HomeMy WebLinkAboutNCG030139_MONITORING INFO_20190514STORMWATER DIVISION CODING SHEET
NCG PERMITS
PERMIT NO.
Iv C& 030/39
DOC TYPE
❑ �HI ORICALFILE
kk MONITORING REPORTS
DOC DATE
❑ AD Iq OS�
YYYYMMDD
Semi-annual Stormwater Discharge Monitoring Report
for North Carolina Division of Water Quality General Permit No. NCG030000
Date submitted 05 07 2019
CERTIFICATE OF COVERAGE NO. NCG030139
FACILITY NAME Mueller -Systems
COUNTY Rowan
PERSON COLLECTING SAMPLES Chris Freeman
LABORATORY Meritech, Inc Lab Cert. # 165
Comments on sample collection or analysis:
Part A: Stormwater Benchmarks and Monitoring Results
SAMPLE COLLECTION YEAR 2019
SAMPLE PERIOD ❑ Jan -June ❑ July -Dec
or ® Monthly' April
DISCHARGING TO CLASS ❑ORW ❑HQW ❑Trout ❑PNA
RECEIVED ❑Zero -flow ❑Water Supply ❑SA
®Other Class C
MAY 14 2019
PLEASE REMEMBER TO SIGN ON PAGES 2 AND/OR 3 4
PWR ECFILES N
❑ No discharge this period?'
Outfall No.
Date Sample
Collei tedl
(mo/dd/Yr) .
24-hour rainfall
amount,
3
Inches '
Total Suspended Solids
pH,
Standard units
Copper
Lead
Zinc
Nan -Polar O' &G/
Total -Petroleum
Hydrocarbons
Total Toxic
Organics
Benchmarks ==->
_
-
100 mg/L or 50 mg/L°
6.0 — 9.0
0.007 mg/L
0.03 mg/L
0.067
mg/L
15 mg/L
1 mg/L
01
4/08/19
1.12
44
6.54
0.013
<0.010
0.034
<5
NA
02
4/08/19
1.12
15
6.48
0.036
<0.010
0.054
<5
NA
1 Monthly sampling (instead of semi-annual) must begin with the second consecutive benchmark exceedance for the same parameter at the same outfall.
Z For sampling periods with no discharge at any single outfall, you must still submit this discharge monitoring report with a checkmark here.
3The total precipitation must be recorded using data from an on -site rain gauge. Unattended sites may be eligible for a waiver of the rain gauge requirement.
"See General Permit, Table 3 identifying the especially sensitive receiving water classifications where the more protective benchmark applies.
5 Total Toxic Organics sampling is applicable only for those facilities which perform metal finishing operations, manufacture semiconductors, manufacture
electronic crystals, or manufacture cathode ray tubes. For purposes of this permit the definition of Total Toxic Organics is that definition contained in the EPA
Effluent Guidelines for the facility subject to the requirement to sample (for metal finishing use the definition as found in 40 CFR 433.11; for semiconductor
manufacture use the definition as found in 40 CFR 469.12; for electronic crystal manufacture use the definition as found in 40 CFR 469.22; and for cathode ray
tube manufacture use the definition found in 40 CFR 469.31),
Permit Date:11/1/2012-10/31/2017 5WU-245, last revised 10/25/2012
Page 1 of 3
Outfall No.
Date Sample
Collected'
(mo/dd/yr),.
24-hour rainfall
amount,
Inches3
Non -polar O&G/TPH by
EPA 1664 (5GT-HEM)
Total Suspended Solids.
pH.
Benchmarks
15 mg/L
100 mg/L or 50 mg/L*
6.0 — 9.0 SU
Facilities that incorporate a solvent management plan into the Stormwater Pollution Prevention Plan may so certify, and the requirement for TTO monitoring
may be waived. The solvent management plan shall include a list of the total toxic organic compounds used and the other elements listed in the General
Permit. For those facilities electing to employ the TTO monitoring waiver, the discharger shall sign the following certification statement:
"Based upon my inquiry of the person or persons directly responsible for managing compliance with the permit monitoring requirement for total toxic organics
(TTO), I certify that to the best of my knowledge and belief, no dumping of.concentrated toxic organics into the stormwater or areas which are exposed to rainfall or
stormwater runoff has occurred since filing the last discharge monitoring report. I further certify that this facility is implementing the all the provisions of the
solvent management plan included in the Stormwater Pollution Prevention Plan."
John Small
Name (Print name)
EHS Manager
Title (Print title)
(Si (ature) (Date)
Note: Results must be reported in numerical format. Do not report Below Detection Limit, BDL, <PQL, Non -detect, ND, or other similar non -numerical
format. When results are below the applicable limits, the) mu_s_t be reported in the format, "<XX mg/L", where XX is the numerical value of the detection
limit, reporting limit, etc. in mg/L.
Note: 'if you report a sample value in excess of the benchmark, you must implement Tier 1, Tier 2, or Tier 3 responses. See General Permit text.
Part B: Vehicle Maintenance Area, Monitoring Results: only for facilities averaging > 55 gal of new oil per month.
No discharge this period?z
Footnotes from Part A also apply to this Part B
* See General Permit text, Table 5, identifying the especially sensitive receiving water classifications where the more protective benchmark applies.
Permit Date: 11/1/2012-10/31/2017 SWU-245, last revised 10/25/2012
Page 2 of 3
• Nbte: if you report a sample value in excess of the benchmark, you must implement Tier 1, Tier 2, or Tier 3 responses. See General Permit text.
FOR PART A AND PART B MONITORING RESULTS:
• A BENCHMARK EXCEEDANCE TRIGGERS TIER 1 REQUIREMENTS. SEE PERMIT PART II SECTION B.
• 2 EXCEEDANCES IN A ROW FOR THE SAME PARAMETER AT THE SAME OUTFALL TRIGGER TIER 2 REQUIREMENTS. SEE PERMIT PART II SECTION B.
• TIER 3: HAS YOUR FACILITY HAD 4 OR MORE BENCHMARK EXCEEDENCES FOR THE SAME PARAMETER AT ANY ONE OUTFALL? YES ® NO ❑
IF YES, HAVE YOU CONTACTED THE DWQ REGIONAL OFFICE? YES ® NO
REGIONAL OFFICE CONTACT NAME: Zahid Kahn
Mail an on final and one copy pf this DMR including all "No Dischar e" re orts within 30 days of receipt of the lab results tor at end of monitorin eriod
in the case o "No Discharge" re orts to:
Division of Water Quality
Attn: DWQ Central Files
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
YOU MUST SIGN THIS CERTIFICATION FOR ANY INFORMATION REPORTED:
"I certify, under penalty of law, that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to
assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or
those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I
am aware that there are significant penalties for submitting false information, including the possibility of fines and imprisonment for knowing violations."
(Signature of
Permit Date: 31/1/2012-10/31/2017
J
(D e)
SWU-245, last revised 10/25/2012
Page 3 of 3
Mueller Systems
10210 Statesville Blvd, Cleveland NC 27013 f 704-278-5334 1 jsmall@muellersystems.com
5/07/2019
Division of Water Quality
Attn: DWQ Central Files
1617 Mail Service Center
Raleigh, NC 27699-1617
Dear Division of Water Quality:
Attached are our Stormwater monitoring results for the month of May. We have exceeded the
benchmark of 0.007 mg/L for copper at Outfall #1 with a result of 0.013 mg/L and Outfall #2 with a
result of 0.036 mg/L.
Sincerely,
jI-;'4
fah
John Small
EHS Manager