HomeMy WebLinkAboutNC0060755_NOV-2019-LV-0483 Response_20190715AI
WaterCarolina
d"Lvof North Carolina"
July 15, 2019
MR. W. Cory Basinger, Regional Supervisor
Water Quality Regional Operations. Section
Division of Water Resources
610 East Center Avenue, Suite 310
Mooresville, NC 28115
Ref: Saddlewood WWTP
NPDES Permit - NCO060755
Tracking# NOV — 2019 - LV - 0483
Dear Mr. Basinger,
We are in receipt of the above -mentioned Notice of Violation and respond as follows.
The BOD sample collected on May 15t" with a result of 9.7mgl exceeded the daily permit limit of
7.5mgl. We exceeded one daily limit but were in full compliance for the month.
After evaluation of the WWTP it was determined that blower number two had a bad check
valve and was allowing solids to backflow back into the clarifier. The check valve has been
replaced and everything is back to normal. All other daily and monthly samples collected
comply with the NPDES permit.
If you have any questions or if I can provide any additional information, please do not hesitate
to contact me at 704-621-9204.
Sincerely,
Charles E. Wood Jr.
e 4944 Parkway Plaza Blvd. Ste 375 ® Charlotte, North Carolina 28217 9 800-525-7990
Cc; Tony Konsul