September 17, 2019
Nick Crane, Association Manager
Dunescape Villas Condominium Owners Association, Inc.
PO Box 4455
Emerald Isle, NC 28594
SUBJECT: Compliance Inspection Report
Dunescape Villas WWTF
Non -discharge Permit No. WQ0003044
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Dunescape Villas WWTF
on 9/11/2019. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in Non -discharge Permit No. WQ0003044. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report". There were no significant issues or findings noted during the
inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
Sincerely,
DocuSigned by:
I ONE �narrr OA,
7F141 E73B6F3456,.. for
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Karrie Omara
Uploaded to Laserfiche
North CaroLrsgDepartmentofEnvironmeatalQualk%- I DiuisionofWater Resources
Wilmington Reg•3iLa- Dffioe l 127 Cardirrei Drive Extensors l V`ilrar:ngton, North Car•o--rs 2-3405
"•• 910-796-7215
Compliance Inspection Report
Permit: WQ0003044 Effective:
04/19/17 Expiration: 03/31/22 Owner:
Dunescape Villas Condominium Owners
Association Inc
SOC: Effective:
Expiration: Facility:
Dunescape Villas WWTF
County: Carteret
2111 W Fort Macon Rd
Region: Wilmington
Atlantic Beach NC 28512
Contact Person: Jaye Spring
Title:
Phone: 252-354-6333
Directions to Facility:
Located on Bouge Banks, on the north side
of Hwy 58. It is 1.9 miles west of the entrance to Atlantic Beach.
System Classifications: WW3.,
Primary ORC: Donald P Omara
Certification: 7904
Phone: 252-247-9167
Secondary ORC(s):
On -Site Representative(s):
On -site representative
Donald P Omara
252-247-9167
Related Permits:
Inspection Date: 09/11/2019
Entry Time: 09:30AM Exit Time:
10:20AM
Primary Inspector: Helen I Perez
Phone: 910-796-7387
Secondary Inspector(s):
Reason for Inspection: Routine
Inspection Type:
Compliance Evaluation
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent
Treatment Flow Measurement -Influent
Miscellaneous Questions
Treatment Flow Measurement -Water
Treatment
Treatment Barscreen
Use Records
Treatment Filters
Record Keeping
Treatment Activated Sludge
Treatment Disinfection
End Use -Infiltration
Treatment Flow Measurement
Standby Power
(See attachment summary)
Page 1 of 6
Permit: WQ0003044 Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Date: 09/11/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Dunescape Villas WWTF was conducted on September 11, 2019. The purpose of the
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0003044. Don Omara, Karrie Omara and Lee Buck were present during the inspection.
This facility had it's final start-up inspection in July 2017. The new facility consists of a Fluidyne Integrated Surge Anoxic Mix
SBR system. No changes were made to the three LPP fields in the up -grade. The facility is permitted for 55,000 GPD and
averages 40,000 GPD in the summer months and 25,000-30,000 GPD in the winter. One train is normally shut down in the
winter due to lower flows.
Since last inspection, a review of records show no effluent parameter violations and some TDS violations of the monitoring
wells. MW-4, MW-5 and MW-6 are all within the review boundary. The Wilmington Regional Office is tracking the
non -compliant trends for the need to re-evaluate well locations in the future.
The facility is compliant with non -discharge permit WQ0003044. Please review the comment sections of the inspection
report for more details.
Page 2 of 6
Permit: WQ0003044
Inspection Date: 09/11/2019
Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Type : Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Single Family Drip
❑
Single Family Spray, LR
❑
Recycle/Reuse
❑
Lagoon Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Activated Sludge Spray, LR
❑
Reuse (Quality)
❑
Infiltration System
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: No comment.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment: No comment.
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ 0 ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
0
❑ ❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
0
❑ ❑ ❑
Does flowmeter record flow?
0
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
0
❑ ❑ ❑
Comment: The flowmeter was calibrated on 5-7-2019 by Delta Systems.
Standby Power
Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Page 3 of 6
Permit: WQ0003044 Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Date: 09/11/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑
Is generator operable? ❑ ❑ ❑
Does generator have adequate fuel? ❑ ❑ ❑
Comment: The generator is tested weekly under load and documented in the maintenance log book. The
generator powers the facility as well as the influent pump station located across the street at the
Dunescape Villas complex. Staff indicated that they had no issues with the generator when
activated due to loss of power during Hurricane Dorian the week prior to inspection.
Treatment Barscreen Yes No NA NE
Is it free of excessive debris? 0 ❑ ❑ ❑
Is disposal of screenings in compliance? ❑ ❑ ❑
Are the bars spaced properly? ❑ ❑ ❑
Is the unit in good condition? ❑ ❑ ❑
Comment: A compacting WAM 6-mm fine screen is used for pretreatment.
Treatment Activated Sludqe Yes No NA NE
Is the aeration mechanism operable? 0 ❑ ❑ ❑
Is the aeration basin thoroughly mixed? 0 ❑ ❑ ❑
Is the aeration equipment easily accessed? 0 ❑ ❑ ❑
Is Dissolved Oxygen adequate? 0 ❑ ❑ ❑
Are Settleometer results acceptable? ❑ ❑ ❑
Is activated sludge an acceptable color? 0 ❑ ❑ ❑
Comment: The SBR system is operated by a pre-programmed process control panel based on DO levels
from the DO meters built in the system, liquid levels and time. Staff analyzes settleability for
process control.
Treatment Filters
Yes No NA NE
Is the filter media present?
❑ ❑ ❑
Is the filter media the correct size and type?
❑ ❑ ❑
Is the air scour operational?
❑
❑ ❑
Is the scouring acceptable?
❑
❑ ❑
Is the clear well free of excessive solids?
❑ ❑ ❑
Is the mud well free of excessive solids and filter media?
❑ ❑ ❑
Does backwashing frequency appear adequate?
0
❑ ❑ ❑
Comment: The two Hydrotech tertiary filters are backwashed automatically.
Treatment Disinfection
Yes No NA NE
Is the system working?
0
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑ ❑ ❑
Page 4 of 6
Permit: WQ0003044 Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Date: 09/11/2019 Inspection Type : Compliance Evaluation Reason for Visit:
Routine
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑
❑ ❑
If tablets, are tablets present?
❑
❑ ❑
Are the tablets the proper size and type?
❑
❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑
❑ ❑
If UV, are extra UV bulbs available?
❑ ❑ ❑
If UV, is the UV intensity adequate?
❑ ❑ ❑
# Is it a dual feed system?
❑
❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment: No comment.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
0
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑ ❑ ❑
NDAR?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑
❑ ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ 0❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Page 5 of 6
Permit: WQ0003044 Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Date: 09/11/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Were Operational and Maintenance records complete? ❑ ❑ ❑
Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑
Is a copy of the SOC readily available? ❑ ❑ ❑
No treatment units bypassed since last inspection? ❑ ❑ ❑
Comment: Records were oraanized and complete. Staff keeps both an operational loa book and a
maintenacne log book for the facility. Field parameters are performed by staff, certification
#5660, and Environment 1, Inc, certification #10, performs the effluent and monitoring well
parameters. Calibration records for the Oaklon pH meter were complete. Nitrates for MW #5
have been back in compliance since November 2017, after start-up of the new plant. MW- 4,
MW-5 and MW-6 have shown some non-compliance limits for TDS.
End Use -Infiltration
Yes No NA NE
# Is the application High Rate or Low Rate?
High Rate
Are buffers maintained?
❑
0 ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
Is municipal water available in the area?
❑ ❑ ❑
Are GW monitoring wells required?
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RIB and CB?
❑
❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Is a usable green area maintained?
❑ ❑ ❑
Is the disposal site acceptable?
❑ ❑ ❑
Is the distribution equipment acceptable?
❑ ❑ ❑
Is the disposal site free of ponding?
❑ ❑ ❑
Is the disposal site free of breakout?
0
❑ ❑ ❑
Are the disposal sites free of solids, algae, etc.?
❑ ❑ ❑
Do the records show that the fields are properly maintained?
❑ ❑ ❑
Are the disposal sites free of vegetation?
❑ ❑ ❑
Do any surface water features appear to be adversely impacted by GW discharge?
❑
❑ ❑
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
0
❑ ❑ ❑
Comment: Setbacks of the high rate fields do not follow 02T non -discharge regulations because the fields
were constructed prior to 02T rules. MW-4, MW-5, and MW-6 are located within the review
boundary. The 3 LLP fields were well maintained. The dosing of Field #2 was observed during
the inspection and no issues were detected. Each field has a flow meter for measurement of
application.
Page 6 of 6