HomeMy WebLinkAboutWQCSD0508_Compliance Evaluation Inspection_20190930ROY COOPER
MICHAEL 5, REGAN
S.trre ary
LINDA CULPEPPER
Ctu: e;t7r
Mr. Levell Langley, Mayor
Town of Red Oak
P.O. Box A
Red Oak, N.C. 27868
`JT, .
`n
Envirurmsn:ai Q,alir.
September 30, 2019
Subject: Compliance Evaluation Inspection
Red Oak Collection System
Collection System PermitNo: %VQCSD0508
Nash County
Dear ,Mayor Langley:
it f4r! 19'
On September 4, 2019, Cheng Zhang of the Raleigh Regional Office (RRO) Division of Water
Resources conducted a Compliance Evaluation Inspection of the subject facility. The assistance
and cooperation of Mr. Scott Farmer, the operator of the system, and 11r. Jonathan Boone, Nash
County Utilities Director, were very helpful and appreciated. A checklist of items is enclosed
with this letter. During the inspection the following items were noted:
1.) Town of Red Oaks holds a deemed sewer collection system permit in Nash County (Nash
County Public Utilities Department is operating and maintaining the system). There has been
no reportable sanitary sewage overflow (SSO) incidents from the collection system since the
last inspection.
2.) The collection system includes gravity sewer lines. force mains, and two duplex pump
stations.
3.) The facility maintains a map of the system to include all required elements.
4.) The facility has developed and implemented an operation and maintenance plan which Iists
the frequency of system inspections, prey-entive maintenance schedule (right -or -way
maintenance), and overflow response plan.
5.) Grease educational flyers are sent to all users semi-annually.
6.) During the inspection, the two pump stations were obsen-cd and found to be in good
condition.
7.) The right-of-way behind 5378 Red Oak Road was maintained and accessible. Sewer line
clearing has not been conducted since the system was built in 2007, preventive line cleaning
and maintenance may be considered and planned in the future.
If you have any questions regarding the attached report or any of the findings, please contact
Cheng Zhang at: (919) 791-4200 (or email: cheng.zhanY-u ncdenri-gov).
Sincerely,
447
Rick Bolich, L.G.
Assistant Supervisor
Division of Water Resources
Ralei�-li Regional Office
Attachments: Compliance Inspection Report
Cc: Central Files w::attachment
Raleigh Regional Office w :attachment
Scott Farmer, Nash County, w..'attachment (electronic copy only)
Compliance Inspection Report
Permit: WOCSDO508 Effective, D1;26r10 Expiration
SOC: Effective: Expiration,
County: Nash
Region: Raleigh
Contact Person: Derek Hawkes Titrr,.
Directions to Facility:
System Classifications:
Primary ORC: Certification:
Secondary ORC(s):
On -Site Representative(s):
On-s to representative S--ctt Fanr.er
Owner: Town of Red Oak
Facility: Town of Red Oak Sanitary Sewer System
Phone: 252462-2613
Phom:
Related Permits:
NCO030317 City of Rocky Mount - Tar River Regional VjYjiP
WQCS0001 S City of Rocky Mount - Rocky Mount Collection System
Inspection Date- 09f0+2019 Entry Time: 09 30AM Exit Time: 11 00AM
Primary Inspector: Cheng Zhang Phone: 919-7914200
Secondary Inspector{s):
Reason for Inspection; Routine Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Deemed permitted collection system management and operation
Facility Status: Compliant Not Compliant
Question Areas:
Miscellaneous questions N General Grease Control
Spills/Response Plan N Inspec4ans Lines
Manholes N Pump Stations
(See attachment summary)
Page i of 6
Permit: WOCSDO508 Owner • Facility' Town cf Red Oak
Inspection Datet 09104-Wig Inspection Type : Ccllecticn System Inspect Non Sampling Reason for Visit: Routine
General
Yes No NA NE
# Is this system a satellite syslem7 e ❑ ❑
# If Yes, what is system name or perrrW number? WQCS000t 1
Is there a overall sewer system map? 0 ❑ ❑ El
Does the map include
Pipe sizes
■ ❑ ❑ ❑
Pipe materials (PVC, DIP, etc)
■ ❑ ❑ ❑
Pipe location
. ❑ ❑ ❑
# Flow direction
.
# Approximate pipe age
■ El El El
# Pump station ID, location and capacity
0 El El El
# Force main air release valve location & type
D El 0 El
# Location of satellte connections
■
Are system maintenance records maintained?
■
Comment:
Grease Control Yes Na NA NE
Is greaselsewer education program documented with req'd customer distribution? El 00
# Are other types of education tools used like webs tes. booths special meetings, etc? ■
If Yes what are they? (This can reduce mailing to annual.)
For public systems is there a Grease Control Program via an ordinance/agreement? 0 El❑ ❑
If Yes. does it require grease control devices at applicable locations? ❑ ❑ M
Is the Grease Control Program enforced via periodic inspections/records review? ❑ ❑
Is action taken against violators? ■
Comment: No rease trap slinterce tors in the system,
Spills and Resnonse Action Plan
"
Yes No NA NE
# Is system free of known points of bypass?
■ El 1:10
If No describe type of bypass and location
# Have there been any Sevier spills in the past 3 years?
M ❑ El
If Yes were they reported to the Division if meeting the reportable criteria?
El El 0 D
If applicable, is there documentation of press releases and public notices issued?
Are all spills or sewer related issueslcomplaints documented?
El D ■ El
# Are there repeated overflows/problems (2 or more :n 12 months) at same location?
❑ El ■ ❑
# If Yes, is there a corrective action plan?
❑ M ❑
Is a Spill Response Action Plan available?
■
Is a Spill Response Action Plan available for all personnel?
Page 3 of 6
Permit: WOCSDO508 owner -Facility: Town of RedCak
Inspection Date: 09/0412019 Inspection Typo. Ccltection System lnspert i'lon Samrlir; Reason for Visit Rc..Pe
Does the plan include:
# 24-hour contact numbers ■ ❑ ❑ ❑
# Response time .
# Equipment list and spare pans inventory ■ Cl ❑
13
# Access to cleaning equipment ■ El ❑ ❑
# Access to construction crews, contractors, and/or engineers ■
# Source of emergency funds El D
# Site sanitation and cleanup materials ■
# Posl-overllowlspill assessment ■ ❑ ❑
Comment: The Plan was updated on September 4. 2019 after the site visit.
Inspections
Are adequate maintenance records maintained?
Yes No NA NE
❑ El
Are pump stations being inspected at the required frequency?
.
Is at least one complete functionality test conducted weekly per pump station?
■
Is there a system or plan in place to observe the entire system annually?
■ ❑ El 11
Is the annual inspection documented?
1:1 Cl
# Does the system have any high -priority lines/locations?
■ ❑
Are inspections of HPL documented at least every 6 months?
El ❑ ■ ❑
Are new lines being added to the HPL list when found or created"
❑ ■ ❑
Comment No high -priority lines in the system
Lines/Right-of-Ways/Aerial Lines
Yes No NA NE
Please list the Lines/Right of WaysiAerial Lines Inspected
Two outfall Imes jo n together behind 5378 Red Oak Road were visited during the inspection. Oulfall lines
were maintained and accessible.
Are right-of-ways and easements maintained for the full w'dlh for access? ■
If No. g ve dela'Is on temporary access:
Is ma-nteriance documented? ■ ❑ ❑
Were all areaslhnes inspected free of issues? . ❑ ❑
Comment:
Manholes
Yes No NA NE
Please list the Manholes Inspected:
Manhole at where the two outfall lines join.
Are manholes accessible? ■
# Are manhole coverslvents above grade? .
Are manholes free of visible signs of overflow? 11 . ❑
El
Are manholes free of sinkholes and depressions? ■ ❑ ❑
Are manhole covers present? ■ 11 ❑ ❑
Page 4 of 6
Permit: WOCS00508 Owner - Facility: Town of Red Oak
Inspection bate: 09104/2019 Inspection Type : CCliectian System Inspect Non Sampling
Reason for Visit: Routine
# Are manholes property seated?
■El E]❑
# Are manholes in good condition?
■ ❑ El 0
# Are ,nverts in good condition?
■
Is flow unrestricted in manholes?
■ 0
Are manholes free of excessive amounts of grease?
MC1 El ❑
Are manholes free of excessive roots?
■ O 0 El
Are manholes free of excessive sand?
■ El 1:1 El
Are manhole vents screened?
■ ❑ 1:1 El
Are vents free of submergence?
■
Are manholes free of bypass structures or pipes?
■
Comment;
Pump Stations
-
Yea No NA NE
Please list the Pump Stations Inspected
Red Oak Park Pump Station
Red oak Main Pump Station
# Number of duplex or larger pump stations in system
2
# Number of vacuum stations in system
o
# Number of simplex pump stations in system
0
# Number of simplex pump stations in system serving more than one building
0
Wow many pumpivacuum stations have.
# A two-way "auto polling" communication system (SCADA) installed?
t
# A simple one-way telemetrylcommunication system (auto -dialer) installed?
t
For pump stations inspected;
Are they secure with restricted access?
■
Were they free of by-pass structuresipipes?
■ El 1:1 El
Were wet wells free of excessive grease/debris?
■110 ❑
# Do they all have telemetry installed?
■
Is the telemetry system functional?
■El❑ ❑
Is a 24-hour notificat°on sign posted ?
■ ❑ ❑ ❑
Does the sign include
Owner Name?
❑ ❑ ❑
Pump station identifer?
■ El ❑ El
# Address?
■ ❑ El D
Instructions for notification?
M
24-hour emergency contact numbers?
■
Are audio and visual alarms present?
.El U
Are audio and visual alarms operable?
■ ❑ El ❑
Page 5 of 6
Permit: WQCSD0508 Owner • Facility: Town of Red yak
Inspection Date: 09/04/2019 Inspection Type : CcIlectico System Inspe2t Non Sampling Reason for Visit
f -t-t
# Is there a backup generator or bypass pump connected?
■
If tested during inspection, did it function properly?
0 El ■ El
Is the back-up system tested at least bi-annually under normal operating conditions?
.
# (Does it have a dedicated connection for a portable generator?
■
# Is the owner relying on portable units in the event of a power outage)
❑ ■ ❑
# If Yes, is there a distribution plan?
❑ .
If Yes, what resources (UnitslStaffNehiciesletc) are included in Plan')
# Does Permittee have the approved percentage of replacement simplex pumps'?
❑ El ■ ❑
Is recordkeeping of pump station inspection and maintenance program adequate')
Do pump station logs include at a minimum
Inside and outside cleaning and debris removal?
■ ❑ ❑ ❑
Inspecting and exercising all valves?
. ❑
Inspecting and lubricating pumps and other equipment?
. ❑ ❑
Inspecting alarms, telemetry and auxiliary equipment?
■ ❑ ❑ ❑
Comment: Red Oak Main Pump Station is equipped with on -site clenerator, bypass valve. and SCADA_
Rea Oak Park Pump Station serves one building Office and bathrooms and has no backu
awer, in case of Power outra e. the bathrooms will be closed. It is equipped with simple
telemetry.
Page 6 of 6