Loading...
HomeMy WebLinkAboutNC0021369_NOV-2019-LV-0621 Response_20190830MEMORANDUM To: Timothy J. Barth From: Chris Cochran, ORC C� Re: NOV-2019-LV-0621 Exceedance of Weekly Geometric Mean Limit Date: August 30, 2019 The weekly Geometric Mean exceeded its limit because of a failed circulation pump. A storm in the night had hit and turned off a RAS pump. The plant lost solids into the contact chamber. A coupling in the pump pick up line was weak and dropped the foot valve into the lower part of the contact chamber where the solids had settled. When the foot valve dropped into the solids, the solids were pulled into the pump. The pump was taken apart, cleaned and rebuilt and the line was replaced once we found the problem. I was using chlorine tablets while the pup was down. Further progress has been made in regards to changing to bleach, but it is not yet in place at this time. If you have any questions or concerns, please do not hesitate to contact me.