August 2, 2019
Subject: Compliance Evaluation Inspection Report
Shields MHP WWTP
NPDES Permit NCO055271
Alamance County
Dear Ms. Shields:
ReCEIVED/NCDEB/DW2
AUG 0 8 2019
Water Quality
perrrtlolpg Section
On June 26, 2019, Paul DiMatteo and Kelli Park of the Division of Water Resources (Division), Winston-
Salem Regional Office met with Mike Carson, Operator in Responsible Charge (ORC) to conduct a
Compliance Evaluation Inspection of the above referenced wastewater treatment plant.
This inspection consists of (1) a review of the permit and accompanying documentation to determine
compliance with permit conditions, and (2) an on -site inspection of several collection system components.
The attached inspection form notes the areas that were evaluated for the inspection, with any notable
findings outlined as follows:
1. Mr. Carson said that he calibrates his dissolved oxygen (DO) meter quarterly. Please note that NC
Certified Lab procedures for DO require the meter to be calibrated "prior to analysis of samples
each day compliance monitoring is performed." A copy of this procedure is enclosed.
2. Mr. Carson expressed safety concerns with the downstream sampling location at the bridge on NC
SR 1529 and suggested taking samples several hundred feet downstream instead. While the
Regional Office does not have an issue with this change, a formal request should be made to Central
Office.
If you have any questions concerning this report please contact Paul DiMatteo at (336) 776-9691 or Lon
Snider at (336) 776-9800.
Sincerely,
CDocuftned by
Lati T SMxv
n Loi'9n%fer, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Enclosures — Inspection Report, Procedure for the Analysis of DO
CC: WQS Winston-Salem Regional Office
NPDES Unit
Central Files
wP. r. ®� Q^ _ North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 West Hanes Mill Road, Suite 3001 Winston-Salem, North Carolina 27105
NTH CRCARC1INA ��
/'� 336.776.9800
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A National Data System Coding (i e , PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO055271 111 121 19/06/26 117 18 I C I 19 I G I 201
21111111111111111111111111111111111111111111 r6
I
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA , -Reserved
72 LNJ I73174 751 III I 1 80
71 it_]
67 70 L_j
Section B FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10 15AM 19/06/26
17/04/01
Shields Mobile Home Park
Exit Time/Date
Permit Expiration Date
1355 NC Hwy 87 N
1130AM 19/06/26
21/05/31
Elon College NC 27244
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
James M Carson/ORC/336-578-3264/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Jerry L Shields,1341 NC Hwy 87 N Elon NC 27244//336-584-6209/
No
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Operations & Maintenance Records/Reports Self -Monitoring Program
Sludge Handling Disposal 0 Facility Site Review Effluent/Receiving Waters Laboratory
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by
Paul DiMatteo /� WSRO WQ//336-776-9691/ $/2/2019
E�a.0 'D'; (a�d.e.
FtOC7C2E5BB34D4 .
Signature of Management Q A Revie DocuSigned by Agency/Office/Phone and Fax Numbers Date
Lov T S",dtr 8/2/2019
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete
Page#
NPDES yr/mo/day Inspection Type
31 NCO055271 I� 121 19/06/26 117 18 I c i
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO055271
Inspection Date. 06/26/2019
Owner -Facility: Shields Mobile Home Park
Inspection Type: Compliance Evaluation
Operations $ Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? E ❑ ❑ ❑
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable ❑ ❑ N ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment The previous inspection noted some cracked or broken septic tank lids. Many of these have
been repaired.
Permit
Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
E
❑
❑
❑
# Are there any special conditions for the permit?
❑
E
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment The permit became effective April 1, 2017 and expires May 31, 2021.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
N
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab reg required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
0
❑
on each shift?
Is the ORC visitation log available and current?
E
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
N
❑
❑
❑
Page#
3
Permit: NC0055271 Owner - Facility: Shields Mobile Home Park
Inspection Date: 06/26/2019 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review?
Comment:
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment:
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Comment.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV Intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
❑ ❑ E ❑
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
❑. ❑ ■ ❑
Yes No NA NE
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
E ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Durino the insDection the UV system appeared to be offline. Mr. Carson said It was workln
fine last time he checked It. He worked on the Issue after the inspection and later reported
that he thought a bug nesting in the electrical outlet caused It to stop working. He replaced
the outlet and the system ran again.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? N ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? N ❑ ❑ ❑
Page# 4
Permit: NCO055271
Inspection Date- 06126/2019
Effluent Pipe
If effluent (diffuser pipes are required) are they operating properly?
Owner -Facility: Shields Mobile Home Park
Inspection Type: Compliance Evaluation
Comment: There is a step aerator at the effluent and It appeared to be In good condition.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment
Yes No NA NE
❑ ❑ ■ ❑
Yes No NA NE
❑ ❑ E ❑
■ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ N ❑
❑ ❑ ❑ ■
❑ ❑ ❑
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and ❑ ❑ ❑
sampling location)?
Comment Mr. Carson mentioned that he wanted to change the downstream sampling point due to
several hundred feet below the outfall rather than at the bridge on NC SR 1529 due to safety
concerns. -A request should be made to the permit writers.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
E
❑
❑
❑
# Is the facility using a contract lab?
N
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
❑
❑
❑
Celsius)?
Incubator (Fecal Conform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
❑
Incubator (BOD) set to 20 0 degrees Celsius +/- 1 0 degrees?
❑
❑
❑
0
Comment ORC said he calibrates his DO meter quarterly Note that certified field lab
procedures
Indicate that DO meters used for compliance monitoring should be calibrated each day
It Is
used for that purpose
Page# 5
NORTH CAROLINA WASTEWATER/GROUNDWATER LABORATORY CERTIFICATION APPROVED
PROCEDURE FOR THE ANALYSIS OF DISSOLVED OXYGEN (DO)
This document provides an approved procedure for the analysis of DO for compliance monitoring per 15A
NCAC 2H 0805 (a) (7) and (g) (4)
HOLDING TIME:
• Samples must be analyzed within 15 minutes of collection (40 CFR Part 136 Table II); however, in situ or
immediate analysis is recommended due to the unstable nature of dissolved oxygen in samples
GENERAL INFORMATION:
• Types of probes
a Dissolved Oxygen Membrane Electrode
b Luminescence Dissolved Oxygen (LDO) Sensor
• Movement of water across the membrane (for membrane electrode technologies) is important for
accurate readings Some probes come with stirrers for this purpose Measurements should be taken
while the stirrer is in use or by swirling the DO probe in the sample flow Preferably, insert the probe into
flowing conditions If analyzed in a container, stir gently with the probe or add a stir bar Do not put the
probe on the sides or the bottom of the container
• Follow the manufacturer's instructions for probe storage
• Sample duplicates are not a required quality control element for Field parameters
METER CALIBRATION:
• Instruments are to be calibrated according to the manufacturer's calibration procedure prior to analysis of
samples each day compliance monitoring is performed
• The laboratory must use moist air for the air calibration This is accomplished by calibrating the electrode
in an environment with a high relative humidity Using dry air for the calibration can result in errant
readings
• The laboratory must document each time that a calibration is performed Calibration documentation must
include the following, where applicable to the instrument used and the type of calibration performed.
elevation, temperature, barometric pressure (in mmHg), salinity. After calibration, record the final DO
reading in mg/L, the slope or % efficiency
• For LDO sensors that cannot be calibrated, the calibration must be verified each day of use. This can be
performed by back calculating the theoretical DO for the current air calibration conditions (e g ,
temperature, elevation, barometric pressure, etc) The calculated DO value must verify the meter
reading within ±0 5 mg/L Refer to the Dissolved Oxygen Meter Calibration Venfication handout at the
end of this document If the meter verification does not read within ±0 5 mg/L of the theoretical DO,
corrective action must be taken
• When performing analyses at multiple sample sites, a post -analysis calibration verification must be
performed at the end of the run, regardless of meter type It is recommended that a mid -day calibration
verification be performed when samples are analyzed over an extended period of time The calculated
DO value must verify the meter reading within ±0 5 mg/L If the meter verification does not read within
±0 5 mg/L of the theoretical DO, corrective action must be taken Alternatively, if the meter is calibrated at
each sample site prior to analysis, a post -analysis calibration verification is not required
DOCUMENTATION:
The following must be documented in indelible ink whenever sample analysis is performed
1 Date and time of sample collection
Rev 12/05/2017
2. Date and time of sample analysis to verify the 15-minute holding time is met Alternatively, one time
may be documented for collection and analysis with the notation that samples are measured in situ
or immediately at the sample site
3 Facility name, sample site (ID or location), and permit number
4 Collector's/analyst's name or initials
5 Calibration variables (elevation, temperature, barometric pressure [in mmHg], salinity)
6 Meter calibration and/or verification time(s)
7 Final calibration information (final DO reading in mg/L, the slope or % efficiency)
8 Theoretical value and value obtained for the calibration verification(s), where applicable
9 Units of measure
10 Instrument identification (serial number preferred)
11 Parameter analyzed
12 Method reference
13. Data qualifier(s), when applicable
14 Equipment maintenance (recommended)
Refer to http.//deg.nc.gov/about/divisions/water-resources/water-resources-data/water-sciences-home-
page/laboratory-certification-branch/technical-assistance-policies) for additional quality assurance and quality
control requirements
Ref- Standard Methods 4500-0 G - 2011
Hach Method 10360, Rev 12, October 2011
In Situ Method 1002-8-2009
ASTM Method D888-09 (B)
ASTM Method D888-09 (C)
Rev 12/05/2017
Dissolved Oxygen Meter Calibration Verification r,
DO meters/probes must be calibrated each day of use prior to sample analysis. If the meter cannot be calibrated, the calibration must be verified each day of use.
Additionally, when performing DO analyses at multiple sample sites, a post analysis calibration verification must be analyzed at the end of the run for all types of DO
probes, unless the meter is recalibrated at each sample site Below is a procedure for verifying the calibration of a DO probe
1) Follow the manufacturer's instructions for meter operation -
2) Place probe in a plastic bag, the probe storage cup, the storage well of the meter(each containing a wet sponge), or a BOD bottle partially filled with water.Allow
appropriate instrument warm up time.
- 3) Read DO and temperature.
4) Check the reading vs the solubility table below and apply appropriate atmospheric(barometric) pressure or altitude correction factor
5) Calculated DO value must verify meter reading within ±0.5 mg/L (do NOT calculate and apply a correction factor to calculated DO)
Temp. °C DO mg/L Temp °C DO mg/L Atmospheric Pressure mm Hg Equivalent Altitude Ft. Correction Factor
- � 4'"".;�.+ ,. - ,W'4' x'"yr'y�,^ -_ - �__ , - „`d'" ;iy^.»s�,.`^d,='"%�c'r°+°+5c`a',�"�:� �.�'�=Y,'�v'_a _`"�'<-%>c - ___ �Y'i�-'�'f".��F.' S. "<"L.F.�I'..� '.5t
. .". .0;, .. � ��°��13.�1�1;� � ,�� �Tr��'.,... �1�9r75 -,•,r,�,�#��;v.�,A�9.h1_�a�.�,�,,.,"_; "a��,.� �76Q:., -_����..���,n,�. x,.����'� .-� , �.
yi��a�, �u•,"""'r.`;.� 4ll,','� nt,�dv��',',IL'�'o .�;,�*,",W�.,�%u, a;s� „��,
"t(i�q-,"G"„tF'”',74�" _ ,rp„o-' a,�2e .#�� 3 !*ri D'+'„"s -4 anA,c,"� , :e; 'a "�3 "
4 5 ;%% 12 94 20.0 9 09 ,. ,.�-�. � .- 7 _,��r�_ - ._",�, r� ,�,_��.��� �s���278 ��. :�„� �. ��� ,"..9� �
ii�g,{.,','V,`'. - h{.'`!�'.4,e ., « >v'a^y!''.,,,w to:T'^� 'rz ( "F, .";ti',y "rvr^k'IPAr.,'.
50:F;� °�' '.�"12"T���;�_�:"����= ...';:�', �'2�055 '��,'"���:Px���,9?i�0.;;��", 745 558 .98
5 5 12 61 21 0 8 92 737 841 97
All
S� •.-`,;;fi ,m";r,Ei;rc•-2", u�'"''"k�'� I�'i'"•;, .� ,.`z3-"3�n° �+r..'_^�• % k"';.'�•,"�;,e"s,", �"`�`� S `"'��s ar`�'u` :{I�,,7 (dN �. r �I�r� 5g+ 3f�
.'6.b';.?',,.`7: F.,12;45' ;;..; T r =„ 21 5 w; µ'"a r1'w' 8 83., :�^" ` '�730��`�,u. n g'� '� �'I'1a26 -. " 96�.: :„M
6.5 12.30 22 0 8 74 'Y ' ;i,i�a,�:"ki,i .,�,;"= str;; a ,` or'�`: °° >n 1!41.3 � <I _, ' 96 [.
i 'ay,•,, ` •�G2yy4";:. '�?,�?;�at u�w�.s€�`.�, '� nnaF__. :� ,:�.nt:94:4I '^r�, y .�
S", s ue,^ d.,r' -,w,,.� a ,,,?;,yd.;R,K..: &' }:, f�6�fi„C.'' g33s�'“:,
-et,!,:"a7�e0;a?�,r,,�x,%�,,,��k��12 'i'4�:�t�;;�' �.-9'�;��� 22�5";. ."''�a� ��v �b�,8�66 .�i�,","f" 714 1703 .94
7 5 11 99 23.0 8 58 - 707 1995 .93
---'- -�°.i':,:'.,, rc": - a'°u`„� �`�"",�r',ai"rI�N� a'° �„��p�, y �"y,�^�':� �� - ; ""P``k;����t'Ae�r ',"��:,;�'r,t mi,& _ � &n,,o ,,� ,W�� gY ,', ,• '� :&".
�8'.'0.jb. ' �'1�1..84:t " ;';U.� 2'3�,= .„x ,. :`8.50 ,.`�� ��m=.����'��.x:,6�9,._. :�:�,.m.�.�,.1w, �.,�,� � 229`° ,�� 92:
- reDw"?;ry �:w'�a�;�, ",� ,.,,,re:.-_„-..x�gs *,gut s $a�{�`" �,.. es-._....
8.5 11 70 24 0 8 42 '; .f i"�1,i.,692 �4 i ^. � n fira 587.. .E ., $ fi* m, 91 ,a ,
-"<.;-9:Q i9" 4 14 56i fl :-. a.,7 24:5+ It_'':13 34, F_q,iis 684 2887 90
9 5 11 42 25.0 8 26 676 3190 89
"�.�f" '�r'� ,� �.��.'tm•',x- d ,;.r e'�"w, -, '�W• � <,k`,�°`_. •�Y„�,a",u ,��,_r,�."�._,_ va
-•"rf„'o?o���. '"a~�9sOa .a t :,1616 . : . 84 8x. �, .� a, 1669 i k Ig _ g6 , Y., `a- i8
•,;� ,ham ,�"�,� ��` �_ i�i � ,"_
10,5 11 16 26 0 811 *VT'.y ,�{� .,r 66,9 .;_.r a". 4l�,�"+ -: A �x:�_3804 ' ' ,8,7 ; v
'�, w§e4G.ua.; �«5+"; � xk na'Y�rt, „� ��dR �� .-.,,, �' iiG-,
_ >.;1ri1l:0: ',44 4,a1C1f031.�:i:� i ��26i15 ,. n ")' 8.;04 , :U,n r; 654 4115 .86
11 5 10 90 27.0 7.97 646 4430 85
%s,, •6 s;r-'=e ^�..� �;.,� � h � 'a':K .<E,s. �:; �' •e tttr.� '�•' .*•E-�'�mr.s" -_ �... �� �µ� ,1 .Sx 4 m .f �
'I2F,Q ^,:44."a �1.0 8 ``'� s 27 5 7190. �y 638 - ..., ,ak, V .77 , �� p
a'°w;a" +rd ._, � a n&. b a���� ie°i��ri,r�'^t � i"w., � i4 .Afi4� a +a44 uvtaar � .�84�` ,,.,
12.5 10,66 28 0 7 83 ". _ : '" , 63�,h.� "'h= `x; M°LI ,a .,,_= __T::5C16T '_ 4 .83
sP �✓" �rt ,rk� a- i,ww
Tr;";1,3'f3 m�`, t'! 1=0.54 :=-A,1 `4 2$'Y6. Wit' 7 76 in 623 5391 82
135 1042 290 7.69 616 5717 .81
.�a41,a5 N, ]F-lUl l ,ecpg" � � s w5.V,, 7 4s2*e it .04 ft" 1' _-""+"-t"s o$0:"r• at a� =k',M*� g' , _te G oa7 �a`� ,!"x
� :��.8a
14 5 10 20 30.0 7.56 E g,l ;,,",?' ?600 ,, - ^,. ,, , 5m6tn.,o3$ ��, ttr ��=. t- i9" ,a
-
; ; ift'll ji ,4fiR1,10ti :; t it 1 5.0 ` 593 6717 78
15.5 9 98 31 0 7.43
:,,,,KI., ,' s f` "wt. - _1-�,g s z, e ig6 -- . `"��7�37;,t5/n:; Ref YSI Model 5000/5100 DO Meter Manual Slight variations in DO,pressure,and/or altitude may be found in other manuals
�6;0 ="<9:8r7 .._�" 3�E �� .��..a-.
16 5 9.77 32 0 7 31 Example If ambient temperature is 21°C and elevation is approximately 1126 ft, the theoretical DO
441117403 .,,•9f67` ,,,. ' 0-3.2 5, 7424 would be.
175 957 330 718
TIM 11' ' , ..338 1 ,t 712, �' 8.92 X 0.96 = 8 56 mg/L
18 5 9 38 34.0 7 07
c `"1;9 b1S 'Itiet 49 28 3:415 _ -la a or, If ambient temperature is 21°C and the atmospheric(barometric) pressure is 745 mm Hg, the
r 5 sfit 0`' i gw theoretical DO would be
8.92 X 0.98 = 8.74 mg/L