June 18, 2012
L. Kirk Bass, Superintendent
Tar River Regional Wastewater Treatment Facility
P.O. Box 1180
Rocky Mount, North Carolina 27802
Dear Mr. Bass:
Dee Freeman
Secretary
Subject: Compliance Evaluation Inspection
City of Rocky Mount — Tar River Wastewater Treatment Facility
NPDES Permit Number NCO030317
Stormwater Permit Number NCG110030
Edgecombe County
On June 11, 2012 Mitch Hayes of the Raleigh Regional Office conducted a compliance evaluation
inspection of the subject facility. The assistance of Darrell Highsmith, Amanda James, Angie Boswell,
and you were gratefully appreciated. Please find the attached Basin Wide Information Management
System (BIMS) inspection checklist summarizing each inspection. Below is a list of recommendations
and findings developed from the inspection:
The reissued NPDES Permit NCO030317 effective July 01, 2010 and will expire October 31,
2014. Permit renewal is required within 6 months of the permit expiration date.
2, BIMS lists L. Kirk Bass as the Operator in Responsible Charge (ORC) wastewater grade 4
certified (WW-4), Darrell Highsmith as back-up ORC (bORC) WW-4, and David J. Gardner as
bORC WW-4.
3. The 21.0 MGD wastewater treatment facility consists of the following units: influent screw pump
station with 4 screws; 4 automatic bar screens with grit channels; 4 parallel biological nutrient
reduction (BNR) trains utilizing the Anaerobic — Anoxic — Oxic (A20) process with a total of 8
aeration basins, 8 secondary clarifiers and 8 tertiary filters; 1 chlorine contact basin providing 30
minute detention time; 1 dechlorination contact basin; post aeration basin; 4 — 1.5 million gallon
aerobic digesters with pump station; 2 dissolved air floatation (DAF) thickeners with pump
station; 1 sludge truck loading station; an oxygen, generation plant; 3 on site generators capable
of operating the entire plant; 2 reclaim secondary clarifiers with pump station; in house plant
process water distribution system and 1 sodium hydroxide feed system for pH control.
4. At the time of inspection, automatic and manual bar screens and grit removal system were
functioning normally. The following were not in service due to low inflow: 2 out of 4 influent
screw pumps; the "C° automatic bar screen; aeration basin B and the 2 associated rectangle
secondary clarifiers and the # 4 tertiary clarifier; the DAF thickeners and associated pump
station and the #3 digester. The oxygen generation plant was offline and is considered a back-
up source for oxygen. Compressed liquid oxygen is used as an oxygen source in the A20
process. Sludge blanket in the C1 seconda clarifier was 3 feet and 5 feet in secondary clarifier
North Carolina Division of Water Quality Raleigh Regional Office Surface Water Protection Phone (919) 791-4200 Customer Service
Internet: www,rcwaterquality.org 1628 Mai! Service Center Raleigh, NC 27699-1628 FAX (919) 788-7159 877-623-6748
Location: 3800 Barrett Drive Raleigh, NC 27609
NorthCarolina
An Equal OpportunitylAffirmative Action Employer— 50% Recycled110°/ Post Consumer Paper Naturally
Tar River Regional WWTF CFI
Page 2
4
D2. Both clarifiers have 15 foot sidewall depths. Effluent in the wet well at the tertiary filters
appeared clear with no foam. Effluent appeared cleared flowing over the weirs in clarifiers C1
and D2. Effluent flowing into the Tar River appeared clear with little foam, dissipating within 30
feet.
5. Biosolids are land applied under the City of Rocky Mount Land Application Permit WQC005568.
The permit will expire October 31, 2016. Granville Farms Inc. is contracted for transportation,
application, and overseeing of the land application program.
6. The laboratory was checked in a cursory manner. All instrument calibration logs are maintained
in a log book. Fecal coliform bath temperature was 44.3 degrees C and the laboratory
refrigerator was 1.5 degrees C. BOD incubator temperature was 19.8 C. All thermometers are
checked against a certified thermometer. The influent and effluent flow meters were calibrated
June 05, 2012 by plant staff. The influent sampler temperature was 0.5 degrees C and the
effluent sampler temperature was 1 degree C.
7. Discharge Monitoring Reports (DMR's) for the period December 2010 through April 2012 were
reviewed for compliance with permit limits and monitoring requirements. A Notice of Violation
was issued for not meeting daily minimum pH on August 31, 2011. This violation has been
addressed. There were no other violations listed for the review period.
8. The Permittee is a member of the Tar -Pamlico River Basin Association. The Phase III Nutrient
caps for the Tar -Pamlico River Basin Association for total nitrogen is 891,272 pounds per year
(lblyr) and 161,070 Ib/yr for total phosphorus. Based upon the 2011 annual report, the Tar -River
Basin Association was well under the nutrient cap for total nitrogen and total phosphorus.
Stormwater Permit NCG110030
9. Inspection of the stormwater outfalls and plant site were conducted at the same time as the CEI
for the Wastewater Treatment Facility. Permit NCG110030 was reissued and became effective
on June 01, 2008 and will expire on May 31, 2013. Permit renewal is required within 6 months
prior to permit expiration date.
10. There are 2 stormwater outfalls listed for the facility. The last completed stormwater qualitative
monitoring report for both outfalls was December 22, 2011. There is no vehicle maintenance
done on site. The stormwater pollution prevention control plan is reviewed and amended if
needed, annually. Please be sure to document all spill and clean up efforts that occur in keeping
with requirements of your stormwater pollution prevention plan. Annual employee training on
spill prevention and response occurred on May 07, 2012,
would like to thank you, Darrell Highsmith, Amanda James, and Angie Boswell for your time and
assistance with this inspection. If you have any questions about this report or the inspection, please
contact me at 919.791.4261.
Sincerely,
A., �J.�AT)
Mitch Hayes
Environmental Specialist
Cc; Permit files
Central Files
i
Permit: NCG110030
SOC:
County: Edgecombe
Region: Raleigh
Compliance Inspection Report
Effective: 06/01 /08
Effective:
Contact Person: Wayne A Hollowell
Directions to Facility:
System Classifications:
Primary ORC,
Secondary ORC(s):
On -Site Representative(s):
24 hour contact name Leon Bass
On -site representative Leon Bass
Related Permits:
Expiration: 05/31/13 Owner: City of Rocky Mount .
Expiration: Facility: Tar River Regional WWTP
3031 Water Treatment Plant Rd
NC Hwy 97 E
Rocky Mount NC 27802
Title: Phone: 252-972-1291
Certification:
W00005568 City of Rocky Mount - City of Rocky Mount Residuals Land
Application Program
NCO030317 City of Rocky Mount - Tar River Regional WWTP
WQCS00011 City of Rocky Mount - Rocky Mount Collection System
Phone:
Phone: 252-972-1400
Phone: 252-972-1400
Inspection Date: 06/1112012 Ent Time' 1/0::15 AM Exit Time: 12:36 PM
Primary Inspector: Mitchell S Hayes dw 1 `] ' Phone: 919-791-4200
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Municipal WWTP > 1 MGD, Stormwater Discharge, COC
Facility Status: ■ Compliant ❑ Not Compliant
Question Areas:
0 Storm Water
(See attachment summary)
Page: 1
t
Permit: NCG110030 Owner - Facility: City of Rocky Mount
Inspection Date: 06/11/2012 inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
There are 2 stormwater outfalls listed for the facility. Each outfall discharge is driven by a stormwater retention pond. The
last completed stormwater qualitative monitoring report for both outfalls was December 22, 2011. There is no vehicle
maintenance done on site. There have been three by-passes during the review period, all occurring in 2011. The
stormwater pollution prevention control plan is reviewed and amended if needed, annually. Annual employee training on
spill prevention and response occurred on May 07, 2012.
Page: 2
Permit: NCG110030 Owner - Facility: City of Rocky Mount
Inspection Date: 06/11/2012 Inspection Type: Compliance Evaluation
Stormwater Pollution Prevention Plan
Does the site have a Stormwater Pollution Prevention Plan?
# Does the Plan include a General Location (USGS) map?
# Does the Plan include a "Narrative Description of Practices"?
# Does the Plan include a detailed site map including outfall locations and drainage areas?
# Does the Plan include a list of significant spills occurring during the past 3 years?
# Has the facility evaluated feasible alternatives to current practices?
# Does the facility provide all necessary secondary containment?
# Does the Plan include a BMP summary?
# Does the Plan include a Spill Prevention and Response Plan (SPRP)?
# Does the Plan include a Preventative Maintenance and Good Housekeeping Plan?
# Does the facility provide and document Employee Training?
# Does the Plan include a list of Responsible Party(s)?
# Is the Plan reviewed and updated annually?
# Does the Plan include a Stormwater Facility Inspection Program?
Has the Stormwater Pollution Prevention Plan been implemented?
Reason for Visit: Routine
Comment:
Qualitative Monitoring
Has the facility conducted its Qualitative Monitoring semi-annually?
Comment: monitoring was last completed 12.22.2011
Permit and Outfalls
# Is a copy of the Permit and the Certificate of Coverage available at the site?
# Were all outfalls observed during the inspection?
# If the facility has representative outfall status, is it properly documented by the Division?
# Has the facility evaluated all illicit (non stormwater) discharges?
Comment: There are 2 stormwater outfalls listed for the facility. Each outfall is driven
by a stormwater retention pond.
Yes No NA NE
Yes No NA NE
Page: 3
o
ffl•
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Coleen H. Sullins Dee Freeman
Governor Director Secretary
March 18, 2010
City of Rocky Mount
Mr, Wayne Hollowell
Director of Water Resources
PO Drawer 1180
Rocky Mount, NC 27802-1180
Subject: Compliance Evaluation Inspections
Tar River Regional Wastewater Treatment Plant
NPDES Wastewater Permit NC0030317 and
,NPDES Stormwater Permit NCG 110030
Edgecombe County
Dear Mr. Hollowell:
1, Dave Parnell of the Raleigh Regional Office of the Division of Water Quality conducted two compliance
evaluation inspections (CEI) on March 15, 2010, consisting of the NPDES wastewater and stormwater
inspections. The assistance of L. Kirk Bass, Operator in Responsible Charge (ORC), Darrell Highsmith,
Backup ORC, Angela Boswell, Compliance Administrator and Brent Bent, Laboratory Supervisor, was
appreciated. Please review the attached Basinwide Information Management System (BIMS) inspection
checklists summarizing the inspections.
Below is a list of findings and recommendations developed from the inspections:
1. NPDES Wastewater Inspection,
1. The current permit re -issuance is pending. The application timeframe was adhered to by the facility.
2. The 21.0 MGD wastewater treatment plant consists of the following units: influent pump station,
mechanical bar screens, grit chamber, parshall flume, pure oxygen A/O process aeration basin,
secondary clarifiers, tertiary filters, chlorination basins, de -chlorination basins, post aeration basins,
and aerobic sludge digesters.
N` hCarolina
aturally
- l -North Carolina Division of Water Quality Raleigh Regional Office - Surface Water Protection Phone (919) 791-4200 Customer Service
Internet: www.ncwaterquality.org 1628 Mail Service Center Raleigh, NC 27699.1628 FAX (919) 571-4718 1-877-623.6748
An Equal Opportunity/Affirmative Action Employer — 50% Recycled/1 0% Post Consumer Paper
City of Rocky Mount Tar River_ Wastewater Treatment Plant NPDES Wastewater and Stormwater CEI
3. The inspection began in the treatment plant office. All paperwork was well organized and easily
accessible. Discharge Monitoring Reports were reviewed for compliance with permit limits and
monitoring requirements. Chain of custody records were available and found to be in order. The
laboratory is state certified and performs the majority of permit required parameters. A contract lab,
Tritest, performs the remainder of the parameters required by the permit.
4. Overall maintenance was found to be in good condition. The mechanical bar screen was in
acceptable condition. Grit removal was free of organic matter and excessive odor. Debris is
removed as needed and taken to the landfill.
5. The clarifiers were functioning properly and were free of weir blockages and showed no sign of
short-circuiting. The sludge blanket was reported to be 3 feet, which is within the acceptable range
of sidewall depth.
6. Biological nutrient removal is conducted at the facility. The plant meets its obligation to the Tar -
Pam Association.
7. The tertiary filters, oxygen production system, chlorination and de -chlorination systems, all,
appeared to be functioning properly.
8. The aerobic digester appears to have adequate capacity with no objectionable odor.
9. Standby power, consisting of three generators, is available and is tested on a monthly basis. The
generators have the capacity to run the entire wastewater treatment site.
10. The effluent pipe is located across from the treatment plant entrance on NC 97. The effluent
discharging into Tar River appeared to be clear. The receiving water is free of foam and other
debris.
II. NPDES Stormwater Inspection:
1. The stormwater pollution prevention plan (SP3) was reviewed and found to be compliant with the
permit. All regular inspections and duties, including training, annual review, qualitative monitoring,
knowledge and inspections of secondary containment are being accomplished as required by the
stormwater permit.
NorthCaroiina
,Naturally
- 2 -North Carolina Division of Water Quality Raleigh Regional Office Surface Water Protection Phone (919) 791-4200 Customer Service
Internet: www.ncwaterquality.org 1628 Mail service Center Raleigh, NC 27699-1628 FAX (919) 571-4718 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer— 50% Recycled/10% Post Consumer Paper
City of Rocky Mount Tar River Wastewater Treatment Plant NPDES Wastewater and Stormwater CEI
The City of Rocky Mount Tar River Wastewater Treatment Plant is considered to be in compliance with the
NPDES wastewater permit, as well as the NPDES general stormwater permit, at the time of these
inspections. Please continue your diligence in the proper operation and maintenance of the facility. if you
have questions concerning this report, please do not hesitate to contact me at 919-791-4200.
Sincerely,
Dave Parnell
Environmental Specialist
Raleigh Regional Office
Attachment: March 15, 2010 NPDES Wastewater and Stormwater CEI BIMS Inspection
Checklists
cc: Central Files
SWP/RRO files
!�or`hCarolina
Natma!!J
- 3 -North Carolina Division of Water Quality Raleigh Regional Office Surface Water Protection Phone (919) 791. 4200 Customer Service
Internet: www.ncwaterquality,org 1628 ,Mail Service Center Raleigh, NC 27699-1628 FAX (919) 371-4718 1-877.623.6748
An Equal Opportunity/Affirmative Action Employer— 50% Recycledll0% Post Consumer Paper
Compliance Inspection Report
Permit: NCG110030 Effective:06/01108 Expiration: 05/31/13
SOC: Effective: Expiration:
County: Edgecomhe
Region: Raleigh
Contact Person: Wayne A Hallowell Title:
Directions to Facility:
System Classifications:
Primary ORC: Certification:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Owner: City of Rocky Mount
Facility: Tar River Regional WWTP
3031 Water Treatment Plant Rd
NC Hwy 97 E
Rocky Mount NC 27802
Phone: 252-972-1291
Phone:
Inspection Date: 03/15/2010 Entry Time: 09:30 AM Exit Time: 0,2:330 PM
Primary Inspector: David R'Parnell 4A4,n 61 ` J ! Phone: 919-791-4260
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Municipal VVWTP > 1 MGD, Stormwater Discharge, COC
Facility Status: ■ Compliant ❑ Not Compliant
Question Areas:
. Storm Water
(See attachment summary)
Page: 1
Permit: NCG110030 Owner - Facility: City of Rocky Mount
Inspection Date: 03/15/2010 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Inspection Summary:
Stormwater Pollution Prevention Plan
Yes
No
NA
NE
Does the site have a Stormwater Pollution Prevention Plan?
■
❑
❑
❑
# Does the Plan include a General Location (USGS) map?
■
❑
❑
❑
# Does the Plan include a "Narrative Description of Practices"?
■
❑
❑
❑
# Does the Plan include a detailed site map including outfall locations and drainage areas?
■
❑
❑
❑
# Does the Plan include a list of significant spills occurring during the past 3 years?
■
❑
❑
❑
# Has the facility evaluated feasible alternatives to current practices?
■
❑
❑
❑
# Does the facility provide all necessary secondary containment?
■
❑
❑
❑
# Does the Plan include a BMP summary?
■
❑
❑
❑
# Does the Plan include a Spill Prevention and Response Plan (SPRP)?
■
❑
❑
❑
# Does the Plan include a Preventative Maintenance and Good Housekeeping Plan?
■
❑
❑
❑
# Does the facility provide and document Employee Training?
■
❑
❑
❑
# Does the Plan include a list of Responsible Party(s)?
■
❑
❑
❑
# Is the Plan reviewed and updated annually?
■
❑
❑
❑
# Does the Plan include a Stormwater Facility Inspection Program?
■
❑
❑
❑
Has the Stormwater Pollution Prevention Plan been implemented?
■
❑
❑
❑
Comment:
Qualitative Monitoring Yes No NA NE
Has the facility conducted its Qualitative Monitoring semi-annually? ■ ❑ Cl ❑
Comment:
Permit and Outfalls Yes No NA NE
# Is a copy of the Permit and the Certificate of Coverage available at the site?
■
❑
❑ ❑
# Were all outfalls observed during the inspection?
■
❑
❑ ❑
# If the facility has representative outfall status, is it properly documented by the Division?
❑
❑
■ ❑
# Has the facility evaluated all illicit (non stormwater) discharges?
■
❑
❑ ❑
Comment:
Page: 2
�CF W A L499 Michael F. Easley, Governor
0 y William G. Ross, Jr., Secretary
C North Carolina Department of Environment and Natural Resources
O 'C
Colleen H. Sullins, Director
Division of Water Quality
lb January 2008
Wayne Hollowell
Director of Water Resources n
P.O. Drawer 1180 ? JAN x -:C���
Rocky Mount, NC 27802-1180 �1
Subject: Compliance Evaluation Inspections of
NPDES Wastewater Permit NCO030317 &
NPDES Stormwater Permit NCG110030
City of Rocky Mount
Tar River Regional Wastewater Treatment Plant
Edgecombe County
Dear Mr. Hollowell:
I, Ron Boone, of the NC Division of Water Quality (DWQ), Raleigh Regional Office (RRO), Surface
Water Protection (SWP) section, conducted wastewater and stormwater compliance evaluation inspections
(CEI) of the subject facility on 8 January 2008. The cooperation and assistance of the Operator in
Responsible Charge (ORC), Leon K. Bass, and the backup ORCs, Darrell Highsmith and Angela Boswell,
were greatly appreciated. The results of the CEI are summarized below and in the attached inspection
reports.
2. This is a Grade IV facility and it is located at 3031 Water Treatment Plant Road in Rocky Mount,
Edgecombe County, NC. It is just north of NC Hwy 97, between Deer Run Road and Cool Springs Road.
The NCO030317 permit allows the discharge of treated wastewater into the Tar River from the Tar River
Regional Wastewater Treatment Plant (WWTP) and the NCGI10030 permit/Certificate of Coverage
(COC) allows the discharge of stormwater to the Tar River from stormwater point source discharges
associated with activities classified as treatment works treating primarily domestic sewage. This section
of the Tar River is currently classified as a Class C, nutrient sensitive water.
3. The plant description in the permit is accurate except for the sludge thickener. This unit can be added to
the plant description in the next permit renewal cycle.
4. The plant is very well operated and maintained. The grounds were well kept and all equipment was in
very good condition. Some minor maintenance work was being done to the grit removal units that were
inactive at the time of the inspection.
5. The flow meters are calibrated monthly and the composite samplers are set up to draw flow proportional
samples over a 24-hour period. Sample coolers were both at 4 degrees Celsius during the inspection.
6. The clarifiers, tertiary filters, chlorination and dechlorination systems and final aeration systems were all
operating normally. No discrepancies were noted.
NOne
Carol na
,1�atural�y
North Carolina Division of Water Quality Raleigh Regional Office Surface Water Protection Phone (919) 791-4200 Customer Service
Internet: h2o.enr.state.nc.uS 1628 Mail Service Center Raleigh, NC 27699-1629 FAX (919) 791-4718 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer— 50% Recycled110% Post Consumer Paper
City of Rocky Mount, Tar River Regional Wastewater Treatment Plant
Compliance Evaluation Inspection
NC00303 t 7 & NCG 110030 t
16 January 2008, Page 2 of 2
Two of the four 1.5 million -gallon aerobic digesters were full and in operation during the inspection. Mr.
Highsmith stated that they would likely place another in operation soon to increase capacity and help
avoid foaming problems.
The operator's visitation and operations and maintenance logs were complete and up-to-date. The
laboratory records were also found to be complete and accurate. A review of discharge monitoring reports
for the months-,of"July and October 2007 yielded no errors or inconsistencies with laboratory bench sheets.
The lab is state certified and performs the majority of the permit -required parameters except for the
metals, toxicity'and-pnority pollutants scans.
9. The stormwater pollution prevention plan required by the NCG110030 permit was reviewed and found to
be complete and up-to-date. All regular checks and duties, including training, annual review, qualitative
monitoring, inspection of secondary containments, etc, are being accomplished as required.
10. Please continue your diligence in the proper operation and maintenance of the Tar River WWTP. Should
you or your staff have any questions regarding the inspection or this notice, please do not hesitate to
contact me at 919-791-4200.
Sincerely,
Ronald C. Boone
Environmental Specialist
Surface Water Protection Section
Raleigh Regional Office
Attachments:
1. Inspection Checklist NCO030317
2. Inspection Checklist NCG110030
CC: Central Files w/ atchs
NPDES West Permitting Unit w/ atchs
RRO/SWP Files w/ atchs
Attn: Leon Kirkland Bass, Operator in Responsible Charge
Tar River Regional Wastewater Treatment Plant
P.O. Drawer 1180
Rocky Mount, NC 27802-1180
w/Atchs
Permit: NCG110030
SOC:
County: Edgecombe
Region: Raleigh
Compliance Inspection Report
Effective: 04/25/03
Effective:
Contact Person: Stephen W Raper
Directions to Facility:
System Classifications:
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
24 hour contact name
On -site representative
Related Permits:
Inspection Date: 01108/2008
Primary Inspector: Ron Boone
Secondary Inspector(s):
Expiration: 04/30/08
Expiration:
Title: City Manager
Leon Kirkland Bass
Leon Kirkland Bass
Entry Time: 1Z30 PM
Certification:
Owner: City of Rocky Mount
Facility: Tar River Regional WWTP
3031 Water Treatment Plant Rd
NC Hwy 97 E
Rocky Mount NC 27802
Phone: 252-972-1111
Exit Time: 04:30 PM
Phone:
Phone: 252-972-1407
Phone: 252-972-1407
Phone: 919-791-4200
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Municipal WWTP > 1MGD, Stormwater Discharge, COC
Facility Status: ■ Compliant ❑ Not Compliant
Question Areas:
Storm Water
(See attachment summary)
Page: 1
Permit: NCG110030 Owner . Facility: City of Rocky Mount
Inspection pate: 01/08/2008 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Very good inspection. No discrepancies found.
Page: 2
Permit: NCG110030 Owner - Facility: City of Rocky Mount
Inspection Date: 01/08/2008 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Stormwater Pollution Prevention Plan Yes No NA NE
Does the site have a Stormwater Pollution Prevention Plan?
■
❑
❑
❑
# Does the Plan include a General Location (USGS) map?
■
Cl
❑
❑
# Does the Plan include a "Narrative Description of Practices"?
■
❑
❑
❑
# Does the Plan include a detailed site map including outfall locations and drainage areas?
■
❑
Cl
❑
# Does the Plan include a list of significant spills occurring during the past 3 years?
■
❑
❑
❑
# Has the facility evaluated feasible alternatives to current practices?
■
❑
❑
❑
# Does the facility provide all necessary secondary containment?
■
❑
❑
❑
# Does the Plan include a SMP summary?
■
Cl
❑
❑
# Does the Plan include a Spill Prevention and Response Plan (SPRP)?
■
❑
❑
❑
# Does the Plan include a Preventative Maintenance and Good Housekeeping Plan?
■
Cl
❑
❑
# Does the facility provide and document Employee Training?
■
❑
❑
❑
# Does the Plan include a list of Responsible Party(s)?
■
❑
❑
❑
# Is the Plan reviewed and updated annually?
■
❑
❑
❑
# Does the Plan include a Stormwater Facility Inspection Program?
■
❑
❑
❑
Has the Stormwater Pollution Prevention Plan been implemented?
■
❑
❑
❑
Comment:
Qualitative Monitoring
Yes
No
NA
NE
Has the facility conducted its Qualitative Monitoring semi-annually?
■
❑
❑
❑
Comment:
Analytical Monitoring
Yes
No
NA
NE
Has the facility conducted its Analytical monitoring?
❑
❑
■
❑
# Has the facility conducted its Analytical monitoring from Vehicle Maintenance areas?
❑
❑
■
❑
Comment: No analytical monitoring is required.
Permit and Outfalls
Yes
No
NA
NE
# Is a copy of the Permit and the Certificate of Coverage available at the site?
■
❑
Cl
❑
# Were all outfalls observed during the inspection?
■
❑
❑
❑
# If the facility has representative outfall status, is it properly documented by the Division?
❑
❑
■
❑
# Has the facility evaluated all illicit (non stormwater) discharges?
■
❑
❑
❑
Comment:
Page: 3
�11i
T
1 a
Mr. Paul B. Blount
Director of Water Resources
City of Rocky Mount
P.O. Box 1180
Rocky Mount, NC 27802-1180
Dear Mr. Blount:
14 November 2006
Michael F. Easley, Governor
William G. Ross, In, Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E., Director
Division of Water Quality
Subject: Compliance Evaluation Inspections
Tar River Regional Wastewater Treatment Plant
NPDES Wastewater Permit NCO030317 and
Stormwater Permit NCG 110030
Nash County
On 8 November 2006, I, Ron Boone, of the NC Division of Water Quality (DWQ), Raleigh Regional
Office (RRO), conducted a compliance evaluation inspection at the Tar River Regional Wastewater
Treatment Plant (WWTP) for both of the subject permits. The assistance and cooperation of Mr.
Wayne Hollowell, Plant Superintendent, Darrell Highsmith, Chief Operator, Leon Bass, Electrical
Supervisor, and Dennis Carpenter, Maintenance Supervisor, was helpful and appreciated. Inspection
reports are attached for your records. Inspection findings are listed below.
2. This plant discharges to the Tar River, this segment of which is classified as a class C, nutrient
sensitive water (NSW) in the Tar Pamlico river basin. The plant is as described in the permit. There
is ongoing construction to install additional aerobic digesters.
3. All plant components were inspected. In general the plant was very clean and well maintained. No
components were noted as inoperable or poorly maintained.
4. The plant experienced a marked increased in flow on the 7th/8th of November as a result of the rain
event of 7 November. According to the operators, just over an inch of rain fell during this rain event.
The marked increase in plant flow strongly indicates the presence of heavy inflow/infiltration (1&1) in
the collection system. The City must undertake measures to identify and correct all sources of I&I in
a timely fashion. Such I&I not only makes the City vulnerable to violations related to the collection
system bui also jeopardizes the plant's ability to treat the wastewater and reduces its ability to remain
compliant with permit limits. Efforts to address this problem should be initiated immediately as
rehabilitation of the collection system can be a very time consuming process.
5. Our records indicate that Mr. Bass is the Operator in Responsible Charge (ORC) of the plant and that
Mr. Hollowell and Mr. Highsmith are backup ORCs. Please submit the necessary paperwork to the
Division to ensure the ORCs are properly reflected in our records.
none h Caro[ina
�atura!!y
North Carolina Division of Water Quality Raleigh Regional Office Surface Water Protection Phone (919) 7914200 Customer Service
Internet: h2o.enrstate.no.us 1629 Mail Service Center Raleigh, NC 27699-1628 FAX (919) 571-4718 1-877-623-6748
An Equal OpportunitylAfTirmative Action Employer— 50% Recycledl10% Past Consumer Paper
Tar River Regional WWTP, Compliance Evaluation Inspection, NCO030317 l 1/14/2006, Page 2 of 2
...rr.;,..L4'. sti.-=:ec''afa.�.`�::•.: i1,1'�.•r...Aw+7
V
6. All plant records were reviewed including the operator's -visitation -log, operations and maintenance
logs, discharge monitoring reports (DMR) for 2006, laboratory calibration records and chains of
custody. All were up to date and compliant. Additionally, January and March 2006 DMRs were
compared to laboratory bench sheets and no transcription errors were noted.
7. The influent and effluent samplers were inspected. The thermometer in the influent sampler read 0.7
degrees Celsius at the time of the inspection. Please have your laboratory personnel check the
accuracy of this thermometer and then adjust the temperature setting for the sampler to maintain the
temperature between 1.0 and 4.4 degrees Celsius.
8. The discharge from the plant was observed. No excessive foam, solids or other pollutant indicators
were noted. The right-of-way to the outfall is well maintained.
9. The stormwater program was also reviewed. All records of qualitative monitoring, facility
inspections, secondary containment inspections and employee training, as well as the site map and
general location map were reviewed and found to be compliant. Stormwater discharge outfalls were
inspected and no excessive foams, solids, sheens, or other pollutant indicators were noted.
10. If you or your staff has any questions regarding the inspection or this letter, please feel free to call me
for assistance at 919-791-4200.
Sincerely,
Ronald C. Boone
Environmental Technician 1V
Raleigh Regional Office
cc: Central Files
RROISWP Files
Wayne Hollowell
3031 Water Treatment Plant Road
NC Hwy 97 East
Rocky Mount, NC 27802
Attachments:
1. Final Inspection Checklist
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Ins ection Re ort
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN1 2 I5I 31 NC003a317 11 121 06/11./oa 117 18ICI 19Isl 20I
lJ
Remarks
21 6
Inspection Work Days Facility Self -Monitoring Evaluation Rating 61 OA --------------------------- Reserved ----- ----------------
671 169 70 11 711 I 721 N I 73 LU 74 751 I I 1 I 1 1 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:30 AM 06/1-1/013
C5/01/01
Tar River Regional WWTP
Exit Time/Date
Permit Expiration Date
3031 Water Treatment Plant Rd
Rocky Mount NC 27802
01:30 PM 06/11/08
09/10/31
Name(s) of Onsite Representative(s)[Titles(s)]Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Paul 9 Blount,PO Box 1180 Rocky Mount NC Contacted
278021180//252-972-1232/2529721232 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit ■ Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory Storm Water
Section D: Summary of Finding/Comments Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boo RRO WO//919-791-4200/
Signature of M gement O A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previ ditio are obsolete.
Page # 1
NPDES yr/molday Inspection Type
NCO030317 I11 12I 06/11/06 117 18ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page # 2
Permit: NCO030317
Inspection Date: 11/08/2006
Owner - Facility: Tar River Regional WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance
Yes
No
NA
NE
Is the plant generally clean with acceptable housekeeping?
■
n
n
0
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge
■
n
n
n
Judge, and other that are applicable?
Comment:
Permit
Yes
_
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
n
n
■
M
Is the facility as described in the permit?
■
n
n
n
# Are there any special conditions for the permit?
n
■
n
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
n
n
n
Comment: No special conditions.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
n
n
Is all required information readily available, complete and current?
■
n
n
n
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
n
n
n
Are analytical results consistent with data reported on DMRs?
■
n
n
❑
Is the chain -of -custody complete?
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
fi
f]
Has the facility submitted its annual compliance report to users and DWQ?
■
n
n
n
(If the facility is = or > 5 MGD permitted flow) Do they operate 24f7 with a certified operator on each shift?
■
n
n
n
Is the ORC visitation log available and current?
■
n
n
n
Is the ORC certified at grade equal to or higher than the facility classification?
■
n
n
n
Is the backup operator certified at one grade less or greater than the facility classification?
■
n
Is a copy of the current NPDr=S permit available on site?
■
n
n
❑
Page # 3
11
Permit: NCO030317
Inspection Date: 11108l2006
Owner - Facility: Tar River Regional WWTP
Inspection Type: Compliance Evaluation
Record Keep'
Yes
No
NA
NE
Facility has copy of previous year's Annual Report on file for review?
■
Cl
Cl
❑
Comment:
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
■
rl
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
■
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■
❑
Comment:
Flow Measurement - Influent
Yes
No
NA
NE
# Is flow meter used for reporting?
❑
■
❑
❑
Is flow meter calibrated annually?
■
❑
❑
❑
Is the flow meter operational?
■
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
■
❑
❑
❑
Comment: Calibrated monthly.
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
■
❑
❑
❑
Is flow meter calibrated annually?
■
❑
Cl
❑
Is the flow meter operational?
■
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
■
❑
❑
❑
Comment: Calibrated monthly.
Aerobic Digester
Yes
No
NA
NE
Is the capacity adequate?
■
❑
❑
❑
Is the mixing adequate?
■
❑
❑
Cl
Is the site free of excessive foaming in the tank?
■
❑
❑
❑
# Is the odor acceptable?
■
❑
❑
❑
# Is tankage available for properly waste sludge?
■
❑
❑
❑
Comment:
Pump Station - Influent
Yes
No
NA
NE
Is the pump wet well free of bypass tines or structures?
■
❑
❑
❑
Is the wet well free of excessive grease?
■
❑
❑
❑
Are all pumps present?
■
❑
❑
❑
Page # 4
Permit: NC0030317
Owner - Facility: Tar River Regional WWTP
Inspection Date: 11/08/2006
Inspection Type: Compliance Evaluation
Pump Station - Influent
Yes
No
NA
NE
Are all pumps operable?
■
❑
❑
❑
Are float controls operable?
❑
❑
■
n
Is SCADA telemetry available and operational?
00
■
1=1
Is audible and visual alarm available and operational?
00
■
n
Comment:
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
❑
b.Mechanical
■
Are the bars adequately screening debris?
■
❑
❑
❑
Is the screen free of excessive debris?
■
n
n
n
Is disposal of screening in compliance? ■ ❑ ❑ ❑
Is the unit in good condition? ■ n ❑ ❑
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
■
Is the grit free of excessive organic matter?
■
n
❑
❑
Is the grit free of excessive odor?
■
n
n
❑
# Is disposal of grit in compliance?
■
n
n
n
Comment:
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
■
❑
n
n
Is the site free of excessive buildup of solids in center well of circular clarifier?
■
n
n
n
Are weirs level?
■
n
n
n
Is the site free of weir blockage?
■
n
n
n
Is the site free of evidence of short-circuiting?
■
n
n
n
Is scum removal adequate?
■
❑
n
n
Is the site free of excessive Floating sludge?
■
❑
❑
n
Page # 5
Permit: NCO030317 Owner - Facility: Tar River Regional WWTP
Inspection Date: 11/08/2006 Inspection Type: Compliance Evaluation
Secondary Clarifier
Yes
No
NA
NE
Is the drive unit operational?
■
n
❑
❑
Is the return rate acceptable (low turbulence)?
■
n
n
❑
Is the overflow clear of excessive solids/pin floc?
■
n
n
n
Is the sludge blanket level acceptable? (Approximately'/, of the sidewall depth)
In
n
Cl
n
Comment:
Aeration Basins .
Yes
No
NA
NE
Mode of operation
Ext.
Air
Type of aeration system
Surface
Is the basin free of dead spots?
■
n
n
n
Are surface aerators and mixers operational?
■
❑
n
❑
Are the diffusers operational?
n
n
■
n
Is the foam the proper color for the treatment process?
■
n
n
n
Does the foam cover Tess than 25% of the basin's surface?
■
D
n
n
Is the DO level acceptable?
■
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mgll)
■
Q
❑
❑
Comment:
Pure Oxygen
Yes
No
NA
NE
Type of pure oxygen system
Generated
on -site
Is there a back-up source for the system?
■
n
n
n
Are mixers operational?
■
n
n
n
Are samples port/points easily accessible?
n
n
❑
■
Comment:
Filtration Hi h Rate Tertiary)
Yes
No
NA
NE
Type of operation:
Down
Flow
Is the filter media present?
■
❑
❑
n
Is the filter surface free of clogging?
■
❑
❑
❑
Is the filter free of growth?
■
n
n
n
Is the air scour operational?
n
n
■
n
Is the scouring acceptable?
❑
❑
■
n
Is the clear well free of excessive solids and filter media?
■
n
n
n
Page
# 6
Permit: NC0030317 Owner - Facility: Tar River Regional WVVfP
Inspection Date: 11/08/2006 Inspection Type: Compliance Evaluation
Filtration Huh Rate Tertiary)
Yes
No
NA
NE
Comment:
Disinfection -Gas
Yes
No
NA
NE
Are cylinders secured adequately?
■
n
n
n
Are cylinders protected from direct sunlight?
■
rl
n
❑
Is there adequate reserve supply of disinfectant?
■
n
F1
n
Is the level of chlorine residual acceptable?
n
n
n
■
Is the contact chamber free of growth, or sludge buildup?
■
n
n
n
Is there chlorine residual prior to de -chlorination?
n
n
n
■
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
■
n
n
n
If yes, then is there a Risk Management Plan on site?
❑
❑
❑
■
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment:
De -chlorination
Yes
No
NA
NE
Type of system ?
Gas
Is the feed ratio proportional to chlorine amount (1 to 1)?
n
n
n
■
Is storage appropriate for cylinders?
■
n
n
n
# Is de -chlorination substance stored away from chlorine containers?
■
n
n
n
Comment:
Are the tablets the proper size and type?
❑
❑
■
Are tablet de -chlorinators operational?
n
n
■
n
Number of tubes in use?
Comment:
Standby Power
Yes
No
NA
NE
Is automatically activated standby power available?
■
n
n
n
Is the generator tested by interrupting primary power source?
■
n
n
n
Is the generator tested under load?
■
n
n
n
Was generator tested & operational during the inspection?
n
■
n
n
Do the generator(s) have adequate capacity to operate the entire wastewater site?
■
❑
D
0
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
■
❑
D
❑
Page # 7
n
Permit: NCO030317
Inspection Date: 1110812006
Owner - Facility: Tar River Regional WWTP
Inspection Type: Compliance Evaluation
StandbyPower
Yes
No
NA
NE
Is the generator fuel level monitored?
■
n
❑
❑
Comment: Generators run by city electrical department; not available during
inspection.
Pumps-RASMAS
Yes
No
NA
NE
Are pumps in place?
■
n
n
n
Are pumps operational?
■
n
n
n
Are there adequate spare parts and supplies on site?
■
n
❑
n
Comment:
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
■
n
n
n
Are all other parameters(excluding field parameters) performed by a certified lab?
■
n
n
n
# is the facility using a contract lab?
■
n
n
n
Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
■
n
n
n
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
■
n
n
n
Incubator (BOD) set to 20.0 degrees Celsius +1- 1.0 degrees?
■
n
❑
n
Comment:
Influent Sampling
Yes
No
NA
NE
# Is composite sampling flow proportional?
■
n
n
n
Is sample collected above side streams?
■
n
n
n
Is proper volume collected?
■
n
ri
n
Is the tubing clean?
■
n
n
n
Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
n
■
n
n
Is sampling performed according to the permit?
■
n
n
n
Comment: Temp was 0.7 degrees C.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
■
n
n
n
Is sample collected below all treatment units?
■
n
n
Is proper volume collected?
■
n
n
n
Is the tubing clean?
®
❑
n
n
Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
■
n
n
Page # 8
Permit: NC0030317 Owner • Facility: Tar River Regional WWTP
Inspection Date: 11/08/2006 Inspection Type: Compliance Evaluation
Effluent Sampling
Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ■
Comment:
Upstream 1 Downstream Sam lP in9 Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? ■ rl n n
Comment:
Page # 9
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8 31 98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yrlmo/day Inspection Type Inspector Fac Type
1 II 2 151 31 NCG110030 111 12106/11/08 117 t$Irl 191g1 201
1-J
Remarks
21111 1111_1 111111.11 1111 1111 11111111 111.1 1111.1II I I I16
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA --------------------------- Reserved ----------------------
671 169 701 1 711 1 721 N I 73I I 174 751 I I 1 1 1 1 1 80
t_I—!
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time0ate
Permit Effective Date
POTW name and NPDES permit Number)
09:30 AM 06/11/08
03/04/25
Tar River Regional WWTP
Exit Time/Date
Permit Expiration Date
3031 Water Treatment Plant Rd
Rocky Mount NC 27802
01:30 PM 06/11/08
08/04/30
Name(s) of Onsite Representative(syTitles(syPhone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Paul 2 Blount,PO Box 11.80 Rocky Mount NC Contacted
278021180/Director/252-972-1232/2529721232 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Storm Water
Section D: Summary of Find in /Comments Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone RRO WQ//919-791-4200/ r rL�J /�%
` f I 64
r1 -
Signature of Mana ent Q A Re ewer Agency/Office/Phone and Fax lumbers Date
y
r
EPA Form 3560-3 (Rev 9.9 vious editions are obsolete.
Page # 1
NPDES yrlmolday Inspection Type
3I NCG110030 f11 12I 06/11/06 I17 181
CI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page # 2
Michael F. Easley
Governor
William G. Ross Jr., Secretary
Department of Environment and Natural Resources
Alan W. Klimek, P.E., Director
Division of Water Quality
April 25, 2003
Mr. Paul B.,
Blount, Director of Water Resources
City of Rocky Mount
One Government Plaza
Rocky Mount, NC 27802-1180
Subject: General Permit No. NCG110000
Tar River Regional Wastewater Treatment Facility
COC NCG 110030
Edgecombe County
Dear Mr. Blount:
In accordance with your application for discharge permit received on February 27. 2003), we are forwarding
herewith the subject certificate of coverage to discharge under the subject state - NPDES general permit. This permit is
issued pursuant to the requirements of North Carolina General Statute 143-215 .1 and the Memorandum of Agreement
between North Carolina and the US Environmental Protection agency dated December 6, 1983.
If any parts, measurement frequencies or sampling requirements contained in this permit are unacceptable to you,
You have the right to request an individual permit by submitting an individual permit application. Unless such demand is
iTiade, this certificate of coverage shall be final and binding.
Please take notice that this certificate of coverage is not transferable except after notice to the Division of Water
Quality. The Division of Water Quality may require modification or revocation and reissuance of the certificate of
coverage.
This permit does not affect the legal requirements to obtain other permits which may be required by the Division
of Water Quality or permits required by the Division of Land Resources, Coastal Area Management Act or any other
Federal or Local governmental permit that may be required.
If you have any questions concerning this permit, please contact Mack Wiggins at telephone number 919/733-
5083 ext. 542.
cc: Raleigh Regional Office
Central Files
Stormwater and General Permits Unit Files
Sincerely,
Alan W. Klimek, P.E.
NTry
-N DEl R
Customer Service
1 800 623-7748
Division of Water Quality 1617 Mail Service Center Raleigh, NC 27699-1617 (919) 733-7015
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
GENERAL PERMIT NO. NCG110000
CERTIFICATE OF COVERAGE No. NCG110030
STORMWATER DISCHARGES
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
In compliance with the provision of North Carolina General Statute 143-215.1, other lawful standards and
regulations promulgated and adopted by the North Carolina Environmental Management Commission, and the
Federal Water Pollution Control Act, as amended,
City of Rocky Mount
is hereby authorized to discharge stormwater from a facility located at
Tar River Regional Wastewater Treatment Facility
3031 Water Treatment Plant Road
east of Rocky Mount off 97
Edgecombe County
to receiving waters designated as Tar River, a class C-NSW water in the Tar -Pamlico River Basin
in accordance with the effluent limitations, monitoring requirements, and other conditions set forth in Parts 1, 11, Ill,
1V, V, and VI of Genera) Permit No. NCGI 10000 as attached.
This certificate of coverage shall become effective April 25, 2003
This Certificate of Coverage shall remain in effect for the duration of the General Permit.
A 6�A
Signed this day April 25, 2003 j:.,•/1,i� l
Alan W. Klimek, P.E., Director
Division of Water Quality
By Authority of the Environmental Management Commission
14
7
77
N
N,
za o
'15
t7
i- N"i f
—41
R'4
0)
-N E -OC130
it
4,
, J,
'6 J
- sue' rs�_-r+'}t -�--�, l�'-. ti is i" & =M t :- �� -
fp
alk
Cern
tT
�'Xs
GD
T-
raci
r 0—
12 4-
Itiary
7-2,
A ITI 4i,
VIC
4
C'il cq�
I' - —e"
t � — - '` � • r1''^_ � 1 - _ 1�'e{_ 1.' •mil , i !� '+ r
4, 1743)
j
91 w
Copyright (C) 1997, Maptech, Inc
ANDivision of Water Quality / Water Quality Section
NCDENR
National Pollutant Discharge Elimination System
NCG110000
/_�F/ ti /r
National Pollutant ischarge;Eilminatfon System application for coverage under General Permit
NCG110P00 /
ATEF3'DISCHARGES associated with activities classified as:
Treatment;Woiks i eating domestic sewage or any other sewage sludge or wastewater treatment
device or system, used in the storage, treatment, recycling, and reclamation of municipal or
domestic sewage, with a design flow of 1.0 million gallons per day or more, or required to have an
approved pretreatment program under Title 40 Code of Federal Regulations (CFR) Part 403,
including lands dedicated to the disposal of sewage sludge that is located within the confines of
the facility.
(Please print or type)
1) Mailing address of owner/operator:
Name
City of Rocky Mount
- Water Resources, Paul Blount, Directo
Street Address
O n e Government Plaza
City
Rocky Mount
State NC ZIP Code 2 7 8 0 2 -1 1 8 0
Telephone No.
252 972-1290
Fax: 252 972-1232
' Address to which all permit correspondence will be mailed
" 2) Location of facility producing discharge:
Facility Name
Tar River_ Regional Wastewater_ Treatment_ Facility
Facility Contact
G . Stanley Curtis
Street Address
3031 Water Treatment
Plant Road
City
Rocky Mount
State NC ZIPCode 27801
County
Edgecombe
- Telephone No.
252 972-1400
Fax: 252 972-1424�
:.-. 3) Physical Location Information:
Please provide a narrative description of how to get to the facility (use street names, state road numbers, and
distance and direction from a roadway intersection). Take Highway 97 East three (3) miles
east of Rocky Mount City limits, turn left on Water Treatment Plant Road
(A copy of a county map or USGS quad sheet with facility clearly located on the map is required to be submitted with this application)•
4) This NPDES Permit Application applies to which of the following:
❑ New or Proposed Facility Date operation is to begin
12 Existing
5) Standard Industrial Classification: 1*t + tt� i _ ill
Provide the 4 digit Standard Industrial Classification Code (SIC CQd�xt�iat describes tfie prirri�ryindustrial
activity at this facility
FES 2 7 2003
SIC Code: 9 9 9 9
Page 1 of 3 '�•
5WU-226-101701 _.
:G110000 N.O.I.
Provide a brief narrative description of the types of industrial activities and products manufactured at
thisfacility: Treatment of domestic, commerical, and industrial
wastewater from Rocky Mount, Nashville, Sharpsburg, and
Whitakers area.
7) Discharge points / Receiving waters:
How many discharge points (ditches, pipes, channels, etc.) convey stormwater from the property? 2
What is the name of the body or bodies of water (creek, stream, river, lake, etc.) that the facility stormwater
discharges end up in? Tar River
If the site stormwater discharges to a separate storm sewer system, name the operator of the separate storm
sewer system (e.g. City of Raleigh municipal storm sewer). N / A
8) Does this facility have any other NPDES permits?
❑ No
Yes
If yes, list the permit numbers for all current NPDES permits for this facility: N C 0 0 30 3 17
9) Does this facility have any Non -Discharge permits (ex: recycle permits)?
No
❑ Yes
If yes, list the permit numbers for all current Non -Discharge permits for this facility:
10) Does this facility employ any best management practices for stormwater control?
❑ No
A3 Yes
If yes, please briefly describe: Sedimentation and erosion control by means
of vegetation for n n- ved veledareas.-and--ae e
of stormwater detention ponds.
11) Does this facility have a Stormwater Pollution Prevention Plan?
❑ No
® Xtes
If yes, when was it implemented? _. Currently in final stages of development
12) Are vehicle maintenance activities occurring at this facility?
(N)NO ❑ Yes
13) Hazardous Waste:
a) Is this facility a Hazardous Waste Treatment, Storage, or Disposal Facility?
1LLkNo ❑ Yes
b) Is this facility a Small Quantity Generator (less than 1000 kg. of hazardous waste generated per month) of
hazardous waste?
❑ No ii Yes
c) Is this facility a Large Quantity Generator (1000 kg, or more of hazardous waste generated per month) of
hazardous waste?
X Z1 No ❑ Yes
d) if you answered yes to questions b. or c., please provide the following information:
Page 2 of 3
SW U-226-101701 -
�G110000 N.O.I.
Types) of waste: Mercury Lab Pack Waste
How is material stored: Glass Vials in Vermiculite 20 gal, Fiber Drum
Where is material stored: Lab Storage Room
How many disposal shipments per year: 2
Name of transport / disposal vendor: Clean Harbors Environmental (Safety - K l e e n )
Vendor address: P. 0. Box 3442, Boston, MA 02241-3442
14) Certification:
North Carolina General Statute 143-215.6 b (1) provides that:
Any person who knowingly makes any false statement, representation, or certification in any application, record, report,
plan or other document filed or required to be maintained under Article 21 or regulations of the Environmental
Management Commission implementing that Article, or who falsifies, tampers with or knowingly renders inaccurate any
recording or monitoring device or method required to be operated or maintained under Article 21 or regulations of the
Environmental Management Commission implementing that Article, shall be guilty of a misdemeanor punishable by a
fine not to exceed $10,000, or by imprisonment not to exceed six months, or by both. (18 U.S.C. Section 1001 provides
a punishment by a fine of not more than $10,000 or imprisonment not more than 5 years, or both, for a similar offense.)
I hereby request coverage under the referenced General Permit. f understand that coverage under this permit
will constitute the permit requirements for the discharge(s) and is enforceable in the same manner as an
individual permit.
I certify that I am familiar with the information contained in this application and that to the best of my knowledge
and belief such information is true, complete, and accurate.
Printed Name Qf'F rson Signing: Pau B. Blount
Title: DirEc or, Waxer -Resou ,51es
of Applicant)
3
(Date Signed)
Notice of Intent must be accompanied by a check or money order for $80.00 made payable to:
NCDENR
Final Checklist
This application will be returned as incomplete unless all of the following items have been included:
❑ Check for $80 made payable to NCDENR
❑ This completed application and all supporting documents