HomeMy WebLinkAboutNC0083313_Inspection_20190827EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0083313 19/08/14 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Brookside Village Condos WWTP
59 Brookside Dr
Hendersonville NC 28792
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:50AM 19/08/14 16/04/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Shannon D James/ORC/828-697-0063/
Other Facility Data
11:30AM 19/08/14 20/11/30
Name, Address of Responsible Official/Title/Phone and Fax Number
Valerie L Smith,538 N Main St Hendersonvlle NC 28792/Treasurer/828-696-2173/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance Sludge Handling Disposal Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Daniel J Boss ARO WQ//828-296-4658/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 652749ED-C14C-4087-99CE-DC431E9917E3
8/27/2019
8/27/2019
NPDES yr/mo/day
19/08/14
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 8/14/2019 I (Daniel Boss) met with Juanita James and Shannon James (ORC) for a compliance
evaluation inspection of the Brookside Village Condos WWTP. The plant appeared to be operating well
overall.
Only one of the two tertiary filter pumps is working. The one pump is enough to operate the filter but
the other pump needs to be repaired.
The right of way to the effluent pipe needs to be cleared.
NC0083313 17
Page#2
DocuSign Envelope ID: 652749ED-C14C-4087-99CE-DC431E9917E3
Permit:NC0083313
Inspection Date:08/14/2019
Owner - Facility:
Inspection Type:
Brookside Village Condos WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Page#3
DocuSign Envelope ID: 652749ED-C14C-4087-99CE-DC431E9917E3
Permit:NC0083313
Inspection Date:08/14/2019
Owner - Facility:
Inspection Type:
Brookside Village Condos WWTP
Compliance Evaluation
Aeration Basins Yes No NA NE
Is the DO level acceptable?(1.0 to 3.0 mg/l)
DO- 4.6 mg/L; pH- 7.0; Settleable solids- 53% in 30minComment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Sludge blanket was not measured, but clear water could be seen several feet into the
clarifier. According to the ORC, the excess floating sludge results from the equalization
basin running when the plant is not on (blowers not running).
Comment:
Filtration (High Rate Tertiary)Yes No NA NE
Type of operation:Down flow
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Only one pump works for this filter. Mrs. James said that there is no backwash function for
this filter and that the working pump only acts as a mudwell pump.
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?1
Page#4
DocuSign Envelope ID: 652749ED-C14C-4087-99CE-DC431E9917E3
Permit:NC0083313
Inspection Date:08/14/2019
Owner - Facility:
Inspection Type:
Brookside Village Condos WWTP
Compliance Evaluation
Disinfection-Tablet Yes No NA NE
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?1
Comment:
Pump Station - Effluent Yes No NA NE
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Page#5
DocuSign Envelope ID: 652749ED-C14C-4087-99CE-DC431E9917E3
Permit:NC0083313
Inspection Date:08/14/2019
Owner - Facility:
Inspection Type:
Brookside Village Condos WWTP
Compliance Evaluation
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
The effluent pipe was not seen during the inspection. The location is known but the right of
way was overgrown.
Comment:
Page#6