HomeMy WebLinkAboutWQ0038465_Permit (Issuance)_20160520PAT MCCRORY Governor DONALD R. VAN DER VAART Secmary S. JAY ZIMMERMAN Director Water Resources ENVIRONMENTAL QUALITY May 20, 2016 Mr. Terry Houk City of High Point P.O. Box 230 High Point, NC 27261 Subject: Permit No. WQ0038465 City of High Point Gravity Sewer to Abandon the Old Thomasville Road Pump Station Wastewater Collection System Extension Permit Randolph County Dear Mr. Houk: In accordance with your application received May 13, 2016, we are forwarding herewith Permit No. WQ0038465 dated May 20, 2016, to the City of High Point (Permittee) for the construction and operation upon certification of the subject wastewater collection system extension. This permit shall be effective from the date of issuance until rescinded and shall be subject to the conditions and limitations as specified therein. This cover letter shall be considered a part of this permit and is therefore incorporated therein by reference. Please pay particular attention to the following conditions contained within this permit: Condition I.1: This permit shall not be automatically transferable; a request must be made and approved. Condition IA: Requires that the wastewater collection facilities be properly operated and maintained in accordance with 15A NCAC 2T .0403 or any individual system- wide collection system permit issued to the Permittee. It shall be responsibility of the Permittee -to ensure that the as -constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing board. 450 West Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 Phone: 336-776-9800 \ Internet: www.ncwaterguality.org State of North Carolina I Environmental Quality I Water Resources City of High Point Permit No. WQ0038465 If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and binding. If you need additional information concerning this matter, please contact Mike Mickey at (336) 776-9697 or via e-mail at mike.mickey@ncdenr.gov. Sincerely, for S. Jay Zimmerman, P.G. Director, Division of Water Resources by Sherri V. Knight, PE, Regional Supervisor Water Quality Regional Operations Section Winston-Salem Regional Office Division of Water Resources, NCDEQ cc: Randy McNeill, PE (Davis, Martin, Powell & Associates, 6415 Old Plank Rd, High Point, NC 27265) Winston-Salem Regional Office Files Water Resources Central Files PERCS (electronic copy) Page 2 of 9 STATE OF NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENTAL QUALITY WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to the City of High Point Randolph County for the construction and operation of approximately 2,524 linear feet of 8-inch gravity sewer that will allow the abandonment of an existing pump station as part of the Gravity Sewer to Abandon the Old Thomasville Road Pump Station project, and the discharge of "0" gallons per day of newly collected wastewater into the City of High Points existing sewerage system, pursuant to the application received May 13, 2016, and in conformity with 15A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February 12,1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting data subsequently filed and approved by the Department of Environmental Quality and considered a part of this permit. This permit shall be effective from the date of issuance until rescinded and shall be subject to the specified conditions and limitations contained therein. 19 _AU,WL�-- for S. Jay Zimmerman, P.G Director, Division of Water Resources By Authority of The Environmental Management Commission Permit Number. WQ0038465 Permit Issued: May 20, 2016 Page 3 of 9 SUPPLEMENT TO PERMIT COVER SHEET City of High Point is hereby authorized to: Construct, and then operate qpon certification the aforementioned wastewater collection extension. The sewage and wastewater collected by this system shall be treated in the Westside High Point Wastewater Treatment Facility in accordance with Permit Number NC0024228. Permitting of this project does not constitute an acceptance of any part of the project that does not meet 15A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February 12,1996 as applicable; and the Divisions Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned herein. Division approval is based on acceptance of the certification provided by a North Carolina -licensed Professional Engineer in the application. It shall be the Permiee s responsibility to ensure that the as -constructed project meets the appropriate design criteria and rules. Construction and operation is contingent upon compliance with the Standard Conditions identified below. I. STANDARD CONDITIONS 1. This permit shall not be transferable. In the event there is a desire for the wastewater collection facilities to change ownership, or there is a name change of the Permiee, a formal permit request shall be submitted to the Division accompanied by documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request shall be considered on its merits and may or may not be approved. [15A NCAC 02T.0104; G.S 143-215.1(d3)] 2. This permit shall become voidable unless the wastewater collection facilities are constructed in accordance with the conditions of this permit; 15A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Divisions Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials unless specifically mentioned herein. [15A NCAC 02T.01101 3. This permit shall be effective only with respect to the nature and volume of wastes described in the application and other supporting data. [15A NCAC 02T .0110] Page 4 of 9 4. The wastewater collection facilities shall be properly maintained and operated at all times. The Permittee shall maintain compliance with an individual system -wide collection system permit for the operation and maintenance of these facilities as required by 15A NCAC 2T .0403. If an individual permit is not required, the following performance criteria shall be met: [15A NCAC 02T .0108(b)]: a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters, and to prevent any contravention of groundwater standards or surface water standards. b. A map of the sewer system shall be developed and shall be actively maintained. c. An operation and maintenance plan including pump station inspection frequency, preventative maintenance schedule, spare parts inventory and overflow response has been developed and implemented. d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e. 365 days per year). Pump stations that are connected to a telemetry system shall be inspected at least once per week. e. High -priority sewer lines shall be inspected at least once per every six -months and inspections are documented. f. A general observation of the entire sewer system shall be conducted at least once per year. g. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina General Statute §143-215.1C. h. A Grease Control Program is in place as follows: For public owned collection systems, the Grease Control Program shall include at least biannual distribution of educational materials for both commercial and residential users and the legal means to require grease interceptors at existing establishments. The plan shall also include legal means for inspections of the grease interceptors, enforcement for violators and the legal means to control grease entering the system from other public and private satellite sewer systems. 2. For privately owned collection systems, the Grease Control Program shall include at least bi-annual distribution of grease education materials to users of the collection system by the permittee or its representative. 3. Grease education materials shall be distributed more often than required in Parts (1) and (2) of this Subparagraph if necessary to prevent grease -related sanitary sewer overflows. Page 5 of 9 i. Right-of-ways and easements shall be maintained in the full easement width for personnel and equipment accessibility. j. Documentation shall be kept for Subparagraphs (a) through (i) of this Rule for a minimum of three years with exception of the map, which shall be maintained for the life of the system. 5. The Permittee shall report by telephone to a water resources staff member at the Winston- Salem Regional Office, telephone number (336) 776-9800, as soon as possible, but in no case more than 24 hours, following the occurrence or first knowledge of the occurrence of either of the following: a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or breakage, etc.; or b. Any SSO and/or spill over 1,000 gallons; or c. Any SSO and/or spill, regardless of volume, that reaches surface water Voice mail messages or faxed information is permissible, but this shall not be considered as the initial verbal report. Overflows and spills occurring outside normal business hours may also be reported to the Division of Emergency Management at telephone number (800) 858- 0368 or (919) 733-3300. Persons reporting any of the above occurrences shall file a spill report by completing and submitting Part I of Form CS-SSO (or the most current Division approved form) within five days following first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to ensure that the problem does not recur. Part H of Form CS-SSO (or the most current Division approved form) can also be completed to show that the SSO was beyond control. [G.S.143-215.1C(al)] 6. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of the State. [15A NCAC 02T.0108(b)] 7. Upon completion of construction and prior to operation of these permitted facilities, the completed Engineering Certification form attached to this permit shall be submitted with the required supporting documents to the address provided on the form. A complete certification is one where the form is fully executed and the supporting documents are provided as applicable. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. A complete certification is one where the form is fully executed and the supporting documents are provided as applicable. Supporting documentation shall include the following: Page 6 of 9 a. One copy of the project construction record drawings (plan & profile views of sewer lines &_force mains) of the wastewater collection system extension. Final record drawings should be clear on the plans or on digital media (CD or DVD disk) and are defined as the design drawings that are marked up or annotated with after construction information and show required buffers, separation distances, material changes, etc. b. One copy of the supporting applicable design calculations including pipe and pump sizing, velocity, pump cycle times, and level control settings, pump station buoyancy, wet well storage, surge protection, detention time in the wet well, and force main, ability to flush low points in force mains with a pump cycle, and downstream sewer capacity analysis. If a portable power source or pump is dedicated to multiple stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, include travel timeframes, shall be provided. c. Changes to the project that do not result in non-compliance with this permit, regulations; or the Minimum Design Criteria should be clearly identified on the record drawings, on the certification in the space provided, or in written summary form. Prior to Certification (Final or Partial): Permit modifications are required for any changes resulting in non-compliance with this permit (including pipe length increases of 10% or greater, increased flow, pump station design capacity design increases of 5% or greater, and increases in the number/type of connections), regulations, or the Minimum Design Criteria. Requested modifications or variances to the Minimum Design Criteria will be reviewed on a case -by -case basis and each on its own merit. Please note that variances to the Minimum Design Criteria should be requested and approved during the permitting process prior to construction. After -construction requests are discouraged by the Division and may not be approved, thus requiring replacement or repair prior to certification & activation. [15A NCAC 02T .0116] 8. Gravity sewers installed greater than ten percent below the minimum required slope per the Divisions Gravity Sewer Minimum Design Criteria shall not be acceptable and shall not be certified until corrected. If there is an unforeseen obstacle in the field where all viable solutions have been examined, a slope variance can be requested from the Division with firm supporting documentation. This shall be done through a permit modification with fee. Such variance requests will be evaluated on a case -by -case basis. Resolution of such request shall be evident prior to completing and submitting the construction certification. [ 15A NCAC 02T.0105(n)] 9. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the wastewater collection facilities. [15A NCAC 02T .0116] 10. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2T; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as applicable; and other supporting materials may subject the Page 7 of 9 Permittee to an enforcement action by the Division, in accordance with North Carolina General Statutes §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing board. [15A NCAC 02T .0104;15A NCAC 02T .0108(b-c)] 11. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action, including those as may be required by this Division, such as the construction of additional or replacement facilities. [15A NCAC 02T .0110;15A NCAC 02T .0108(b)] 12. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules, regulations, or ordinances that may be imposed by the Division any other Federal, State, or Local government agencies which have jurisdiction or obtaining other permits which maybe required by the Division or any other Federal, State, of Local government agencies. [G.S. 143-215.1(b)] Page 8 of 9 FAST TRACK SEWER ENGINEERING CERTIFICATION PERMITTEE: City of High Point PERMIT #: WQ0038465 PROJECT: Gravity Sewer to Abandon the Old Thomasville Road Pump Station ISSUE DATE: May 20, 2016 This project shall not be considered complete nor allowed to operate in accordance with Condition 7 of this permit until the Division has received this Certification and all required supporting documentation. It should be submitted in a manner that documents the Division's receipt. Send the required documentation the Regional Supervisor, Water Quality Regional Operations Section at the address at the bottom. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. The Permittee is responsible for tracking all partial certifications up until a final certification is received. A Final Certification shall be a complete set of record drawings and design calculations regardless of whether partials have been submitted. PERMITTEE'S CERTIFICATION I, the undersigned agent for the Permittee, hereby state that this project has been constructed pursuant to the applicable standards & requirements, the Professional Engineer below has provided applicable design/construction information to the Permittee, and the Permittee is prepared to operate & maintain the wastewater collection system permitted herein or portions thereof. Printed Name, Title Signature Date ENGINEERS CERTIFICATION I, , as a duly registered Professional En ineer in the State of North Carolina, having been authorized to observe (❑ periodically, ff weekly, ❑ full time) the construction of the project name and location as referenced above for the above Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit,15A NCAC 02T; the Division of Water Resources' (Division) Gravity Sewer Minimum Design Criteria adopted February 12,1996 as applicable; the Divisions Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials. North Carolina Professional Engineer's Seal w/signature & date: ❑ Final ❑ Partial (include description) Certification Comments/Qualifiers (attach if necessary): NC DWR - Water Quality Regional Operations Section 450 West Hanes Mill Road, Suite 300, Winston-Salem, NC 27105 Winston-Salem Regional Office Phone: (336) 776-9800 FAX: (336)-776-9797 I USE THE TAB KEY TO MOVE FROM FIELD TO FIELD APPiication Number: (to be completed by DWR) 1. Owner/Permittee: 11a. Ci of -High Point NC Full Legal Name (company, municipality, HOA, utility, etc.) Z_._.. 1b. ----- -- ---._. --- ------- - -- -- ----------------------------------------- Terry Houk, Director of Public Services 0 Signing Official Name and Title (Please review 15A NCAC 2T 0106 (b) for authorized signing officials) 1 c. The legal entity who will own this system is ❑ Individual ❑ Federal ® MunicIpality 0 State/County ❑ Private Partners1hjp_0 Corporation ❑ Other_(specify). 0 ;1d. POBox230 Ile. High Point L LL ! 4.. Mailing Address City .. ._._._.. .... ._ .._._._... ._._ .._.... ._.._._ _._._._._.. .. ... ... ... ._..___.._.. _ ___. .. ._._.._._. .___..__._.___._._.___. L 1f. North Carolina 1g. 27261 Z State Zip Code OI-._._....-- _ 1h. ---.._.__.._ .___....__.__._ .... .------- .. _..----- ----.__-.._.__ .. ------- ...-----------..-.._... _-------- --------_----._... 336 883-3215 11i. .1j. Terry.Houk@highpointnc.gov QTelephone L Facsimile E-mail U 2 Protect (Facility) Information: J i2a. Gravity Sewer to Abandon Old Thomasville Road Pump Station 12b. Randolph d Brief Project Name (permit will refer to this name) ( County Where Project is Located a ___ 3. .. ___----- .---_-__. Contact Person: Q 3a. Randy McNeill, PE Davis -Martin -Powell Name and Affiliation of Someone Who Can Answer Questions About this Application 13b. (336) 886-4821 [3c. rmcneill@dmp-inc.com Phone Number E-mail 1. Project is ® New ❑ Modification (of an existing permit) If Modification, Permit No.: 2. Owner is ® Public (skip to Item B(3)) ❑ Private (go to Item 2(a)) 1 i2a. If private, applicant will be: i 2b. If sold, facilities owned by a (must choose one) ❑ Retaining Ownership (i.e. store, church, single office, etc.) or i ❑ Public Utility (Instruction D) ❑ Leasing units (lots, townhomes, etc. - skip to Item B(3)) ❑Homeowner Assoc./Developer (Instruction E) ❑ Selling units (lots, townhomes, etc. - go to Item B(2b)) Z 3. City of High Point, NC ' Owner of Wastewater Treatment Facility (WWTF) Treating Wastewater From This Project Q4a. Westside WWTF 1,4b. NCO024228 ' Name of WWTF WWTF Permit No. 0 Sa. Cityof High Point 5b. 8-in ®Gravity Sc. LL IOwner of Downstream Sewer Receiving Sewer Srze ❑ Force Main Permit # of Downstream Sewer (Instruction F) ......_._.__.._- ..__.____.._._.._._..__._ Z 6. The origin of this wastewater is (check all that apply):-_-- ------------------------ H ! ❑ Residential Subdivision ❑ Retail (Stores, shopping centers) % Domestic/Commercial ❑ Apartments/Condominiums ❑ Institution % Industrial ❑ Mobile Home Park ❑ Hospital LLU 1 ❑ School ❑ Church (Attach Description) p, ! ❑ Restaurant ❑ Nursing Home ova Other ❑ Office ❑ Other (specify) m I.Attacb_Descrintion)....._ I 7. Volume of wastewater to be allocated or permitted for this particular project: None gallons per day *Do not include future flows or previously permitted allocations 8. If the permitted flow is zero, indicate why: ❑ Pump Station, Outfall or Interceptor Line where flow will be permitted in subsequent pe[m�ts hat connect to this line„ Iv C �epaY[ment of ❑ Flow has already been allocated in Permit No. ronmenaua Envitl Quality Y ® Rehabilitation or replacement of existing sewer with no new flow expected Received (see 15A NCAC 02T .0303 to determine if a permit is required) v FTA 10-14 APPLICATION MAY 13 LUIb s*' Winston-Salem Page 4of6 Regional Office ---__ ________ --- --------------- _______ 9. Provide the wastewater flow calculations used in determining the permitted flow in accordance with 15A NCAC 2T .0114 for the value in Item B(7) AND/OR the design flow for line or pump station sizing if a reduced or zero flow is being requested in Item B(7). Values other than that in 15A NCAC 2T .0114 (b) and (c) must be supported with actual water or wastewater use data in accordance with 15A NCAC 2T .0114 (f). Gravity extension to abandon an existing pump station i10. Summary of Sewer Lines to be Permitted (attach additional sheets if necessary) Sae (inches) Length (feet) New Gravity or Additional Force Main _._ -.__._ __ _--- _ ___ __. _._._._ - -- 8 2,524 E New Gravity -------------- _ _. --_ --. _- -- -- - - - - --- -- _ -- - c------ - 1 w- -- - L - - - __ _ --------------------- ------ --- Z F, "11_ Summary of Pump Stations w/ associated Force Mains to be Permitted (attach additional sheets as necessary) __... __._._._.._.-..-.-_._. .______._._._ __._..-.__-. _ ___.. Z O !pump Station Location ID: (self chosen - as shown on plans/map for reference) 0 'I ":Longitude: Latitude: Z, Oi ___---------------- ___---------- ----- --- -__._---_----------- ___ _--__.______. Design Flow Power Reliability Option Operational Point Q (MGD) GPM @TDH i 1 - permanent generator w/ATS; Force Main Sae i Force Main Length 1 2 portable generator w/MTS - - - --. ---- - - --- -- --- o U. j i Z — ;Pump Station Location ID: (self chosen - as shown on plans/map for reference) N i !Longitude: Latitude: - --- -_ ... ------ --- _._. _._-___ .. _._-. _.._-- .---_.____.._ . . W Design Flow Power Reliability Option a (MGD) Operational Point1 - permanent generator w/ATS; Force Main Sae Force Main Length m GPM @TDH 2 - portable generator w/MTS ------ — '... .. I I I i12. Will the wastewater flow in the proposed sewer lines or pump stations be able to be directed to another treatment facility? ❑ Yes ® No If Yes, permit number of 2nd treatment facility (RO - if "yes" to 13,12 please contact the Central Office PERCS Unit) 113. Does the sewer system comply with the Minimum Design Criteria for the Permitting of Pump Stations and Force Mains (latest version), the Gravity Sewer Minimum Design Criteria (latest version) and 15A NCAC Chapter 2T as applicable? ® Yes ❑ No I If No, complete and submit the Variance/Alternative Design Request (VADC 10-14) application and supporting documents for review. Approval of the request is required prior to submittal of the Fast Track Application and supporting documents. FTA 10-14 APPLICATION Page 5 of 6 14. Have the following permits/certifications been submitted for approval for the system or project to be served? Wetland/Stream Crossings - General Permit or 401 Certification? ❑ Yes ❑ No ® N/A i Sedimentation and Erosion Control Plan? ® Yes ❑ No ❑ N/A Trout Buffer Waiver? ❑ Yes ❑ No ® N/A Stormwater? ❑ Yes ❑ No ® N/A 115. Does this project include any high priority lines (15A NCAC 02T .0402 (2)) involve aerial lines, siphons, or interference manholes)? These lines will be considered high priority and must be checked once every six months Check if Yes: ❑ and provide details: 11. Owner/Permittee's Certification: (Signature of Signing Official and Project Name) I /, Terry Houk, attest that this application for Gravity Sewer to Abandon Old Thomasville Road Pump Station has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of i this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. Note: In accordance with North Carolina General Statutes 143-215.6A and 143-215.6E any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000 as well as civil penalties _uprto $25,000 per violation. �Il a. L Signing Official ature Date i ENGINEERING DESIGN DOCUMENTS MUST BE COMPLETED PRIOR TO SUBMITTAL OF THIS APPLICATION. THESE DOCUMENTS MUST INCLUDE PLAN AND PROFILE OF SEWERS, THEIR PROXIMITY to TO OTHER UTILITIES, DESIGN CALCULATIONS, ETC. REFER TO 15A NCAC 02T .0305 Z O _____ ____ __-_ --- --_ _____ __.______ ____ --- ______----------- ____________ _--- ___ ___________ _ h-- Q 2. Professional Engineer's Certification: (Signature of Design Engineer and Project Name) C) 1,� 7 1/ ' "/� attest that this application for Gravity Sewer to Abandon Old Thomasville LL Road Pump Station has been reviewed by me and is accurate, complete and consistent with the information in the engineering plans, calculations, and all other supporting documentation to the best of my knowledge. I further attest that W to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, V Gravity Sewer Minimum Design Criteria for Gravity Sewers adopted February 12, 1996, and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 and the watershed classification in V accordance with Division guidance. Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that / have reviewed this material and have judged it to be consistent with the proposed design. Note: In accordance with NC General Statutes 143-215.6A and 143- 215.6B any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 Professional Engineer Name Davis -Martin -Powell & Associates, Inc. Engineering Firm Mailing Address Rn--..--. .�. 2d High Point 2e NC 2f 27265s t�,�'�jN��� \ City State Zip 2g. 336-819-5283 2h. 336-886-4458 2i. rmcneill@dmp-inc.com Telephone j Facsimile IE-mail INC PE Seal, Signature & Date FTA 10-14 APPLICATION Page 6 of 6 Mr. Corey Basinger NCDEQ — DEMLR 450 West Hanes Mill Road, Suite 300 Winston-Salem, North Carolina 27105 Dear Corey: May 11, 2016 Re: City of High Point, NC Gravity Sewer to Abandon Old Thomasville Road Pump Station DMP Project 150302 (BF) NC Department of 4. n Environmental Quality Received MAY 13 2016 re +5fj4'S 7 b`La F.2€=; Winston-Salem Regional Office. Fa On behalf of the City of High Point and in regards to the referenced project we are enclosing the following information for your review and approval: • Two (2) copies of Fast -Track Application for Gravity Sewers, Pump Stations and Forcemains • Two (2) copies of Watershed Classification Attachment (WSCAS-01-15) with Quad sheet • Two (2) copies of site map exhibit • $480 review fee The proposed project will involve the construction of 2,524 LF of 8-inch gravity sewer main and associated appurtenances to allow abandonment of an existing sewer pumping station, with no additional sewer capacity at this time. City staff has talked with your office and determined that a FTSE form is not required since no new flows are associated with this project. We trust the enclosed information is complete and will allow for approval to be issued at an early date. However, should you have any questions or require additional information, please contact our office. Sincerely, C: Terry Houk, City of High Point Tyler Barrier, City of High Point (enc) File (enc) T:336-886-4821 1 F:336-8864458 1 www.dmp-inc.com 6415 Old Plank Road, High Point, NC 27265 State of North Carolina Department of Environment and Natural Resources PI-13s-40in Division of Water Resources of Water Resources Watershed Classification Attachment (WSCAS 01-15) Along with this form, submit a color copy of a USGS Topographic Map to identify the project area and waterbodies. Each map or maps must show the location of the sewer system and include location identifiers where the system traverses over or near waterbodies. The map should have location ID's for each different waterbody and corresponding classifications should be recorded. Include the completed form and map portions with the permit application for submittal to the appropriate review agency. A list of the Division's regional offices, their county coverage, and contact information can be obtained from: http://Portal.ncdenr.org/web/wa/home/ro Location ID Name of Waterbody' River Basin Waterbody Index No. Waterbody Classification S01 Unnamed Tributary to Kennedy Mill Creek Yadkin Pee -Dee 12-119-7-2 C I If unnamed, indicate "unnamed tributary to X% where X is the named waterbody to which the unnamed tributary joins. I certify that as a Registered Professional Engineer in the State of North Carolina that I have diligently followed the Division's instructions for classifying waterbodies and that the above classifications are inclusive of the stated project, complete and correct to the best of my knowledge and belief. PE Seal, Signature and Date IR D _7 DR� ` B - HEL RD CD r RANDOj,PH C P/NEV/ EW n )'' AV BDEN KDADR �v`' \ r r � � AV � W CLE CT 55 � o I � L ��ly o a ,ARCHD ALE, o� a 4 a 70 A, -77 Cl 8,(SUNSET VIEW DR MIDDLFP— / �c 3974 D `� LDpN LP UL OR �. �. RDSPECT-CNURCN RDI 3 LOISw ,,OI ,-��_„�����. ,:� '� ,�,"0;-��:� (" it •.( MENDENHALL ��._. z l / DwaR �a "73 Y1 � JENNIFER CT) �W, r950f 3972 r {j I. r, 1 I' ��� � ( t �6DSypOD TR[ „. �Loiver B D y I \ Lake i 1 Upper Lalc i m '3 300. \\\\\\ LaICe 8 0 O/ COLO AL CIR t %}:r 35052'3( 586 2,30„ 587 188 58900o E 596 so°00' h i iC A . a -EX EX. 8-IN GRAVITY SEWER, _e s DOWNSTREAM y— — — _ — j PROPOSED 8-IN GRAVITY SEWER 2,524 LF - -j - _ Aye. t I � I I � i i2 ,. - pineVieWf AYe ` Boles -Ave t Bolivargye. i I o ` - Bethel Pr qa , a Bethel park 4r PS _.. or r O PctR ~ EX. PUMP STATION BUS 1-85 gad " SL ° I � N I o a � Maxine Dr I Glenda Dr I DAMS • MARTIN • POWELL dm r ' ENGINEERS & SURVEYORS 1 inch = 750 feet Old Thomasville Road Gravity Sewer Extension Street Site Map DMP Project No.: 150302 =_ r J i HANK OF AMERICA as-taisao yl{ City of High Point CHP,RLOTTE,NC28255 �A Treasury Services Division 652$32 - P.O. Box 230 NORTH GROLINA'S INiF.RNAIIONAL i.IfY High Point, NC 27261 05/0512016 .VOID IF PRESENTED AFTER So DAYS PAY Four Hundred Eighty and 00/100 Dollars'' $480.00 This Disbursement has been approved as required by the Local Government Budget and Fiscal Control Act TO THE NCDEQ (47659) ORDER OF 450 WEST HANES MILL RD STE 300 1—T— WINSTON SALEM NC 27105 ill 0652832V 1:0S30001961: 000695to63612110 Description PO # Inv # OLD TVILLE RD PUMP STA OLD TVILLE 05/02/16 FAST TRACK APP RDPUMP STA Total Amount Description $480.00 ------------- # Inv# Amount $480.00 ,". NC Department of .-q Environmental Quality Received ' MAY i 0 2016 4 Winston-Salem 1'4l��; a,. Regional Office a r