HomeMy WebLinkAboutNCG551612_Compliance Evaluation Inspection_20190927ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER Director Bryan Albrecht 7840 Massey Chapel Rd Durham NC 27713-8760 Dear Mr. Albrecht: NORTH CAROLINA, Environmental Quality September 27, 2019 Subject: Compliance Evaluation Inspection 7840 Massey Chapel Road SFR Permit No. NCG551612 Durham County On September 16, 2019, Joan Sclineier from the Raleigh Regional Office visited your single- family residence (SFR) wastewater treatment system to evaluate compliance with the above permit to discharge wastewater. Your assistance during the inspection was greatly appreciated. The checked boxes below show what conditions were noted at your facility: ® In compliance: You are reminded to regularly maintain the UV disinfection system, have the effluent sampled once a year, and have the septic tank pumped out every 3 to 5 years. Your good record of operation and meeting the permit requirements is highly commended. ® Other: Please check the ammeter in the control box periodically to be sure the UV system is working. If you have questions or comments about this inspection or the requirements to take corrective action, please contact Joan Schneier or me at 919-791-4200 or joan.schneierr,(.Lncdenr.gov. Also please see the attached inspection report. Since ly, ;iock- tich, L.G., Assistant Regional Supervisor Raleigh Regional Office, Water Quality Regional Operations Section, Division of Water Resources �\ v�rrth �:arulirra Drp;ut(r:r•nl of Fmironn(rulnl �u.di(g IJi.tsi�:n ut l;l'aH•r Nr�uur( cs _ \\ } Rn;c'IyII Rryiunal U(lit.( # 'Stf(]U IS•n l+ It p(Iti+• 1thIP (ill. Nol III V;1:41vrl:r !A )09 � ,.a ;IL+rnw W.4V+.� � rllll -rSl�r\li Attachments: Inspection Report cc: (minus attachments) RROrSWP Files NPDES Permitting Unit Files — Charles Weaver United States Environmental Protacdan Agency Form Approved. EPA Washinglon, D C 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-9a Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yrlmolday Inspection Type Inspector Fac Type 1 u 2 1a 1 3 I NCG551612 '11 12113109116 17 18 L I 19 I C t 201 I 21 I J LJ LJ 6 Inspection Work Days Facility Self -Monitoring Evaluation Rating 81 GA Reserved 67 70 � I 71 L 72 t t 73 � 74 75 80 �J Section B- Facility Data �j Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES oermit Numberl 7840 Massey Chapel Road 7840 Massey Chapel Rd Durham NC 27713 Name(s) of Onsite Representative(s)fTiBes(s)1Phone and Fax Number(s) 111 Name, Address of Responsible OfficiaUTidefPhone and Fax Number Entry Time/Dale I Perm 1 Effective Data 09 30AM 19109/16 14: 02/03 Exit TimefDale I Perm;l Expiration Date 10 35AM 19/09:16 18;07;31 Other Facility Data Bryan C Albracht,7840 Massey Chapel Rd Durham NC 27713/11 Contacted No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Operations & Maintenance 0 Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/OfticefPhons and Fax Numbers Joan Schneier DWR+RRO GW/919.7914200; Signaturl'.0,41-nagement 0 A Reviewer •• Agency:ONcelPhone and Fax Numbers EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete Date Page# 1 NPDES yrlmolday Inspection Type (Cont) 31 NCG551612i11 12 19/09/16 17 18 I C Section C: Summary of FindinglComments (Attach additional sheets of narrative and checklists as necessary) The system consists of an Advantex AX-20 RT pod containing filter, recirc pump, and UV in the back yard. There is a lift pump and tank to send the effluent to the front road storm ditch. The outfall is riprapped and has a vermin grate. It was installed in 2014 to replace a failing sand filter. Bryan Albrecht assisted during the inspection and had tools to open all covers. AWT maintains 2xlyear. They cleaned the effluent filter and sampled on 811212019.The BOD, TSS, and fecal values were well within limits, although ammonia (no limit) was high. The septic tank was not opened during the inspection due to recent maintenance. The pod cloth filters seemed to be uniformly covered and the sprayers worked. The high water alarms worked by pulling the float trees and waiting a while. The UV ammeter in the panel showed 0.41 amps after resetting the breaker. However a clamp -on ammeter showed 0.07 amps before and after the reset. The bulb had been replaced by AWT in August. The lift pump was triggered by hand momentarily and the pipe was barely dripping by the time we got out to the ditch. The riprap was clean. Earler problems mentioned were a float issue and a connector on the UV, both of which were resolved by AWf'. Access Notes: 112 socket for pod, Allen wrench for tanks. The yard is fenced with a dog and a security camera with audio is in place . paw Permit NCG551612 Owner - Facility 7840 Massey Chapel Road Inspection Date: 09I16I2o19 Inspection Type Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permitlee submitted a new ❑ ❑0 ❑ application? Is the facility as described In the permit? ■ ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ . ❑ Is access to the plant site restricted to the general public? ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? ❑ ❑ ❑ Comment: Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ M ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The effluent BOD TSS and fecal values were well within limits although ammonia no limit wa�n- Se tic Tank Yes No NA NE (If pumps are used) Is an audible and visual alarm operational? ❑ ❑ M ❑ Is septic tank pumped on a schedule? ■ ❑ ❑ ❑ Are pumps or syphons operating properly? ❑ ❑ ■ ❑ Are high and low water alarms operating properly? ❑ ❑ ❑ Comment: The new septic tank was installed in 2014 and has not yet been cleaned out. Sand Filters Low rate Yes No NA NE (If pumps are used) Is an audible and visible alarm Present and operational? E ❑ ❑ ❑ Is the distribution box level and watertight? ❑ ❑ . ❑ Is sand filter free of ponding? ❑ ❑ ■ ❑ Is the sand filter effluent re -circulated at a valid ratio? ❑ ❑ N Is the sand filter surface free of algae or excessive vegetation? ❑ ❑ ❑ # Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1) ❑ ❑ ❑ Comment: AWT maintains 2xI ear. They cleaned the effluent filter and sampled on 8/12/2019. The septic tank was not opened during the inspection due to recent maintenance. The Pod cloth filters seemed to be uniformly covered and the sprayers worked. The high water alarms worked by Dullingthe float trees and waiting a while_ Disinfection - UV Yes No NA NE Page# 3 Permit NCG551612 owner - Facility 7840 Massey Chapel Road Inspection Date' 09111612019 Inspection Type Compliance Evaluation Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? ❑ ❑ ❑ M Are UV bulbs clean? M ❑ ❑ ❑ Is UV Intensity adequate? 0 ❑ ❑ ❑ Is transmittance at or above designed level? ❑ ❑ ❑ N Is there a backup system on site? ❑ El M ❑ Is effluent dear and free of solids? 0 ❑ ❑ ❑ Comment: The UV ammeter in the panel showed 0.41 amps after resetting the breaker. However a clamp -on ammeter showed 0.07 am s before and after the reset. The bulb had been replaced by AWT in August. Effluent Pine Yes No NA NE Is right of way to the outfall properly maintained? ■ ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ N ❑ Comment: The lift Dump was triggered by hand momentarily and the pipe was barely dripping by the time we got out to the ditch. The riorap was clean. F a g 9 N 4