HomeMy WebLinkAboutNC0084573_Inspection_20190918ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mr. Don Chamblee, Public Works Director
County of Lincoln
It 5 West Main Street
Lincolnton, NC 28092
Dear Mr. Chamblee:
NORTH CAROLINA
Enwhvftwenfaf Qegority
September 18, 2019
Subject: Compliance Evaluation Inspection
Lincoln County WTP
NPDES Permit No. NCO084573
Lincoln County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at the subject facility
on September 11, 2019, by Ori Tuvia. Adam Jolicoeur's cooperation during the site visit was much appreciated. Please
advise the staff involved with this NPDES Permit by forwarding a copy of the enclosed report.
The following should be addressed:
At the time of inspection, ORC logs were incomplete. 15A NCAC 08G .0204 (5) RESPONSIBILITIES OF AN
OPERATOR IN RESPONSIBLE CHARGE states that an ORC of a water pollution control system shall
"document the operation, maintenance, and all visitation of the system in a log that shall be maintained at the
system".
2. Chlorine standards must to be verified annually (in addition to the Chlorine curve)
The report should be self-explanatory; however, should you have any questions concerning this report, please
do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuviakncdenr.gov.
Sincerely,
Doccu/Signed by:
A14CC681AF27425...
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
Cc: NPDES, MRO Files (Laserfiche)
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704 663 1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCO084573 111 12 I 19/09/1, I17 18 I S I 19 I G I 201 I
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved -------------------
67
1.0 70 71 [„ I 72 n 73 L_LJ74 751
u u I I I I I I I80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:50AM 19/09/11
17/04/01
Lincoln County WTP
7674 Tree Farm Rd
Exit Time/Date
Permit Expiration Date
Denver NC 28037
11:20AM 19/09/11
20/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Adam Michael Jolicoeur/ORC/704-483-7070/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Adam Michael Jolicoeur,7674 Tree Farm Rd Denver NC 28037//704-483-7070/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Ori A Tuvia i DWR/MRO WQ/704-663-1699/ 9/18/2019
CC
EBB057A2DE017498...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
EDocuSigned by:
eyj 9/18/2019
AtaccsatAFvazs... Page#
NPDES yr/mo/day Inspection Type
NCO084573 I11 121 19/09/11 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO084573 Owner - Facility: Lincoln County WTP
Inspection Date: 09/11/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The subject permit expires on March 31, 2020.
The facillity is in the process of installing an additional screw press for sludge.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
❑
0
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑0
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: The Dermittee's records were organized and well maintained and records reauested durin
the inspection were readily retrievable. DMRs, COCs, ORC logs, and calibration logs were
reviewed for April 2019 through September 2019. 15A NCAC 08G .0204 (5)
RESPONSIBILITIES OF AN OPERATOR IN RESPONSIBLE CHARGE states that an ORC
of a water pollution control system shall "document the operation, maintenance, and all
visitation of the system in a log that shall be maintained at the system".
Page# 3
Permit: NCO084573 Owner - Facility: Lincoln County WTP
Inspection Date: 09/11/2019 Inspection Type: Compliance Evaluation
Record Keeping
Yes No NA NE
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: The permit requires grab samples for all required parameters.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
M
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Lincoln Countv WTP (certification #5025) perform samDlina for chlorine and DH. RA Labs
(Turbidity and TSS) and ETS Labs (Toxicity and metals) have also been contracted.
Chlorine standards, need to be verified annually (in addition to the Chlorine curve)
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Yes No NA NE
Liquid
❑
❑
❑
■
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
Page# 4
Permit: NCO084573 Owner - Facility: Lincoln County WTP
Inspection Date: 09/11/2019 Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Comment: Liquid sodium thiosulfate is used for dechlorination; stored within new building used for
sludge management
Are tablet de -chlorinators operational? ❑ ❑ 0 ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The flow meter was last calibrated on August 5, 2019 by Wright Instruments.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: At the time of the inspection the effluent appeared clear.
Drying Beds
Yes No NA NE
Is there adequate drying bed space?
0
❑
❑
❑
Is the sludge distribution on drying beds appropriate?
❑
❑
0
❑
Are the drying beds free of vegetation?
0
❑
❑
❑
# Is the site free of dry sludge remaining in beds?
0
❑
❑
❑
Is the site free of stockpiled sludge?
0
❑
❑
❑
Is the filtrate from sludge drying beds returned to the front of the plant?
❑
❑
0
❑
# Is the sludge disposed of through county landfill?
0
❑
❑
❑
# Is the sludge land applied?
0
❑
❑
❑
(Vacuum filters) Is polymer mixing adequate?
❑
❑
0
❑
Comment: The permittee previously used vacuum filter beds before the recent sludge handling
upgrade; they are no longer in service, only to be used in case of emergency. If drying
beds
are no longer needed, they should be removed from the permit during renewal process
prior
to being removed.
Page# 5
Permit: NC0084573
Inspection Date: 09/11/2019
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Owner - Facility: Lincoln County WTP
Inspection Type: Compliance Evaluation
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: sludge dewatering system (polymer addition, screw presses, screw conveyers, sludge
handling building and a truck loading bay).
Page# 6