HomeMy WebLinkAboutWQCSD0614_Compliance Evaluation Inspection_20190823ROY COOPER Governor MICHAEL S. REGAN Seavfary LINDA CULPEPPER Vir'cc for Michael Parks 2548 Oaks Plantation Drive Raleigh, NC 27610 Dear Mr. Parks: a NORTH CARO INA Environmental Quality August 23, 2019 Subject: Compliance Evaluation Inspection Plaza Garibaldi Wastewater Collection System 315 Foushee Street, Durham Street 27704 Permit No. WQCSD0614 Mitch Hayes of the Division of Water Resources performed the subject inspection on August 23, 2019. There was no one on site to help with the inspection. The following observations were made during the inspection: 1. This is one duplex pump station serving a restaurant. 2. There is no emergency contact signage or other contact information in case of an overflow or emergency. 3. The pump station is not connected to telemetry or to SCADA. The pump station must be inspected every day. 4. The wet well was bolted down preventing inspection of the inside. There was no indication of any past overflows on the ground. If you have any questions about this letter or the inspection, please contact Mitch Hayes at 919.791.4261 or at mitch.hayes0ncdennuov . Sincerely, // r` �1 lick, L.G., Assistant Regional Supervisor Water Quality Regional Operations Section Raleigh Regional Office Division of Water Resources, NC DEQ cc: permit files North Carolina Department of Environmental Quality Division of Water Resources Raleigh Regional Office 3800 Barrett Drive 1628 Mad Ser ice Center Raleigh. North Carol na 27699 1628 01a 701 n')nn Compliance Inspection Report Permit: WOCSDO614 Effective: 03/28114 Expiration: SOC: Effective: Expiration: County: Durham Region: Raleigh Contact Person: Michael Parks Directions to Facility: System Classifications: Primary ORC: Secondary ORC(s); On -Site Representative(s): 24 hour contact name Related Permits: Title; Certification; Michael Parks Owner: Michael Parks Facility: 313 Foushee 313 Foushee St Durham NC 27704 Phone: Phone: Inspection Date: 08/23/2019 Entry Time: 10 45AM Exit Time: 11 00AM Primary inspector: Mitchell S Hayes tV; aGt! k_V -S, f-hjZ> (� 8' 1 3 . ZU 19 Phone: 919-791-4200 Secondary Inspector(sy // Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: Compliant Not Compliant Question Areas: Miscelfaneau5 Quest om 0 Pump Slat;Dns (See attachment summary) Page 1 of 4 Permit: WQCSD0614 owner - Facility: Michael Parks Inspection Date: 0812312019 Inspection Type . Collection System inspect Non Sampling Reason for Visit: Routine Inspection Summary No one was on site during the inspection. Wet well was secured with bolts. Pump station has no contact emergency s:gnage. There was no indication of past overflows. Page 2 of 4 Permit: WQCSD0614 Owner -Facility: Michael Parks Inspection Date: 0812312019 Inspection Type: Collection System Inspect Non Sampling Reason for Visit: Ilasitine Pump Stations Yes No NA NE Please list the Pump Stations Inspected Pump station behind restaurant. # Number of duplex or larger pump stations in system 1 # Number of vacuum stations in system 0 # Number of simplex pump stations in system 0 # Number of simplex pump stations in system serving more than one building o How many pumptvacuum stations have # A two-way "auto polling" communication system (SCADA) installed? 0 # A simple one-way telemelrylcommunication system (auto -dialer) mstalledl 0 For pump stations inspected Are they secure wilh restricted access? 0 Cl D ❑ Were they free of by-pass structuresipipes? 0❑ ❑ ❑ Were wet wells free of excessive grease/debris? 0 El 0 # Do they all have telemetry installed? Is the telemetry system functional? 0 Is a 24-hour notification sign posted ? Does the sign include. Owner Name? Pump slalkm identifier? . 0 El # Address? El 0 El 0 Instructions for notification? 11. 24-hour emergency contact numbers? Are audio and visual alarms present? N El 0 El Are audio and visual alarms operable? ■ # Is there a backup generator or bypass pump connected? If tested during inspection, did it function properly? El❑ E 11 Is the back-up system tested at least bi-annually under normal operating conditions? 11❑ N ❑ # Does it have a dedicated connect on for a portable generator? ❑ E ❑ El # Is the owner relying on portable units in the event of a power outage) ❑ ❑ # If Yes, is there a distribution plan? ❑ If Yes. what resources (Units/StaffNehicleslelc) are included in Plan? # Does Permittee have the approved percentage of replacement simplex pumps? 0 El 11 0 Is recordkeeping of pump station inspection and maintenance program adequate? ri Do pump station logs include at a minimum Inside and outside cleaning and debris removal? Page 3of4 permit; WOCSDO614 owner • Facility: Michael Parks Inspection Date: 0012312019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspecting and exercising all valves? Inspecting and lubricating pumps and other equipment? ❑❑❑■ ❑ ❑ ❑ Inspecting alarms. telemetry and auxiliary equipment? ❑ ❑ 110 Comment: No one was on site during the inspection. Wet well was secured with bolts. Pump station has no contact emergency signage. There was indication of past overflows. Page 4 of 4