HomeMy WebLinkAboutNCG551416_NOV-2019-PC-0613 Response_20190913XV DePte'rtnvlr
ohnl egra l Qua li [Y
sip
Reg ...a! Oft"c
e
Septic System installation & Maintenance
1-888-817-1904
Ref: Bay Leaf Fire Dept. NOV2019-PC-0613 /XG 55 H/h
After the initial site visit with Cory Larsen. I scheduled a re -sampling of the
effluent.
To address the PH, I added 4 Ibs of baking soda. Latest lab data attached shows
PH at 5.7. 1 spoke to the treatment system manufacturer and to Cory Larsen. We
agreed on a plan to change recirculation rates and add additional baking soda
until PH is in compliance. I will re -sample in a few days.
To address the fecal, I pulled and UV sleeve to examine, it had been previously
cleaned in April, it did not appear dirty, but was cleaned. Also I changed to
protocol during sampling so as not to create velocity in the discharge piping.
Latest lab data shows fecal as ND. I believe the protocol was more responsible for
this change in lab results than the cleaning.
Cory J. Brantley
David Brantley and Sons INC
aceAnalytica(
www.pecekDscme
i
I
ANALYTICAL RESULTS
Project: Bay Leaf Fire Dept
Pace Project No.: 92443780
Pace Analytical Services, LLC
6701 Conference Drive
Raleigh, NC 27607
(919)834.4984
Sample: EFF Lab ID: 92443780001 Collected: 09/03/19 08:30 Received: 09/03/19 09,00 Matrix- Water
Parameters Results Units Report Limit DF Prepared Analyzed CAS No. Clual
4500H+ pH, Electrometric EDN Analytical Method: SM 4500-H+B-2011
PH at 25 Degrees C 5.7 Std. Units 1.0 1 09/04/19 16:10 H3
Colllert-18 Fecal Coliform RAL Analytical Method: Colliert-18 Preparation Method: Colilert-18
Fecal Coliforms ND MPN1100mL 1.0 1 09/03/19 15:54 091041 19 12:44
Date: 09/06/2019 12:46 PM
XC Dept of Environmental Quality
SEP 13 2019
Meigh Regional Off;icc
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.