HomeMy WebLinkAboutNC0021369_NOV-2019-LV-0621 Response_20190830MEMORANDUM
To: Timothy J. Barth
From: Chris Cochran, ORC C�
Re: NOV-2019-LV-0621
Exceedance of Weekly Geometric Mean Limit
Date: August 30, 2019
The weekly Geometric Mean exceeded its limit because of a failed circulation pump. A storm in the
night had hit and turned off a RAS pump. The plant lost solids into the contact chamber. A coupling in
the pump pick up line was weak and dropped the foot valve into the lower part of the contact chamber
where the solids had settled. When the foot valve dropped into the solids, the solids were pulled into
the pump. The pump was taken apart, cleaned and rebuilt and the line was replaced once we found the
problem. I was using chlorine tablets while the pup was down. Further progress has been made in
regards to changing to bleach, but it is not yet in place at this time.
If you have any questions or concerns, please do not hesitate to contact me.