January 27, 2004
Mr Gordon H Kolb, President
G H K Developments, Inc
170 Broadway Street, Suite 227
New Orleans, LA 70118
Subject Permit No SW8 031031
Walgreens @ 17th Street & S College Road
High Density Stormwater Project
New Hanover County
Dear Mr Kolb
The Wilmington Regional Office received a complete Stormwater Management Permit
Application for WaIgreens @ 17t" Street & S College Road on January 21, 2004 Staff review
of the plans and specifications has determined that the project, as proposed, will comply with the
Stormwater Regulations set forth in Title 15A NCAC 2H 1000 We are forwarding Permit No
SW8 031031 dated January 27, 2004, for the construction of Walgreens @ 17th Street & S
College Road
This permit shall be effective from the date of issuance until January 27, 2014, and shall be
subject to the conditions and limitations as specified therein Please pay special attention to the
Operation and Maintenance requirements in this permit Failure to establish an adequate system
for operation and maintenance of the stormwater management system will result in future
compliance problems
If any parts, requirements, or limitations contambd in this permit are unacceptable, you have the
right to request an adludicatory hearing upon written request within thirty (30) days following
receipt of this permit This request must be in the form of a written petition, conforming to
Chapter 150B of the North Carolina General Statutes, and filed with the Office of Administrative
Hearings, P O Drawer 27447, Raleigh, NC 27611-7447 Unless such demands are made this
permit shall be final and binding
If you have any questions, or need additional information concerning this matter, please contact
Laurie Munn, or me at (910) 395-3900
Sincerely,
Rick Shiver
Water Quality Regional Supervisor
RSS/ Ism S 1WQSISTORMWATIPERMIT1031031 jan04
cc John S Tunstall, P E
Tony Roberts County Building Inspections
Beth E Wetherill, New Hanover County Engineering
Laurie Munn
Wilmington Regional Office
Central Files
N C Division of Water Quality 127 Cardinal Drive Extension (910) 395-3900
Wilmington Regional Office Wilmington, NC 28405 (910) 350-2004 Fax
Customer Service
1 800 623-7748
r
State Stormwater Management Systems
Permit No SW8 031031
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
STATE STORMWATER MANAGEMENT PERMIT
HIGH DENSITY DEVELOPMENT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North
Carolina as amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
G HK Developments, Inc
Walgreens @ 17'h Street & S College Road
New Hanover County
FOR THE
construction, operation and maintenance of an infiltration trench in compliance with the
provisions of 15A NCAC 2H 1000 (hereafter referred to as the "stormwater rules') and the
approved stormwater management plans and specifications and other supporting data as attached
and on file with and approved by the Division of Water Quality and considered a part of this
permit Portions of this project include the construction of impervious areas with the runoff to be
treated in an offsrte permitted stormwater facility This portion of the runoff will be routed to a
wet detention pond operated and maintained by University Group, Inc , under the terms and
conditions set forth in Permit No SW8 981023 Modification
This permit shall be effective from the date of issuance until January 27, 2014, and shall be
subject to the following specified conditions and limitations
I. DESIGN STANDARDS
1 This permit is effective only with respect to the nature and volume of stormwater
described in the application and other supporting data
2 The total allowable built -upon area for this proLect is 58,270 square feet of impervious
area Runoff associated with this project from Drainage Area 1 has been approved to be
discharged into a stormwater management system permitted under Stormwater
Management Permit No SW8 981023, as described on page 3 of this permit, the Project
Data Sheet The built -upon area allotted to this development by Stormwater Management
Permit No SW8 981023 is 30,360 square feet This project proposes 30,360 square feet
The stormwater system for Drainage Area 2 has been approved for the management of
stormwater runoff as described on page 4 of this permit, the Project Data Sheet The
stormwater control has been designed to handle the runoff from 27,910 square feet of
impervious area This system must be operated with a vegetated filter
3 The tract will be limited to the amount of built -upon area indicated on pages 3 and 4 of
this permit, and per approved plans
4 All stormwater collection and treatment systems must be located in either dedicated
common areas or recorded easements The final plats for the project will be recorded
showing all such required easements, in accordance with the approved plans
5 The runoff from all built -upon area within the permitted drainage area of this project must
be directed into the permuted stormwater control system A permit modification must be
submitted and approved prior to the construction of additional built -upon area from
outside of the approved drainage area
2
State Stormwater Management Systems
Permit No SW8 031031
e
0
DIVISION OF WATER QUALITY
PROJECT DESIGN DATA SHEET
DRAINAGE AREA 1— SERVED BY OFFSITE SYSTEM
Project Name 17th Street and College Road Project
Permit Number SW8 981023 Modification
Location New Hanover County
Applicant Mr Terry Turner, President
Mailing Address University Group, Inc
1904 Eastwood Road, Suite 212
Wilmington, NC 28403
Application Date
December 7, 2001
Name of Receiving Stream/Index #
Cape Fear River / Barnards Creek / 18-80
Classification of Water Body
"C Sw"
If Class SA, chlonde sampling results
n/a
Pond Depth, feet
55
Permanent Pool Elevation, FMSL
40
Drainage Area, acres
1123
Total Impervious Surfaces, ft2:
415,931
Bank of Wilmington (Existing)
+ N
Buildings, ft2
3,540
Parking, ft2
69,623
Sidewalks, ft2
3,892
Future Development, ft2
308,516
SW8 031031, ft':
30,360
Offsite Area entering Pond, ft2
None, per engineer
Required Surface Area, ft2
27,158
Provided Surface Area, ftz
27,448
Required Storage Volume, ft3
35,885
Provided Storage Volume, ft3
43,854
Temporary Storage Elevation, FMSL 415
Controlling Orifice 3"cp pipe
3
State Stormwater Management Systems
Permit No SW8 031031
DIVISION OF WATER QUALITY
PROJECT DESIGN DATA SHEET
DRAINAGE AREA 2
Project Name
Permit Number
Location
Applicant
Mailing Address
Application Date
Receiving Stream/River Basin
Stream Index Number
Classification of Water Body
Drainage Area, acres
Onsite, sq ft
Offsite, sq ft
Total Impervious Surfaces, sq ft
Trench Dimensions, LxWxH, feet
Piping (12" perforated piping)
TSS removal efficiency
Trench Bottom Elevation, FMSL
Permitted Storage Volume, ft3
Temporary Storage Elevation, FMSL
Type of Soil
Expected Infiltration Rate
SHWT Elevation, FMSL
Time to draw down
Walgreens @ 171h St and S College Rd
SW8 031031
New Hanover County
Mr Gordon H Kolb
G H K Developments, Inc
170 Broadway Street, Suite 227
New Orleans, LA 70118
January 21, 2004
Barnards Creek / Cape Fear
"C Sw"
166
35,714
none
30,360
400x lOx2
800 linear feet
85% (a 30' vegetated filter is required)
425
2,682
440
Sand
37 5 in/hr
405
< 1 hour
4
State Stormwater Management Systems
Permit No SW8 031031
IL SCHEDULE OF COMPLIANCE
The stormwater management systems shall be constructed in its entirety, vegetated and
operational for its intended use prior to the construction of any built -upon surface
2 During construction, erosion shall be kept to a minimum and any eroded areas of the
system will be repaired immediately
3 For Drainage Area 1, the University Group, Inc, and for Drainage Area 2, the penrirttec
shall at all times provide the operation and maintenance necessary to assure the permitted
stormwater system functions at optimum efficiency The approved Operation and
Maintenance Plan must be followed in its entirety and maintenance must occur at the
scheduled intervals including, but not limited to
a Semiannual scheduled inspections (every 6 months)
b Sediment removal
C. Mowing and revegetation of slopes and the vegetated filter
d Immediate repair of eroded areas
e Maintenance of all slopes in accordance with approved plans and specifications
f Debris removal and unclogging of outlet structure, onfice device, flow spreader,
catch basins and piping
g Access to the outlet structure must be available at all times
4 Records of maintenance activities must be kept and made available upon request to
authorized personnel of DWQ The records will indicate the date, activity, name of
person performing the work and what actions were taken
5 The facilities shall be constructed as shown on the approved plans This permit shall
become voidable unless the facilities are constructed in accordance with the conditions of
this permit, the approved plans and specifications, and other supporting data
6 Upon completion of construction, prior to issuance of a Certificate of Occupancy, and
prior to operation of this permitted facility, a certification must be received from an
appropriate designer for each system installed certifying that the permitted facility has
been installed in accordance with this permit, the approved plans and specifications, and
other supporting documentation Any deviations from the approved plans and
specifications must be noted on the Certification A modification may be required for
those deviations
7 If the stormwater system was used as an Erosion Control device, it must be restored to
design condition prior to operation as a stormwater treatment device, and prior to
occupancy of the facility
8 The permittee shall submit to the Director and shall have received approval for revised
plans, specifications, and calculations prior to construction, for any modification to the
approved plans, including, but not Iimited to, those listed below
a Any revision to any item shown on the approved plans, including the stormwater
management measures, built -upon area, details, etc
b Project name change
c Transfer of ownership
d Redesign or addition to the approved amount of built -upon area or to the drainage
area
e Further subdivision, acquisition, or sale of all or part of the project area The
project area is defined as all property owned by the permittee, for which
Sedimentation and Erosion Control Plan approval or a CAMA Major permit was
sought
f Filling in, altering, or piping of any vegetative conveyance shown on the approved
plan
5
State Stormwater Management Systems
Permit No SW8 031031
9 The permittee shall submit final site layout and grading plans for any permitted future
areas shown on the approved plans, prior to construction If the proposed BUA exceeds
the amount permitted under this permit, a modification to the permit must be submitted
and approved prior to construction
10 A copy of the approved plans and specifications shall be maintained on file by the
Permittee for a minimum of ten years from the date of the completion of construction
11 At least 30 days prior to the sale or lease of any portion of the property, the permittee
shall notify DWQ and provide the name, mailing address and phone number of the
purchaser or leasee An access/maintenance easement to the stormwater facilities shall be
granted in favor of the permittee if access to the stormwater facilities will be restricted by
the sale or lease of any portion of the property
12 The permittee must maintain compliance with the proposed built -upon area and ensure
that the runoff from all the built -upon is directed into the permitted system
13 The Director may notify the permittee when the permitted site does not meet one or more
of the minimum requirements of the permit Within the time frame specified in the notice,
the permittee shall submit a written time schedule to the Director for modifying the site to
meet minimum requirements The permittee shall provide copies of revised plans and
certification in wnting to the Director that the changes have been made
14 The permittee must maintain the current permitted drainage area No additional runoff
from outside of the permitted drainage area boundary may enter the permitted stormwater
facilities without first applying for and receiving a permit modification
III. GENERAL CONDITIONS
This permit is not transferable except after notice to and approval by the Director In the
event of a change of ownership, or a name change, the permittee must submit a formal
permit transfer request to the Division of Water Quality, accompanied by a completed
name/ownership change form, documentation from the parties involved, and other
supporting materials as may be appropnate The approval of this request will be
considered on its ments and may or may not be approved The permittee is responsible
for compliance with all permit conditions until such time as the Division approves the
transfer request
2 Failure to abide by the conditions and limitations contained in this permit may subject the
Permittee to enforcement action by the Division of Water Quality, in accordance with
North Carolina General Statute 143-215 6A to 143-215 6C
3 The issuance of this permit does not preclude the Permittee from complying with any and
all statutes, rules, regulations, or ordinances which may be imposed by other government
agencies (local, state, and federal) which have jurisdiction
4 In the event that the facilities fail to perform satisfactorily, including the creation of
nuisance conditions, the Permittee shall take immediate corrective action, including those
as may be required by this Division, such as the construction of additional or replacement
stormwater management systems
5 The permittee grants DENR Staff permission to enter the property during normal business
hours for the purpose of inspecting all components of the permitted stormwater
management facility
6 The permit may be modified, revoked and reissued or terminated for cause The filing of
a request for a permit modification, revocation and reissuance or termination does not
stay any permit condition
State Stormwater Management Systems
Permit No SW8 031031
7 Unless specified elsewhere, permanent seeding requirements for the stormwater control
must follow the guidelines established in the North Carolina Erosion and Sediment
Control Planning and Design Manual
8 Approved plans and specifications for this project are incorporated by reference and are
enforceable parts of the permit
9 The permittee shall notify the Division any name, ownership or mailing address changes
within 30 days
Permit issued this the 27th day of January 2004
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
Alan W Klimek, P E ,Director
1-0 Division of Water Quality
By Authority of the Environmental Management Commission
7
State Stormwater Management Systems
Permit No SWS 031031
Walgreens @ 17`" Street and S College Road
Stormwater Permit No SW8 031031
New Hanover County
Designer's Certification
I, , as a duly registered
in the State of North Carolina, having been authorized to observe (periodically/weekly/full time)
the construction of the project,
(Project)
for (Project Owner) hereby state that, to the best of
my abilities, due care and diligence was used in the observation of the project construction such
that the construction was observed to be built within substantial compliance and intent of the
approved plans and specifications
The checklist of items on page 2 of this form is included in the Certification
Noted deviations from approved plans and specification
SEAL
Signature
Registration Number
Date
State Stonnwater Management Systems
Permit No SW8 031031
Certification Requirements
1 The drainage area to the system contains approximately the permitted acreage
2 The drainage area to the system contains no more than the permitted amount of
built -upon area
3 AlI the built -upon area associated with the project is graded such that the runoff
drains to the system
4 The outlet/bypass structure elevations are per the approved plan
S The outlet structure is located per the approved plans
6 Trash rack is provided on the outlet/bypass structure
7 All slopes are grassed with permanent vegetation
8 Vegetated slopes are no steeper than 3 1
9 The inlets are located per the approved plans and do not cause short-circuiting of
the system
10 The permitted amounts of surface area and/or volume have been provided
11 Required drawdown devices are correctly sized per the approved plans
12 All required design depths are provided
13 All required parts of the system are provided, such as a vegetated shelf, and a
forebay
14 The overall dimensions of the system, as shown on the approved plans, are
provided
cc NCDENR-DWQ Regional Office
New Hanover County Building Inspections
0
A&K #03035-Mod
nr:>~rr_r~_r rc>a_nin v
Date Received
Fee Paid
Permit Numher
0- - 3
L 3
D a
State of North Carolina
Department of Environment and Natural Resources
Division of Water Quality
STORMWATER MANAGEMENT PERMIT APPLICATION FORM
This form may be photocopied for use as an original
I GENERAL INFORMATION
I Applicants name (specify the name of the corporation, individual, etc who owns the project)
G H K Developments, Inc
Print Owner/Signing Official's name and title (person legally responsible for facility and compliance)
Gordon H Kolb, President
3 Mailing Address for person listed in item 2 above
170 Broadway Street, Suite 227
City New Orleans State LA Zip 70118
Telephone Number (504) 866-7300
4 Project Name (subdivision, facility, or establishment name - should be consistent with project name on
plans, specifications, letters, operation and maintenance agreements, etc }
Walgreens c@ 17th Street & S College Road
Location of Project (street address)
3720 S College Road
City Wilmington County New Hanover
6 Directions to project (from neArest major intersection)
N
Site is located on S College Road approximately 500 feet south of the intersection of 17th St _
and S College Road
7 Latitude 340 11' 00"
Longitude 770 53' 30"
of project
Contact person who can answer Questions about the project
Name John S Tunstall, P E Telephone Number (910) 343-9653
II PERMIT INFORMATION
Specify whether project is (check one)
Form SWU-101 Version 3 99
X New
Page 1 of 4
Renewal X Modification
C
2 If this application is being submitted as the result of a renewal or modification to an existing permit, list the
Existing permit number SW8 981023 Mod And its issue date (if known) January 8, 2002
3 Specify the type of project (check one)
Low Density X High Density Redevelop General Permit Other
4 Additional Project Requirements (check applicable blanks)
CAMA Major X Sedimentation/Erosion Control 404/401 Permit NPDES Stormwater
Information on required state permits can be obtained by contacting the Customer Service Center at
1-877-623-6748
111 PROJECT INFORMATION
I In the space provided below, summarize how stormwater will be treated Also attach a detailed narrative
(one to two pages) describing stormwater management for the project
Stormwater for the east portion of the site will be treated by an underground infiltrations stem
(0 84 AM and the stormwater allocated for Fulton Station Lot 5 will be directed to Fulton Station
regional pond (0 82 AC) _
2 Stormwater runoff from this project drains to the Cape Fear River Basin
3 Total Project Area 1 66 AC 4 Project Built Upon Area 78 24 %
5 How many drainage areas does the project have9 2
6 Complete the following information for each drainage area If there are more than two drainage areas in the
project, attach an additional sheet with the information for each area provided in the same format as below
I nt -;; Fiiitnn Stntinn Pnnrl SWR QR1W.3 C)nSitP Infiltratinn System
Basin Information
Drainage Area 1
Drainage Area 2
ReceivinE Stream Name
Banards Creek
Banards Creek
Receiving Stream Class
C-SW
C-SW
Drainage Area
35,719 SF 10 82 AC
36,590 SF 10 84 AC
Existing Impervious * Area
0
0
Proposed Impervious* Area
30,360 SF 10 69 AC
27,910 SF / 0 64 AC
% Impervious* Area (total)
85%
76 3%
Impervious* Surface Area
Drainage Area 1
Drainage Area 2
On -site Buildings
14,550 SF 10 33 AC
-------
On-site Streets
15,810 SF 10 36 AC
6,637 SF 1 61 AC
On -site Parkin
On -site Sidewalks
315 SF 1 007 AC
1,352 SF 1 03 AC
Other on-site
-------
-------
Off-s ite
-------
-------
Total 30,360 SF 10 69 AC
Total 27,910 SF 10 64 AC
" Impervious area is defined as the built upon area including, but not limited to, buildings, roads, parking areas
sidewalks, gravel areas, etc
Form SWU-101 Version 3 99 Page 2 of 4
7 How was the off -site impervious area listed above derived?
NIA
IV DEED RESTRICTIONS AND PROTECTIVE COVENANTS
The following italicized deed restrictions and protective covenants are required to be recorded for all
subdivisions, outparceis and future development prior to the sale of any lot If lot sizes vary significantly, a
table listing each lot number, size and the allowable built -upon area for each lot must be provided as an
attachment
The following covenants are intended to ensure ongoing compliance with state stormwater management permit
number NIA as issued by the Division of Water Quality These covenants may
not be changed or deleted without the consent of the State
2 No more than NIA square feet of any lot shall be covered by structures or impervious materials
Impervious materials include asphalt, gravel, concrete, brick, stone, slate or similar material but do not include
wood decking or the water surface of swimming pools
3 Swales shall not be filled in, piped, or altered except as necessary to provide driveway crossings
4 Built -upon area in excess of the permitted amount requires a state stormwater management permit modification
prior to construction
A11 permitted runoff from outparcels or future development shall be directed into the permitted stormwater control
system These connections to the stormwater control system shall be performed in a manner that maintains the
integrity and performance of the system as permitted
By your signature below, you certify that the recorded deed restrictions and protective covenants for this project
shall include all the applicable items required above, that the covenants will be binding on all parties and persons
claiming under them, that they will run with the land, that the required covenants cannot be changed or deleted
without concurrence from the State, and that they will be recorded prior to the sale of any lot
V SUPPLEMENT FORMS
The applicable state stormwater management permit supplement form(s) listed below must be submitted for
each BMP specified for this project Contact the Stormwater and General Permits Unit at (919) 733-5083 for
the status and availability of these forms
Form SWU-102
Form SWU-103
Form SWU-104
Form SWU-105
Form SWU-106
Form SWU-107
Form SWU-108
Form SWU-109
Wet Detention Basin Supplement
Infiltration Basin Supplement
Low Density Supplement
Curb Outlet System Supplement
Off -Site System Supplement
Underground Infiltration Trench Supplement
Neuse River Basin Supplement
Innovative Best Management Practice Supplement
Form SWU-101 Version 3 99 Page 3 of 4
VI SUBMITTAL. REQUIREMENTS
Only complete application packages will be accepted and reviewed by the Division of Water Quality (DWQ).
A complete package includes all of the items listed below. The complete application package should be
submitted to the appropriate DWQ Regional Office.
Please indicate that you have provided the following required information by initialing in the space provided
next to each item
• Original and one copy of the Stormwater Management Permit Application Form
• One copy of the applicable supplement form(s) for each BMP
• Permit application processing fee of $420 (payable to NCDENR)
• Detailed narrative description of stormwater treatment / management
• Two copies of plans and specifications, including
- Development / Project name
- Engineer and firm
- Legend
- North arrow
- Scale
- Revision number & date
Mean high water line
- Dimensioned property I project boundary
Location map with named streets or NCSR numbers
Original contours, proposed contours, spot elevations, finished floor elevations
- Wetlands delineated, or a note on plans that none exist
- Existing drainage (including off -site), drainage easements, pipe sizes, runoff calculations
- Drainage areas delineated
Vegetated buffers (where required)
VII AGENT AUTHORIZATION
If you wish to designate authority to another individual or firm so that they may provide information on your
behalf, please complete this section
John S Tunstall, P E
Designated agent (individual or firm) Andrew & Kuske Consulting Engineers, Inc
Mailing Address 902 Market Street
City Wilmi
Phone (910) 343-9653
VM. APPLICANT'S CERTIFICATION
State NC Zip
Fax (910) 343-9604
28401
1, (print or type name of person listed to General Information, item 2) Gordon H Kolb, President ,
Certify that the information included on this permit application form is, to the best of my knowledge, correct and
that the project will be const cted in conformance with the approved plans, that the required deed restrictions and
protective covenants will b ded, and that the proposed project complies with the requirements of 15A NCAC
2H 1000 A
Signature
Form SWU-101 Version 3 99 Page 4 of 4
Date
A&K #03035
Permit No ,S W 2 Q , l�, 03 1
State of North'Carolma (to be provided by DWQ)
Department of Environment and Natural Resources
Division of Water Quality
STORMWATER MANAGEMENT PERMIT APPLICATION FORM
UNDERGROUND INFILTRATION TRENCH SUPPLEMENT
This form may be photocopied for use as an original
DWQ Stormwater Management Plan Review
A complete stormwater management plan submittal includes a stormwater management permit application, an
underground trench supplement for each system, design calculations, and plans and specifications showing all
stormwater conveyances and system details
I. PROJECT INFORMATION
Project Name Walgreens @ r Street & S College Road
Contact Person John S Tunstall, P E Phone Number (910) 343-9653
For projects with multiple infiltration systems, a supplement form must be completed for each system This
worksheet applies to Trench 1 in Drainage Area 1
(from plans) (from Form SWU--101)
H- DESIGN INFORMATION (attach supporting calculations/documentation)
Soils Report Summary (based upon an actual field investigation and soil borings)
Soil Type
Infiltration Rate
SHWT Elevation
Trench Design Parameters
Design Volume
Design Storm
Drawdown Time
Perforated Pipe Size
Perforated Pipe Length
No Observation Wells
Stone Type (if used)
Stone Void Ratio
Sand
Design 21 5 ®m/hr or ❑cf/hr/sf (check appropriate units) Act 37 5" t HR
405 friisl (Seasonal High Water Table elevation)
2,505
c f
inch event
1
for others)
00156
days
(2) 12"
inch diameter
400
ft
(1 5 inch event for SA waters, 1 inch event
0 (may be required on a case —by-case basis)
#4 Washed Stone
40%
Trench Elevations (in feet mean seal level)
Bottom Elevation
425 fmsl
Storage/Overflow Elevation 44 0 fmsl
Form SWU-107 Version 3 99 Page] of4
Trench Dimensions
Height
Width
2 ft Length
400 ft
10 ft Volume Provided 2,682 cu ft
III. REQUIRED ITEMS CHECKLIST
The following checklist outlines design requirements per the Stormwater Best Management Practices Manual
(N C Department of Environment, Health and Natural Resources, February 1999) and Administrative Code
Section 15 A NCAC 214 1008
Initial in the space provided to indicate the following design requirements have been met and supporting
documentation is attached If the applicant has designated an agent in the Stormwater Management Permit
Application Form, the agent may initial below If a requirement has not been met, attach justification
Applicants Initials
NIA
a System is located 50 feet from class SA waters and 30 feet from other surface waters
b System is located at least 100 feet from water supply wells
c Bottom of system is at least 2 feet above the seasonal high water table
d Bottom of the system is 3 feet above any bedrock or impervious soil horizon
e
Off-line system, runoff in excess of the design volume bypasses the system (bypass detail
provided)
System is designed to draw down the design storage volume to the proposed bottom
elevation under seasonal high water conditions within five days based upon infiltration
through the bottom only (a hydrogeologic evaluation may be required)
g Soils have a minimum hydraulic conductivity of 0 52 inches per hour
h System is not sited on or in fill material or DWQ approval has been obtained
Plans ensure that the installed system will meet design specifications (constructed or
restored) upon initial operation once the project is complete and the entire drainage area is
stabilized
System is sized to take into account the runoff at the ultimate built -out potential from all
surfaces draining to the system, including any off -site drainage
k System is located in a recorded drainage easement for the purposes of operation and
maintenance and has recorded access easements to the nearest public right-of-way
1 System capture and infiltrates the runoff from the first 10 inch of rainfall (1 5 inch event
for areas draining to SA waters)
m Drainage area for the device is less than 5 acres
n A pretreatment device (filter strip, grassed Swale, ediment trap etc ) is provided
o Trench bottom is covered with a layer of clean sand to an average depth of 4 inches
p Sides of the infiltration trench are lined with geotextile fabric
q Rock used is free of fines (washed stone) and has a large void ratio
r Side to bottom area ratio is less than 4 1
Form SWU-107 Version 3 99 Page 2 of 4
s Observation well(s) are provided (case -by -case basis)
t Vegetated filter is provided for overflow (50 feet for SA waters, 30 feet for other waters)
and detail is shown on plans
u A benchmark for checking sediment accumulation is provided 150T CS
IV. INFILTRATION BASIN OPERATION AND MAINTENANCE AGREEMENT
1 After every runoff producing rainfall event and at least monthly inspect the bypass/overflow structure for
blockage and deterioration and the infiltration system for erosion, trash accumulation, grass cover, and general
condition
2 Repair eroded areas immediately, re -seed as necessary to maintain adequate vegetative cover, mow vegetated
cover to maintain a maximum height of six -inches, and remove trash as needed
3 Remove accumulated sediment annually or when depth is reduced to 75% of the original design depth Restore
depth to original design depth without over -excavating Over -excavating may cause the required water table
separation to be reduced and may compromise the ability of the system to perform as designed
4 The water level in any monitoring wells will be recorded after a 1 inch rainfall event and at least once a
month Chronic high water table elevations (within 1 foot of the bottom of the system for a period of three
months) shall be reported to DWQ immediately
5 If DWQ determines that the system is failing, the system will immediately be repaired or replaced to original
design specifications if the system cannot be repaired to perform its design function, other stormwater control
devices as allowed by NCAC 2H 1000 must be designed, approved and constructed
b Remove accumulated sediment from the infiltration system annually or when depth in the unit is reduced
to 75% of the original design depth The system shall be restored to the original design depth without
over -excavating Over excavating may cause the required water table separation to be reduced and may
compromise the ability of the system to perform as designed Removed sediment shall be disposed of in an
appropriate manner and shall not be handled in a manner that will adversely impact water quality (i e
stockpiling near a stormwater treatment device or stream, etc )
A benchmark shall be established in the infiltration system The benchmark will document the original
design depth so that accurate sediment accumulation readings can be taken The measuring device used to
determine the depth at the benchmark shall be such that it will give an accurate depth reading and not
readily penetrate into accumulated sediments
When the depth at the benchmark reads 3 0' , the accumulated sediment shall be removed
from the system
See Detail Sheet C5
■ Benchmark Top of drop inlets of infiltration system = 45 5
• Sediment trap 1' below pipe invert = 43 25
• Sediment trap cleanout = 42 5 or T below top of DI grate
Form SWU-107 Version 3 99 Page 3 of
M
I acknowledge and agree by my signature below that I am responsible for maintaining the stormwater
collection system in accordance with the six maintenance procedures listed above I agree to notify DWQ of
any problems with the system or prior to any changes to the system or responsible party
Print Name and Title Gordon H Kolb, President
Address 170 Broadwev Street, Suite 227 New Orleans, LA 70118
Phone
Signature
Note* The legally responsible party should not be a homeowners association unless more than SO% of the lots have been sold
and a resident of the subdivision has been named the president
�� ` /
I, �, j �ftil , a Notary Public for the State of L 6u i .T 4-t4 dX . ee—tty of
do hereby certify that y� �/, xh_�6 personally appeared before me this
day of QC 166&r „ -, and acknowledge the due execution of the foregoing infiltration
basin maintenance reauirements Witness my hmdrmd official seal
SEAL
expiresSignature
w..
JUSTIN B SCHMIDT
NOTARY PUBLIC
Penh of Orleans State of Louisiana
My Commission is issued for Life
Form SWU-107 Version 3 99 Page 4 of 4
A&K #03035-Mod
PermitNo
State of North Carolina (to be provided by DWQ)
Department of Environment and Natural Resources
Division of Water Quality
STORMWATER MANAGEMENT PERMIT APPLICATION FORM
OFF -SITE SYSTEM SUPPLEMENT
This form may be photocopied for use as an original
DWQ Stormwater Management Plan Review
A complete stormwater management plan submittal includes a stormwater management permit application,
an off -site system supplement for each off -site stormwater treatment system, appropriate supplement forms
for any on -site stormwater treatment systems, and plans and specifications showing all stormwater
conveyances and drainage details for the project
I. PROJECT INFORMATION
Project Name Walgrreens 9 171' Street & S College Road
Contact Person John S Tunstall, P E Phone Number (910) 343-9653
Is all drainage from the project directed to the off -site system9 (check one) ❑ Yes ® No
Lot 5 (0.82 AC) was originally designed to go to a regional facility. The remainder of Walgreens will
be treated by an infiltration system permitted separately.
IL OFF -SITE SYSTEM INFORMATION (please complete the following information for the off -site system
will treat runoff from your project)
Permit No SW8 981023 Modification
Project Name 17th Street and College Road Project
Type of System (wet pond, infiltration basin, etc ) Wet Pond
Lot No (if part of a subdivision) Lot 5
How much built upon area draining to the permitted treatment system has been allocated to this
project 0 82 AC Y_ Q. 0. l0 R g a C
III. REQUIRED ITEMS CHECKLIST
Prior to issuing an off -site permit, verification of the following information must be provided Initial in the space
provided to indicate that the following requirements have been met and supporting documentation is attached If
the applicant has designated an agent in the Stormwater Management Permit Application Form, the agent may
initial below If a requirement has not been met, attach justification
Form SWU-106 Version 3 99 Page 1 of 2
r
Applicants Initials
a Deed restrictions limiting the built -upon area on the site have been recorded
b Engineers certification for the existing off -site system has been submitted to DWQ
c There are no outstanding Notices of Violation for the off -site system
d Off -site system is in compliance with the issued permit
IV. STORMWATER COLLECTION SYSTEM MAINTENANCE REQUIREMENTS
1 Mowing will be accomplished as needed according to the season Grass height will not exceed six inches
at any time
2 Accumulated sediment and trash will be removed from the collection system as necessary Swales and
ditches will be reseeded or sodded following sediment removal
3 Eroded areas of swales and ditches will be repaired and reseeded Swales and ditches will be revegetated
as needed based on monthly inspections
4 The collection system, including catch basins, curb cuts, velocity reduction devices, and piping, will be
inspected monthly or after every significant runoff producing rainfall event Trash and debris will be
cleared away from grates, curb cuts, velocity reduction devices, and piping
5 The collection system may not be altered in any way without prior approval from NCDENR Division of
Water Quality
I acknowledge and agree by my signature below that 1 am responsible for maintaining the stormwater
collection system in accordance with the five maintenance procedures listed above I agree to notify DWQ
of any problems with the system or prior to any changes to the system or responsible party
Print Name and Title Gordon H Kolb, President
Address 170 Broadwav Street, Suite 227 New Orleans, LA 70118
Phone
Signature
Date
Note: The legally responsible party should not be a homeowners association unless more than 50% of the lots have been sold
and a resident of the subdivision has been named the president
A1, no- M '
a Notary Public for the State of A a 6n h n County of
do herby certify that _i�(}�'[�r� personally appeared before me this
day of and acknowledge the due execution of the foregoing infiltration
basin maintenance requirements Witness my hand and official seal
SEAL ,�n�,, My c mmission expires Ug
Signature a[LCII{ - -_- -- - -
Form SWU-106 Vernon 3 99 Page 2 of 2
T
TO Linda Lewis, Environmental Engineer
NC DENR(Division of Environmental Management
Water Quality Section
127 Cardinal Drive Extension
Wilmington, NC 28405-3845
RE- 17"' Street & College Road Project
Wilmington, NC
A & K Project No. 02151
Engineer's Certification
State Stormwater Management Systems
Permit No SW8 981023 Modification
I, J Phillip Norris, P E _ , as a duly registered Professional Engineer in the State of
North Carolina, having been authorized to observe (periodically, weekly, M fine) the construction of the project,
17'h Street & Colle a Road Project (Project)
for Univer ' Grou , Inc (Project Owner) hereby state that, to the best of my abilities, due
care and diligence were used in the observation of the project construction such that the construction was observed
to be built within substantial compliance and intent of the approved plans and specifications
Required items to be checked for this certification to be considered complete are on page 2 of this form
Noted deviations from approved plans and specifications
7PN/asn
02151 12-04-03a
IZ
Sigpature
Registration No 11966
Date _ 1 Z, o4 (7 !)
cc Tony Roberts, New Hanover County Building Inspector
ME
CONSULTING ENGINEERS, INC
i 902 Market Street Wilmington NC 28401-4733
910-343-9653 Phone 910-343-9604 Fax
www andrewandkuske com
i
Certification Requirements
The drainage area to the system contains approximately the permitted acreage.
The drainage area to the system contains no more than the permitted amount of built -upon area.
All the built -upon area associated with the project is graded such that the runoff drains to the
system
The outlet/bypass structure elevations are per the approved plan.
The outlet structure is located per the approved plans
Trash rack is provided on the outlet bypass structure
All slopes are grassed with permanent vegetation
Vegetated slopes are no steeper than 3.1
�9 The inlets are located per the approved plans and do not cause short-circuiting of the system
The permitted amounts of surface area and/or volume have been provided
Required drawdown devices are correctly sized per the approved plans
S
All required design depths are provided
All required parts of the system are provided, such as vegetated shelf, and a forebay
The overall dimensions of the system, as shown on the approved plans, are provided
cc Tony Roberts, New Hanover County Building Inspector