HomeMy WebLinkAboutSW5200602_Plan (SCM Detail)_202010201�
3 MIN
INFLOW PIPE
SEDIMENTATION CHAMBER
6"
#57 WASHED 2' RIP RAP
STONE
3" GRAVEL / STONE SURFACE
EL 439.5
CLEAN -OUT
(PVC PIPE
W / GLUED CLEAN -OUT FITTINGS
AND SCREW TYPE CAP)
3" GRAVEL / STONE
SURFACE
.444.00
RIP RAP BERM
(CLASS B)
SANFILTER MEDIA
(ASTM C-33 SAND
OR EQUIVALENT)
1.5' MEDIA
6'X6' OVERFLOW OUTLET
CONTROLSTRUCTURE -
RIM. ELEV 445.00
6" PERFORATED UNDER DRAIN
@ 0.5% SLOPE
V 100 YR ELEV. = 445.57
PROFILE VIEW
N.T.S
EL 447.00
3 MIN.
30" RCP OUTFLOW PIPE
436.79
1' GRAVEL LAYER
NOTICE TO CONTRACTOR:
SCARIFY BOTTOM PRIOR TO
INSTALLATION OF UNDER DRAIN SYSTEM
(DO NOT COMPACT)
PEAK CONTROL
POST -DEVELOPMENT
POST -ROUTING
ELEVATION
STORM EVENT
RUNOFF (CFS)
RUNOFF (CFS)
EL 442.25
TOP OF DAM
447.00
3" GRAVEL /STONE
SURFACE
0 0 0
2 YR
21.18
1.2
443.45
o
EL 442.00 (Top Sandfilter)
10 YR
28.93
3.17
444.40
25 YR
39.72
8.47
445.01
100 YR
60.86
45.75
445.57
FILTER FABRIC
PROVIDED
REQUIRED
ELEVATION
1.5' SAND FILTER MEDIA
DDV
10267 CF
8935 CF
443.10
(ASTM C-33 SAND OR
EQUIVALENT)
SAND FILTER
4500 SF
4468 SF
442.00
NOTE:
EL 440.5
1. SAND FILTER IS SIZED FOR DDV AND CHECKED FOR FREEBOARD.
`I �..
WASHED
12"
I`,I``,I`
rat
#57 STONE
`�' `I `tlt't .�I
2. PER GEO-TECHNICAL REPORT PREPARED BY TERRACON CONSULTANTS, INC. RALEIGH, NC.
EL439.5
THERE IS NOT ANY GROUND WATER ENCOUNTERED AT SAND FILTER 1 LOCATION.
FILTER FABRIC 6" PERFORATED
PIPE/GRAVEL
UNDER DRAIN SYSTEM
3. CONSTRUCTION OF SAND FILTER FACILITY AND STORM STRUCTURES
COMPLY WITH NC DEQ GUIDELINES.
4. MAINTENANCE AND INSPECTION REQUIREMENT COMPLY WITH
NC DEQ GUIDELINES.
TYPICAL SECTION
N.T.S
5. SAND FILTER SHALL BE INSPECTED ONCE A QUARTER AND WITHIN 24 HOURS
AFTER EVERY STORM EVENT GREATER THAN 1.0 INCHES (OR 1.5 INCHES IF IN A
COASTAL COUNTY). RECORD OF OPERATION AND MAINTENANCE WILL BE KEPT
IN A KNOWN SET LOCATION AND WILL BE AVAILABLE UPON REQUEST.
NCDEQ Stormwater BMP Manual
NCDEQ Stormwater BMP Manual
Table 1: Sample Operation and Maintenance Provisions fop, Sand Filters
Sand filters shall be inspected at least once a quarter and shall be maintained as needed to
remove surface sediment accumulation, trash, debris, and leaf litter to prevent the filter from
clogging. Sediment should be cleaned out of the fore bay/sed i me ntatio n chamber when it
Entire BMP"
Trash/debris is present.
Remove the trash/debris.
accumulates to a depth of more than 6 inches. During inspection, structures such as outlets
and flow diversions should be checked at least annually for damage or degradation. Figure 6
shows an example of a sand filter that is overdue for maintenance.
Adjacent pavement (if
Sediment is present on the
Sweep or vacuum the sediment
applicable)
pavement surface.
as soon as possible.
Figure 6. Sand Filter Overdue for Maintenance
Perimeter of sand filter
Areas of bare soil and/or
Regrade soil if necessary to
Clogged Sediment Chamber Clogged Sand Chamber
erosive gullies have formed.
remove the gully, and then
„
plant a ground cover and water
until it is established. Provide
Al
a
lime and a one-time fertilizer
All" ;Ul
application.
l
Vegetation is too short or too
Maintain vegetation at an
r l
long.
appropriate height.
(p t
Flow diversion structure
The structure is clogged.
Unclog the conveyance and
dispose of any sediment offsite.
a
The structure is damaged.
Make any necessary repairs or
replace if damage is too large
for repair.
r �
Forebay or pretreatment area
Sediment has accumulated to a
Search for the source of the
depth of greater than six
sediment and remedy the
inches.
problem if possible. Remove
the sediment and stabilize or
Important maintenance procedures for a sand filter include:
dispose of it in a location where
it will not cause impacts to
streams or the BMP.
1. Manage the drainage area to reduce the sediment load to the sand filter.
2. Clean out the sedimentation chamber or forebay whenever sediment depth exceeds six
Erosion has occurred.
Provide additional erosion
inches.
protection such as reinforced
turf matting or riprap if needed
3. At least once a year, skim the sand media.
to prevent future erosion
problems.
4. Replace the sand filter media whenever it fails to function properly after maintenance.
Weeds are present.
Remove theweeds, preferably
5. Inspect the sand filter at least quarterly. Any problems that are found shall be repaired
by hand. If a pesticide is used,
immediately.
wipe it on the plants rather than
spraying.
Maintain operation and maintenance records in a known set location. Operation and
maintenance records will be available upon request.
Filter bed and underdrain
Water is ponding on the surface
Check to see if the collector
collection system
for more than 24 hours after a
system is clogged and flush if
storm.
necessary. If water still ponds,
remove the top few inches of
C-6. Sand Filter
C-6. Sand Filter 7 Revised: 1-3-2017
8
Revised: 1-3-2017
SANDFILTER 1
NCDEQ Stormwater BMP Manual
'
filter bed media and replace. If
water still ponds, then consult
an expert.
Outlet device Clogging has occurred.
Clean out the outlet device.
Dispose of the sediment offsite.
The outlet device is damaged
Repair or replace the outlet
device.
Receiving water Erosion or other signs of
Contact the NC Division of
damage have occurred at the
Water Resources.
outlet.
C-6. Sand Filter 9 Revised: 1-3-2017
ALUMINUM GRATING R
REQUIRED, SEE DETAIL \
BELOW
6.00' 6.00'
RISER CREST
I E: 445.00
oa
r,.
2.0'Wxl.O'H WEIR
(^ ^
IE:444.00
TRASH RACK
W/#2 BAR
TOP OF SANDFILTER &
BOTTOM OF POND IE: 442.00
BOTTOM OF SANDFILTER IE: 440.50
6" ORIFICE
I E: 439.50
,
L 1 .N
r
<, 0" RG
l�l
INV
is
If
L ,N�
r
V�;,li muk� ml W��rii
y,
t, L L,
8'X8'X1.5'
CONC FOOTING
POND 1 / SANDFILTER - OUTLET STRUCTURE DETAIL
N.T.S.
NOTE:
GRATING SECTION SHALL BE FASTENED TO THE SUPPORTS WITH A
MINIMUM OF FOUR (4) SADDLE CLIP ANCHORS DESIGNED TO FIT OVER
TWO (2) BEARING BARS WITH STUD BOLTS, WASHERS AND NUTS.
ALUMINUM RIVETED GRATIN
(1-1 /8" X 7")
1 /4"
ALUMINUM ANGLE 3" x
2" x 3/8", LLV
1 /2"0 S.S. EXP. ANCHORS
@ 2'-0" O.C. 3 1 /2" MIN.
EMBEDMENT
INSIDE FACE OF CONC. BOX
GRATING DETAIL
NOT TO SCALE
3'
CARRY RIP RAP UP SPILLWAY
SIDES OF SPILLWAY
_ Fr
-SILT FENCE
CLASS 1 OR 2
RIP RAP
ZIP RAP APRON
.\ "ZOW
FA
(5' MIN.) �I
ELEVATION OF POND SPILLWAY
NOT TO SCALE
POND
SPILLWAY
SPILLWAY CREST
SPILLWAY CREST
ID
BOTTOM
LENGTH
ELEV.
NUMBER
WIDTH
(L)
(H)
SF 1
10'MIN.
10'
446.00
NOTE: CONTRACTOR TO REMOVE SILT FENCING
AFTER POST -CONSTRUCTION ACTIVITIES HAVE BEEN
COMPLETED, AND POND SLOPES HAVE BEEN STABILIZED.
POND 1 / SANDFILTER OVERFLOW EMERGENCY SPILLWAY
N.T.S.
4H:1 V
SIDE SLOPES
#5 WASHED STONE ON
OUTER SURFACE OF
BERM ACROSS SPILLWAY
NO STONE THRU BERM
O
m
n
CONSULTANTS:
Civil:
Stantec
801 Jones Franklin Road, Suite 300
Raleigh, NC 27606
ME_
SSC Engineering, Inc.
18207 Edison Ave.
Chesterfield, MO 63005
z
O
Q
O
O
U rn
� ti
CN
= U
� Z
UJ
J
m J
G >
UJ �
Z
U 0
UJ >UJ
J Q
UJ �
aco
UJ
..,;COOPERATIVE
BUILDING SOLUTIONS
M11
II 1V ' III "II III 'll 'W °"^I
II 111,11,°ro1u. II
C 0 I
,. �U"r��r.P'
PROFESSIONAL RECORD
' %
082
" 08/14/202
DATE
07-10-2020
PROJECT NUMBER
19.025
TITLE
SANDFILTER 1
DETAILS
SHEET
304
SEDIMENTATION CHAMBER
6"
#57 WASHED 2' RIP RAP
STONE
1�
3 MIN
INFLOW PIPE
3" GRAVEL / STONE SURFACE
SAND FILTER 2 BMP SUMMARY CHART
CLEAN -OUT
(PVC PIPE
W / GLUED CLEAN -OUT FITTINGS
AND SCREW TYPE CAP)
PEAK CONTROL
STORM EVENT
POST -DEVELOPMENT
RUNOFF (CFS)
POST -ROUTING
RUNOFF (CFS)
ELEVATION
TOP OF DAM
450.00
2 YR
5.8
0.89
446.88
10 YR
10.6
1.14
447.46
25 YR
14.48
1.31
447.93
100 YR
22.07
5.30
448.56
PROVIDED
REQUIRED
ELEVATION
DDV
6713 CF
2559 CF
446.70
SAND FILTER
1500 SF
1200 SF
446.00
NOTE:
1. SAND FILTER IS SIZED FOR DDV AND CHECKED FOR FREEBOARD.
2. PER GEO-TECHNICAL REPORT PREPARED BY TERRACON CONSULTANTS, INC. RALEIGH, NC.
THERE IS NOT ANY GROUND WATER ENCOUNTERED AT SAND FILTER 1 LOCATION.
3. CONSTRUCTION OF SAND FILTER FACILITY AND STORM STRUCTURES
COMPLY WITH NC DEQ GUIDELINES.
4. MAINTENANCE AND INSPECTION REQUIREMENT COMPLY WITH
NC DEQ GUIDELINES.
5. SAND FILTER SHALL BE INSPECTED ONCE A QUARTER AND WITHIN 24 HOURS
AFTER EVERY STORM EVENT GREATER THAN 1.0 INCHES (OR 1.5 INCHES IF IN A
COASTAL COUNTY). RECORD OF OPERATION AND MAINTENANCE WILL BE KEPT
IN A KNOWN SET LOCATION AND WILL BE AVAILABLE UPON REQUEST.
3" GRAVEL/STONE
SURFACE
.448.00
RIP RAP BERM
(CLASS B)
SANFILTER MEDIA
(ASTM C-33 SAND
OR EQUIVALENT)
1.5' MEDIA
4'X4' OVERFLOW OUTLET
CONTROLSTRUCTURE -
RIM. ELEV 448.50
V 100 YR ELEV. = 448.56
2.0' W x 0.5' H rec weir
DDV ELEV. = 446.70 \ \ CL +' 0.UU
6" PERFORATED UNDER DRAIN
@ 0.5% SLOPE
PROFILE VIEW
N.T.S
EL 450.00
3 MIN.
1F-j
18" RCP OUTFLOW PIPE
ELEV 443.5
I' GRAVEL LAYER
NOTICE TO CONTRACTOR:
SCARIFY BOTTOM PRIOR TO
INSTALLATION OF UNDER DRAIN SYSTEM
(DO NOT COMPACT)
ALUMINUM GRATING R
REQUIRED, SEE DETAIL \
BELOW
4°00' 4°00'
INV i
EL 446.25
3" GRAVEL / STONE
SURFACE 1 2�
EL 446.00 (Top Sandfilter)�_ i ,r�
FILTER FABRIC
1.5' SAND FILTER MEDIA
(ASTM C-33 SAND OR 6'X6'X0.50'
EQUIVALENT) CONC FOOTING
EL 444.5
�y � WASHED
12" ���.; #57STONE
EL 443.5
FILTER FABRIC 6" PERFORATED PIPE / GRAVEL
UNDER DRAIN SYSTEM
TYPICAL SECTION
N.T.S
SANDFILTER 2
POND 1 / SANDFILTER - OUTLET STRUCTURE DETAIL
N.T.S.
NOTE:
GRATING SECTION SHALL BE FASTENED TO THE SUPPORTS WITH A
MINIMUM OF FOUR (4) SADDLE CLIP ANCHORS DESIGNED TO FIT OVER
TWO (2) BEARING BARS WITH STUD BOLTS, WASHERS AND NUTS.
ALUMINUM RIVETED GRATIN
(1-1/8" X 7")
ALUMINUM ANGLE 3" x
2" x 3/8", LLV
1 /2"0 S.S. EXP. ANCHORS
@ 2'-0" O.C. 3 1/2" MIN.
EMBEDMENT
INSIDE FACE OF CONC. BOX
GRATING DETAIL
NOT TO SCALE
/4"
NCDEQ Stormwater BMP Manual NCDEQ Stormwater BMP Manual NCDEQ Stormwater BMP Manual
IN a
i n to n rice Table 1: Sarrafale Operation and Maintenance Provisions for Sand Filters
filter bed media and replace. If
water still ponds, then consult
Sand filters shall be inspected at least once a quarter and shall be maintained as needed to • ° " ®, , , e ° an expert.
remove surface sediment accumulation, trash, debris, and leaf litter to prevent the filter from �1N 3'
clogging. Sediment should be cleaned out of the fore bay/sed i me ntatio n chamber when it Entire BMPTrash/debris is present. Remove the trash/debris. Outlet device Clogging has occurred. Clean out the outlet device. CARRY RIP RAP UP SPILLWAY LENGTH/-4H:IV
'
accumulates to a depth of more than 6 inches. During inspection, structures such as outlets Dispose of the sediment offsite. SIDES OF SPILLWAYS SIDE SLOPES
and flow diversions should be checked at least annually for damage or degradation. Figure 6
shows an example of a sand filter that is overdue for maintenance. Adjacent pavement (if Sediment is present on the Sweep or vacuum the sediment
applicable] pavement surface. as soon as possible. The outlet device is damaged Repair or replace. the outlet I Ogg
device. / 0 T
2"
Figure 6: Sand Filter Overdue for 1lrlaiarteaaaapce x o
Perimeter of sand filter Areas of bare soil and/or Regrade soil if necessary to 1 o0 0
Clogged Sediment Chamber Clog
ged Sand Chamber erosive gullies have formed. remove the gully, and then Receiving water Erosion or other signs of Contact the NC Division of SILT FENCE
99 99 damage have occurred at the Water Resources. I
r plant a ground cover and water V x #5 WASHED STONE ON
2 until it is established. Provide outlet. CLASS 1 OR 2
lime and cone -time fertilizer �
application.
3 x RIP RAP H OUTER SURFACE OF
TH IP RAP APRON BERM ACROSS SPILLWAY
Vegetation is too short or too Maintain vegetation at an NO STONE THRU BERM
e
long, appropriate height.
ER
�s lr t Flow diversion structure The structure is clogged. Unclog the conveyance and 0�.
dispose of any sediment offsite.
F�Ow (5' MIN.)
(, The structure is damaged. Make any necessary repairs or \
' replace if damage is too large x_ x%` ELEVATION OF POND SPILLWAY
for repair.
NOT TO SCALE
Forebay or pretreatment area Sediment has accumulated to a Search for the source of the
depth of greater than six sediment and remedy the
inches. problem if possible. Remove
the sediment and stabilize or
Important maintenance procedures for a sand filter include: dispose of it in a location where POND SPILLWAY SPILLWAY CREST SPILLWAY CREST
it will not cause impacts to
1. Manage the drainage area to reduce the sediment load to the sand filter. streams or the BMP. ID BOTTOM LENGTH ELEV.
NUMBER WIDTH
W (H)
2. Clean out the sedimentation chamber or forebay whenever sediment depth exceeds six Erosion has occurred. Provide additional erosion
inches. protection such as reinforced , ,
turf matting or riprap if needed SF 2 10 MIN. 10 449.00
3. At least once a year, skim the sand media. to prevent future erosion
problems.
4. Replace the sand filter media whenever it fails to function properly after maintenance.
Weeds are present. Remove the weeds, preferably NOTE: CONTRACTOR TO REMOVE SILT FENCING
5. Inspect the sand filter at least quarterly. Any problems that are found shall be repaired by hand. If a pesticide is used, AFTER POST -CONSTRUCTION ACTIVITIES HAVE BEEN
immediately. wipe it on the plants rather than COMPLETED, AND POND SLOPES HAVE BEEN STABILIZED.
spraying.
Maintain operation and maintenance records in a known set location. Operation and
maintenance records will be available upon request. Filter bed and underdrain Water is ponding on the surface Check to see if the collector
collection system, for more than 24 hours after a system is clogged and flush if
storm. necessary. If water still ponds,
remove the top few inches of
C-6. Sand Filter 7 Revised: 1-3-2017
C-6. Sand Filter 8 Revised: 1-3-2017
C-6. Sand Filter 9 Revised: 1-3-2017
POND 1 / SANDFILTER OVERFLOW EMERGENCY SPILLWAY
N.T.S.
O
W
m
.E
n
CONSULTANTS:
C=
Stantec
801 Jones Franklin Road, Suite 300
Raleigh, NC 27606
MEP/FP:
SSC Engineering, Inc.
18207 Edison Ave.
Chesterfield, MO 63005
Z
O
Q
O
O
U rn
CN
= U
� Z
LLI J
m J
G >
LLI U)
Z
U 0::D
U LU
LLI >
J Q
LLI LLI �
a co
N
..,;COOPERATIVE
BUILDING SOLUTIONS
ll E ' III L.. III � 41, 'W
ILI 1b W!."'1p. MIL.. F
A� D D [��������� r,0,J h#'2
0 7 / 1 I..L/,�:? O�:? o
J �l," m C 0 I S
I..,O:',r,/ " ,mf4 / ,2 0�r2 0
PROFESSIONAL RECORD
t,rttlllfilllll7
' % CaA
082
" 08/14/202
DATE
07-10-2020
PROJECT NUMBER
19.025
TITLE
SANDFILTER 2
DETAILS
SHEET
305
1
VEGETATIVE FILTER
STRIP
VEGETATIVE FILTER
STRIP
V I 20'
1 1
1
i rvv v111�11.� II
o'A'
lJ
r
30 I I ;;;;°Prrra�Gara
1
1
I
1
SWALE / FORBAY J 1
1
LEVELSPREADER 1
1
#57 STONE 1
0
LEVEL SPREADER FILTER STRIP 2 PLAN VIEW ; I
z�F
� M
LEVEL SPREADER FILTER STRIP 1 SECTION A -A
N.T.S.
NOTE:
1. LEVEL SPREADER_ FILTER STRIP IS SIZED FOR HANDLE THE FLOW
DURING 10-YEAR STORM EVENT.
2. CONSTRUCTION OF LEVEL SPREADER_ FILTER STRIP COMPLY WITH
NCDEQ STORMWATER BMP MANUAL C-9.
3. MAINTENANCE AND INSPECTION REQUIREMENT COMPLY WITH NCDEQ
STORMWATER BMP MANUAL C-9.
21
.
LEVEL SPREADER FILTER STRIP 1 SECTION B-B
N.T.S.
O
m
.E
a
n
ARCHITECT:
16150 Main Circle Drive, Suite 100
St. Louis, MO 63017
(636) 449-1175 / fax (636) 449-1176
CONSULTANTS:
Civil:
Stantec
801 Jones Franklin Road, Suite 300
Raleigh, NC 27606
MEP/FP:
SSC Engineering, Inc.
18207 Edison Ave.
Chesterfield, MO 63005
E LI wIII'°°i
I i
Da [[µµµµ r,�U,J
#ry2
7 /1 � / ?� 2y�°�Iu
phA
yy
Iu,
��y Iu
%N�i/ 14f,�N,��%��iN
PROFESSIONAL RECORD
' \ GA'r
082
08/14/202
DATE
07-10-2020
PROJECT NUMBER
19.025
TITLE
LEVEL SPREADER
_FILTER STRIP DETAILS
SHEET
306