HomeMy WebLinkAboutNC0085359_Compliance Evaluation Inspection_20190918 (2)United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCO085359 111 12 I 19/09/04 I17 18 I S I 19 I G I 201 I
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70 I g 71 I tyI 72 I r I 73 I I 174 751 I I I I I I I80
uI I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:27AM 19/09/04
15/01/01
Twelve Mile Creek WWTP
8299 Kensington Dr
Exit Time/Date
Permit Expiration Date
Waxhaw NC 28173
01:04PM 19/09/04
19/12/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Jonathan Brian Jordan/ORC/704-562-4542/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Bart Farmer,4600 Goldmine Rd Monroe NC 2811 OH704-296-4227/7042897395
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Roberto Scheller ESQL DWR/MRO WQ/252-946-6481/ 9/17/2019
91C2A007838943E.-
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
' 9/18/2019
AtaccsatAFvazs... Page#
NPDES yr/mo/day Inspection Type
NCO085359 I11 121 19/09/04 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO085359 Owner - Facility: Twelve Mile Creek WWTP
Inspection Date: 09/04/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The current permit expires on December 31, 2019. Recept of permit renewal application
was received on July 5, 2019.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
❑
0
❑
❑
Dates, times and location of sampling
❑
Name of individual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses
❑
Transported COCs
❑
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
❑
Page# 3
Permit: NCO085359
Inspection Date: 09/04/2019
Record Keeping
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: At time of inspection Chain-of-Custodv (COC) forms were not beina stored on -site at
WWTP. COC's were bing kept off site at Charlotte Labs. Please note that in accordance
with your NPDES Permit NC0085359, Part II, Section D Monitoring and Reporting, Items 6.
Records Retention, 7. Recording Results, and 8. Inspection and Entry, For each
measurement or sample taken prusuant to the requirements of this permit, the Permittee
shall record (a.) the date, exact place, and time of sampling or measurements. And have
access to a coDv of anv record that must be kept under the conditions of the Dermit.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment:
Chemical Feed
Yes No NA NE
Is containment adequate?
0
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Are backup pumps available?
0
❑
❑
❑
Is the site free of excessive leaking?
0
❑
❑
❑
Comment: Lime is being added at head of plant to aid alkalinity.
Page# 4
Permit: NCO085359
Inspection Date: 09/04/2019
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Grit Removal
Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment:
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: At time of inspection influent sampler was recorded at 1 degree Celsius.
Flow Measurement - Influent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
❑
Comment: Influent flow meter was last calibrated on March 19, 2019.
Nutrient Removal
Yes No NA NE
# Is total nitrogen removal required?
❑
❑
0
❑
# Is total phosphorous removal required?
❑
❑
0
❑
Type
# Is chemical feed required to sustain process?
❑
❑
❑
Is nutrient removal process operating properly?
E
❑
❑
❑
Comment: Treatment facility has 4 FAO basins with anoxic and oxic zones. Facility can also add
Sodium Aluminate to aid in phosphorous removal.
Page# 5
Permit: NCO085359
Inspection Date: 09/04/2019
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0
❑
❑
❑
Comment:
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
❑
❑
❑
Comment: At time of insDection three of four clarifiers were in ODeration. Effluent discharaina from
secondary clarifiers was clear with few suspended solids.
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Comment:
Aerobic Digester
Is the capacity adequate?
Yes No NA NE
■ ❑ ❑ ❑
Page# 6
Permit: NCO085359
Inspection Date: 09/04/2019
Aerobic Digester
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Filtration (High Rate Tertiary)
Type of operation:
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Comment: Facility has fabric covered drum filters. At time of in
visible suspended solids.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
Cross flow
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
on effluent was clear with no
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: UV system is to be replaced as part of the plant upgrade. Effluent sampler was recorded at
5 degrees Celsius.
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Solids Handling Equipment
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
Yes No NA NE
Page# 7
Permit: NC0085359
Inspection Date: 09/04/2019
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Comment: Belt filters were not in operation at time of inspection.
Yes No NA NE
❑
❑
❑
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Page# 8