HomeMy WebLinkAboutNC0060755_NOV-2019-LV-0483 Response_20190715AI WaterCarolina d"Lvof North Carolina" July 15, 2019 MR. W. Cory Basinger, Regional Supervisor Water Quality Regional Operations. Section Division of Water Resources 610 East Center Avenue, Suite 310 Mooresville, NC 28115 Ref: Saddlewood WWTP NPDES Permit - NCO060755 Tracking# NOV — 2019 - LV - 0483 Dear Mr. Basinger, We are in receipt of the above -mentioned Notice of Violation and respond as follows. The BOD sample collected on May 15t" with a result of 9.7mgl exceeded the daily permit limit of 7.5mgl. We exceeded one daily limit but were in full compliance for the month. After evaluation of the WWTP it was determined that blower number two had a bad check valve and was allowing solids to backflow back into the clarifier. The check valve has been replaced and everything is back to normal. All other daily and monthly samples collected comply with the NPDES permit. If you have any questions or if I can provide any additional information, please do not hesitate to contact me at 704-621-9204. Sincerely, Charles E. Wood Jr. e 4944 Parkway Plaza Blvd. Ste 375 ® Charlotte, North Carolina 28217 9 800-525-7990 Cc; Tony Konsul