HomeMy WebLinkAboutNC0025461_NOV and Intent to Assess CEI_20190807DocuSign Envelope ID: 1D52854B-4BC4-4556-924F-FA52A1A99A43
ROY COOPER
60�crr,or
MICHAEL S. REGAN
Seerwwy
LINDA CULPEPPER
C4Wtor
Certified Mail # 7019 0700 0000 8867 5787
Return Receipt Reauested
Charles Vines
Town of Bakersville
PO Box 53
Bakersville, NC 28705
NORTH CAROLINA
Environmental Qual"
August 07, 2019
SUBJECT: NOTICE OF VIOLATION & INTENT TO ASSESS CIVIL PENALTY
Tracking Number: NOV-2019-PC-0574
Permit No. NCO025461
Bakersville WWTP
Mitchell County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Bakersville WWTP on July 23,
2019. This inspection was conducted to verify that the facility is operating in compliance with the conditions and
limitations specified in NPDES WW Permit No. NC0025461. A summary of the findings and comments noted
during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Sampling inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following violations were noted during the inspection:
Inspection Area Description of Violation
Disinfection - UV Effluent was discharging excessive solids; TSS 1050 mg/l. Fecal Coliform was 14,000/100ml.
Operations & Maintenance Excessive solids were being discharged to the stream.
Disinfection - UV Effluent trough had solids buildup.
Sequencing Batch Reactors SBR appeared high in solids and was discharging excessive solids.
North Carol!naDepartrnentofEnwortmente;Qua:rty I DiuisionofWater Resources
Ashev.;e RegnrLa-0ff:ce 1 2090 U.S. 701-0glm-ay I Swannsroos, North Csro:ara 23773
DocuSign Envelope ID: 1D52854B-4BC4-4556-924F-FA52A1A99A43
A Notice of Violation/Intent to Issue Civil Penalty is being issued for the noted violation of North Carolina General
Statute (G.S.) 143-215.1 and the facility's NPDES WW Permit. Pursuant to G.S. 143-215.6A, a civil penalty of
not more than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or
fails to act in accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S.
143-215.1.
If you wish to provide additional information regarding the noted violation, request technical assistance, or discuss
overall compliance please respond in writing within ten (10) business days after receipt of this Notice. A review of
your response will be considered along with any additional information provided. You will then be notified of any
civil penalties that may be assessed regarding the violations. If no response is received in this Office
within the 10-day period, a civil penalty assessment may be prepared.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. If the violations are of a continuing nature, not related to operation and/or maintenance problems, and
you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by
Consent.
Reminder: Pursuant to Permit Condition 6 in Section E, the Permittee is required to verbally notify the Regional
Office as soon as possible, not to exceed 24 hours, from first knowledge of any non-compliance at
the facility including limit violations, bypasses of, or failure of a treatment unit. A written report may
be required within 5 days if directed by Division staff. Prior notice should be given for anticipated or
potential problems due to planned maintenance activities, taking units off-line, etc.
If you should have any questions, please do not hesitate to contact Linda Wiggs with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4500.
Sincerely,
DocuSigned by:
7E617A38285848C...
G. Landon Davidson, P.G., Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: ARO Server, LF
G:\WR\WQ\Mitchell\Wastewater\Municipal\25461 Bakersville\7-23-2019\20190807_NC0025461_NOVNOI2019PC0574.rtf
North%aro;!ra Departn,ertof Erv:rorrneuta.Qua:rty I Diusiauof Water Resources
Ashev,;e Ragnrtai4ff:ce l Z090 U.S. 7-DRglway I SwanRSROs, North Q%ro:m 23773
DocuSign Envelope ID: 2DEC1259-31D8-4166-9DC1-7B019D082E9D
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NCO025461 111 12 I 19/07/23 I17
18 Lam] 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I
I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA
---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I
u I�
73 I I 174 751 I I I I I I I80
I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
11:50AM 19/07/23
16/07/01
Bakersville WWTP
306 S Mitchell Ave
Exit Time/Date
Permit Expiration Date
Bakersville NC 28705
12:50PM 19/07/23
20/02/29
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Charles Vines,PO Box 53 Bakersville NC 28705//828-688-2113/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenance 0 Facility Site Review 0 Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers
Date
Linda S Wiggs ARO WQ//828-296-4500 Ext.4653/
EW
Signature of Manageme REAby. Agency/Office/Phone and Fax Numbers
Date
)
8/8/2019
7E617A38285848C...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 2DEC1259-31D8-4166-9DC1-7B019D082E9D
NPDES yr/mo/day Inspection Type
NCO025461 I11 121 19/07/23 117 18 I S
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Linda Wiggs visited the WWTP with Charles Vines and DWR Public Water staff.
Onsite for 1 hour, within that hour the plant was losing solids for 45 minutes.
Effluent samples results:
TSS — 1050 mg/I
Fecal Coliform — 14,000/100ml
Page#
DocuSign Envelope ID: 2DEC1259-31D8-4166-9DC1-7B019D082E9D
Permit: NCO025461 Owner - Facility: Bakersville WWTP
Inspection Date: 07/23/2019 Inspection Type: Compliance Sampling
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ 0 ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: SBR appeared high in solids and was discharging excessive solids.
Sequencing Batch Reactors
Yes No NA NE
Type of operation:
Is the reactor effluent free of solids?
❑
❑
❑
Does minimum fill time correspond to the peak hour flow rate of the facility?
❑
❑
❑
Is aeration and mixing cycled on and off during fill?
❑
❑
❑
The operator understands and can explain the process?
❑
❑
❑
Comment: SBR appeared high in solids and was discharging excessive solids. Grab TSS at effluent
was 1050 mg/I.
Disinfection - UV
Yes No NA NE
Are extra UV bulbs available on site?
❑
❑
❑
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
❑
❑
❑
Is transmittance at or above designed level?
❑
❑
❑
Is there a backup system on site?
❑
0
❑
❑
Is effluent clear and free of solids?
❑
0
❑
❑
Comment: Effluent was discharging excessive solids: TSS 1050 mg/I. Fecal Coliform was
14,000/100ml.
Page# 3