HomeMy WebLinkAboutNC0037176_Inspection_20190814EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0037176 19/08/14 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Bon Worth WWTP
40 Francis Rd
Hendersonville NC 28791
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
02:45PM 19/08/14 16/01/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Kenneth Jason Rummel/ORC/828-697-0063/
Other Facility Data
03:10PM 19/08/14 20/11/30
Name, Address of Responsible Official/Title/Phone and Fax Number
Bill Hale,PO Box 2890 Hendersonville NC 28793//828-697-2216/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Daniel J Boss ARO WQ//828-296-4658/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 8E779735-64CB-4E47-90AF-A28CDE16FDF6
8/22/2019
8/22/2019
NPDES yr/mo/day
19/08/14
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 8/14/2019 I (Daniel Boss) conducted a compliance evaluation inspection of the Bon Worth WWTP.
I met with Jason Rummel (ORC) and Juanita James for the inspection. The plant appears to be
operating well and maintained in good condition.
This plant receives very little flow. There are screens over most of the basins to keep pine needles out
of the wastewater stream.
NC0037176 17
Page#2
DocuSign Envelope ID: 8E779735-64CB-4E47-90AF-A28CDE16FDF6
Permit:NC0037176
Inspection Date:08/14/2019
Owner - Facility:
Inspection Type:
Bon Worth WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
The permit describes the plant as having a bar screen which it does not. The facility has a
septic tank which is not listed in the permit.
Comment:
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Settleable solids are about 60%, the DO was 5.37 mg/L.Comment:
Page#3
DocuSign Envelope ID: 8E779735-64CB-4E47-90AF-A28CDE16FDF6
Permit:NC0037176
Inspection Date:08/14/2019
Owner - Facility:
Inspection Type:
Bon Worth WWTP
Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?1
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?1
Comment:
Page#4
DocuSign Envelope ID: 8E779735-64CB-4E47-90AF-A28CDE16FDF6
Permit:NC0037176
Inspection Date:08/14/2019
Owner - Facility:
Inspection Type:
Bon Worth WWTP
Compliance Evaluation
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Pump Station - Effluent Yes No NA NE
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
There is no alarm for the effluent pump station.Comment:
Page#5