October 02, 2019
Grady W Fulcher
Beacons Reach Master Association Inc
PO Box 989
Atlantic Beach, NC 28512-0989
SUBJECT: Compliance Inspection Report
Beacons Reach WWTP
Non-discharge Permit No. WQ0013676
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Beacons Reach WWTP
on 9/18/2019. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in Non-discharge Permit No. WQ0013676. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
Please respond in writing to this office within 30 days of your receipt of this letter regarding your plans
or measures to be taken to repair the audible alarm at the influent pump station at the wastewater treatment
facility.
If you should have any questions, please do not hesitate to contact Bryan Lievre with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
bryan.lievre@ncdenr.gov.
Sincerely,
Morella Sanchez-King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENT
Cc: File Uploaded to Laserfiche
DocuSign Envelope ID: 660EA05A-9AC6-4052-81A1-A97F57C9555C
Compliance Inspection Report
Permit:WQ0013676 Effective:06/07/17 Expiration:05/31/22 Owner :Beacons Reach Master Association Inc
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Carteret
Wilmington
Grady W Fulcher
Effective:Expiration:Facility:Beacons Reach WWTP
510 Salter Path Rd
Pine Knoll Shores NC 28512
Title:Phone:252-247-4017Property Manager
Stanley Earl Buck 993396 252-503-5307
Allen Wayne Rhue 991815 910-358-3254
Secondary ORC(s):
252-247-9167Phone:22801Certification:Donald P OmaraPrimary ORC:
WW3.,SI,System Classifications:
On-Site Representative(s):
Related Permits:
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
09/18/2019 01:00PM 03:30PM
Bryan Lievre 910-796-7215
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Reclaimed Water
Compliance Evaluation
Question Areas:
Treatment Flow Measurement-Effluent Treatment Flow Measurement-Influent Miscellaneous Questions
Treatment Flow Measurement-Water
Use Records
Treatment Treatment Barscreen
Treatment Filters Record Keeping Treatment Activated Sludge
Treatment Influent Pump Station Treatment Clarifiers Treatment Disinfection
Treatment Flow Measurement Treatment Return pumps End Use-Reuse
Standby Power Wells
(See attachment summary)
Page 1 of 7
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0013676
09/18/2019 Compliance Evaluation
Beacons Reach Master Association Inc
Routine
Inspection Summary:
A routine compliance inspection of the Beacons Reach Master Association Inc. WWTF was conducted on September 18,
2019. The purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and
limitations specified in Permit WQ0013676. Donald Omara (ORC) and wife, Karrie Omara, were present during the
inspection.
The system has been documented as having monitoring wells located around the 5-day holding pond as well as around the
three irrigation lakes/ponds. According to Don Omara, all these monitoring wells have been properly abandoned by licensed
well driller(s). Also the irrigation lakes/ponds (e.g. Egret Lake, Coral Pond and Westport IV Pond) have been disconnected
from the irrigation system and the pump station located near Egret Lake is no longer utilized. Any irrigation water is either
pumped from the 135,000 gallon holding tank at the WWTF or from an irrigation well located near the northwest corner of
Coral Pond. Manual valves must be operated near the irrigation well to direct flow from the well or the holding tank.
The audible alarm at the influent pump station was not operational during the visit and needs to be repaired.
Reminded operator that Well #3 for The Town of Pine Knoll Shores is located at the southwest corner of the parking lot
between the tennis courts along Coral Drive, west of Murex Drive. Advised operator to ensure that reclaimed water irrigation
heads within 100 feet of well are not being used.
The facility is compliant with the non-discharge permit WQ0013676. Please review the comment sections of the inspection
report for more details.
Page 2 of 7
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0013676
09/18/2019 Compliance Evaluation
Beacons Reach Master Association Inc
Routine
Type Yes No NA NE
Single Family Spray, LR
Activated Sludge Drip, LR
Lagoon Spray, LR
Single Family Drip
Infiltration System
Recycle/Reuse
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Reuse (Quality)
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
As previously mentioned during last inspection, the three irrigation ponds (Egret Lake, Coral
Pond, and Westport IV Lake) are no longer used for wastewater storage. Irrigation of common
ways with recycled water is from 135,000 gallon tank at WWTP or irrigation well near NW corner
of Coral Pond.
Comment:
Treatment Influent Pump Station Yes No NA NE
Is the pump station free of bypass lines or structures?
Is the general housekeeping acceptable?
Are all pumps present?
Are all pumps operable?
Are floats/controls operable?
Are audio and visual alarms available?
Are audio and visual alarms operational?
# Are SCADA/Telemetry alarms required?
Are SCADA/Telemetry available?
Are SCADA/Telemetry operational?
The audible alarm for the influent pump station was not operational on the day of visit, 9/18/2019.
The visual alarm activitated and a remote dialer called the ORC while we were on-site. If the
ORC does not answer a call is sent to the BORC and then the Beacon's Reach Office.
Comment:
Treatment Flow Measurement-Influent Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Page 3 of 7
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0013676
09/18/2019 Compliance Evaluation
Beacons Reach Master Association Inc
Routine
Does flowmeter appear to monitor accurately?
Comment:
Treatment Flow Measurement-Water Use Records Yes No NA NE
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement-Effluent Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Flow meter was callibrated on 5/19/2019 by Delta Systems EnvironmentalComment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is generator tested weekly by interrupting primary power source?
Is generator operable?
Does generator have adequate fuel?
Generator is tested automatically every Sunday.Comment:
Treatment Barscreen Yes No NA NE
Is it free of excessive debris?
Is disposal of screenings in compliance?
Are the bars spaced properly?
Is the unit in good condition?
Comment:
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable?
Is the aeration basin thoroughly mixed?
Is the aeration equipment easily accessed?
Is Dissolved Oxygen adequate?
Are Settleometer results acceptable?
Is activated sludge an acceptable color?
Carbon source is still added during off seasons at the splitter box. Activated sludge basin looks
well mixed and aerated with an acceptable odor. Jar tests are performed once a week for
process control.
Comment:
Page 4 of 7
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0013676
09/18/2019 Compliance Evaluation
Beacons Reach Master Association Inc
Routine
Treatment Clarifiers Yes No NA NE
Are the weirs level?
Are the weirs free of solids and algae?
Is the scum removal system operational?
Is the scum removal system accessible?
Is the sludge blanket at an acceptable level?
Is the effluent from the clarifier free of excessive solids?
Effluent looked clear and no floating solids were observed.Comment:
Treatment Return pumps Yes No NA NE
Are they in place?
Are they operational?
Comment:
Treatment Filters Yes No NA NE
Is the filter media present?
Is the filter media the correct size and type?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids?
Is the mud well free of excessive solids and filter media?
Does backwashing frequency appear adequate?
The three sand filters continue to be backwashed daily. Algae tends to build up in the clearwell.
A floating pool chlorinator helps to eliminate this problem (used in additional to sodium
hypochlorate).
Comment:
Treatment Disinfection Yes No NA NE
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
Page 5 of 7
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0013676
09/18/2019 Compliance Evaluation
Beacons Reach Master Association Inc
Routine
# Is it a dual feed system?
Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-____-____)
If yes, then when was the RMP last updated?
System utilizes liquid sodium hypochlorate for disinfection.Comment:
Record Keeping Yes No NA NE
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
Above reports are not typically maintained on-site, but ORC brought records with them.
Environment 1 continues to be contract lab. Residuals are removed by Barnes Environmental
Waste and Hauling monthly during the summer and every other month during the off season
(late fall, winter and early spring).
Comment:
End Use-Reuse Yes No NA NE
Page 6 of 7
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0013676
09/18/2019 Compliance Evaluation
Beacons Reach Master Association Inc
Routine
Is the acreage in the permit being utilized?
Does the acreage specified in the permit correspond to the measured acreage at the site?
Are all essential units provided in duplicate?
Is an automatically activated standby power source available?
Is the equalization capacity adequate?
Is aerated flow equalization present?
Has the turbidity meter been calibrated in the last 12 months?
Does the turbidity meter have recording capabilities?
Is all flow diverted at the appropriate times?
Is all upset wastewater diverted from reuse storage unit?
Is all upset wastewater treated, retreated, or disposed of acceptably?
Is upset wastewater treated prior to discharge to irrigation storage?
Is public access restricted from irrigation area during active site use?
If golf course, is a sign posted in plain sight on the club house?
Is the cover crop acceptable?
Are buffers adequate?
Is the site free of ponding/runoff?
Is the acreage in the permit being utilized?
Is the application equipment acceptable?
Is the application area free of limiting slopes?
How close is the closest water supply well?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
Is municipal water available in the area?
Are GW monitoring wells required?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
The system is equipped with a 125 kW diesel powered generator which is capable of powering
the influent lift station as well as the entire WWTF. The turbidity meter was calibrated on
5/19/2019 by Delta Systems Environmental. Flow is automatically diverted to the 5-day pond if
the turbidity reaches 10 NTU. No ponding liquid was present in the 5-day upset pond on the date
of the visit (9/18/2019). The pond area was observed to be well maintained with grass and a
measuring gauge rod mounted in a concrete base which did not penetrate the surface. The
Town of Pine Knoll Shores has a public water supply well (Well #3) at the southwest corner of a
parking lot located between tennis courts south of Coral Drive, west of Murex Drive.
Comment:
Page 7 of 7