
height not to exceed 8 inches in height.
C. Collection basins and piping will be checked every six months and kept clear as
necessary.
3. CERTIFICATION
The owner will submit to the Department of Environment, Health and Natural Resources an
Engineer's Certification that the stormwater facilities were constructed in accordance with approved
plans. /?
State of North Carol
I, Jeria M. C
aforesaid, certify that Y.
day and acknowledged the
WITNESS my hand
My Commission Expires:
7/26/.�
Utle date
NOTARY'S CERTIFICATION
na County of New Hanover
Leman a Notary Public anforhtate and County
L. ti` ti e , personally appeared before me this
re Ili oregoing instrument.
fhe 31st day of May 1995.
a
PUBLIC ,� gunv N7ir"`t
ottaryaryPublic
202 North Fifth Avenue Wilmington, 7$ftlrT 28401 Telephone: 910/343-9653 Facsimile: 910/343-9604
\��F WAr�9p(r MichadP Easley, Governor
O
N91ham G Ross Jr., Secretan
North Carolina Depanment or Environment and Natural Resources
� y
Q < Alan W Klimek, P E Director
Division ul' Walcr Quahty
July 11, 2007
Sleep Inn Motel
Mr. Michael L. Prevatte, Vice -President
Wilmington Development Company
4505 Market Street
Wilmington, NC 28405
Subject:: Stormwater Permit No. SW8950613
Sleep Inn Motel
New Hanover County
Dear Mr. Prevatte:
The Division of Water Quality Issued a Coastal Stormwater Management Permit, Number SVV8950613
to Mr. Michael L. Prevatte for a High Density pond to serve Sleep inn Motel on 10/3/1996. This permit
expired on 10/3/2006. Section .1003(h) of 15 A NCAC 2H .1000 (the stormwater rules) requires that
applications for permit renewals shall be submitted 180 days prior to the expiration of a permit and must
be accompanied by a processing fee, which is currently set at $420.00. If this is still an active project
please complete and submit the enclosed renewal application in a timely manner If this project has not
been constructed and a permit is no longer needed, please submit a request to have the permit
rescinded If you have sold the project, or are no longer the permittee, please provide the name, mailing
address and phone number of the person or entity that is now responsible for this permit. Enclosed is a
form for change of ownership, which should be completed and submitted if the property has changed
hands.
Your permit requires that upon completion of construction and prior to operation of the permitted
treatment units a certification of completion be submitted to the Division from an appropriate designer
for the system installed This Is to certify that the permitted facility has been installed in accordance with
the permit, the approved plans, specifications and supporting documentation. Please include a copy of
the certification with your permit renewal request and processing fee. Enclosed is a copy of a sample
certification. Also enclosed is a new Operation and Maintenance agreement that should, be completed
and submitted along with your renewal application
You should be aware that failure to provide the Designer's Certification and the operation of a
stormwater treatment facility without a Valid permit, are violations of NC General Statute 143-215 1 and
may result in appropriate enforcement action Including the assessment of civil penalties of up to
$10,000 per day.
If you have any questions, please feel free to contact staff in the stormwater group at 910-796-7215
Si rely,
Ed Beck, Regional Supervisor
Surface Water Protection Section
Wilmington Regional Office
Enclosures
cc: Wilmington Regional Office
North Carolina Division of Water Quality Internet, www ncN%mcrguahlY or One
127 Cardinal drive Extension Phone (910) 796-7215 1 V orth Caro11Ila
Wilmington, NC 28403 Fax (910) 350-2004 Naturally
An Equal OpportumtylAfhrmaUve Action Employer — 50 % Recycled/10% Post Consumer Paper �/ y!!
01
State of North Carolina
Department of Environment, Health, and Natural Resources
Wilmington Regional Office
James B. Hunt, Jr. Division of Water Quality Wayne McDevitt
Governor Water Quality Section Secretary
August 8, 1997
- - Mr. Michael Prevatte, Vice President
Wilmington Development Company
4505 Market Street
Wilmington, NC 28405
Subject: COMPLIANCE INSPECTION
Sleep Inn Motel
Stormwater Project No. SW8 950613
New Hanover County
Dear Mr. Prevatte:
Please find attached a copy of the completed form entitled "Stormwater Compliance Inspection
Report". The report summarizes the findings of a recent inspection of the project's stormwater controls
conducted on August 7, 1997 to determine compliance with Stormwater Certification Number SW8 950613
issued on October 3, 1996.
A summary of the findings and comments are noted under Section 6 of the report. Please inform this
Office in writing before September 8, 1997 of the specific actions that will be undertaken and the time frame
required to correct the deficiencies. Failure to provide the requested information, when required, may initiate
enforcement action. If you have any questions please contact me at the Wilmington Regional Office,
telephone number (910) 395-3900.
Sincerely,
Linda Lewis
Environmental Engineer
RSS/arl: S:\WQS\STORMWAT\INSPECT\950613.AUG
cc: John Kuske
Central Files
Linda Lewis
127 Cardinal Drive Extension, Wilmington, N.C. 28405-3845 • Telephone 910-395-3900 • Fax 91G-35G-2004
An Equal Opportunity Affirmative Action Employer
1
2
3.
4.
5.
6.
STORMWATER COMPLIANCE INSPECTION REPORT
Project Name: • Sleep Inn Motel
Project Number: SW8 950613 Control Measure: a detention pond
Water Body: Smith Creek Classification: C Sw
Directions to site, address: 5225 Market Street, Wilmington
Inspection Date: August 7, 1997
Weather Conditions: Warm, sunny
Comparison of Approved plans vs. As -Built: Compared well.
Maintenance Problems:
a. There is sparse vegetation on the slopes.
b: The area around the inlet pipe is very eroded.
C. The Engineer's Certification has not been received.
PE Certification Received? NO Deed Restrictions Received? N/A
Comments:
a. Please provide a vigorous stand of permanent vegetation.
b. Please repair and stabilize the eroded area around the inlet.
C. Please provide the Engineer's Certification.
Inspector: Linda Lewis 41�
Water Quality/Wilmington Regional Office/(910) 395-3900
RSS/arl: S:\WQS\STORMWAT\INSPECT\950613.AUG