HomeMy WebLinkAboutNCS000571_Tiered Response Notice Letter_20181203Cliffside Steam Station
573 Duke Power Roaa
Mooresboro,
North Carolina 28114
828 657 2000
November 15, 2018
Mr. Zahid Khan
North Carolina Department of Environmental Quality
Mooresville Regional Office
610 East Center Ave. 44PA
Mooresville, NC 28115
Subject: Duke Energy Carolinas, LLC �^
Rogers Energy Complex -Cliffside Steam Station���� �
NPDES Industrial Storm Water'tE
Outfall SWO04 - Copper Tier 3 Y .
Permit Number NCS000571
Dear Mr. Khan: h
v�
In accordance with the requirements of the Industrial Stormwater Permit NCS000571, this letter
is written notification that Cliffside Steam Station is in Tier 3 status at outfall SWO04 for copper.
The benchmark value for copper is 0.010 mg/l. The 4th copper benchmark exceedance result for
the sampling event on 10/10/2018 was received on 10/26/2018.
Stormwater sample results for Outfall SWO04 are as follows (benchmark exceedances in bold):
Date Collected
Cu Results m /1
5/17/2016
0.0127
11/29/2016
0.0242
1/21/2017
0.0031
2/ 15/2017
0.00593
3/31/2017
0.0123
4/19/2017
0.00982
6/ 13/2017
0.00815
8/11/2017
0.00727
9/6/2017
0.00351
11 /7/2017
0.00575
12/20/2017
0.00275
2/7/2018
0.00875
4/23/2018
0.00980
7/19/2018
0.00472
10/10/2018
0.0113
Cliffside has taken measures to reduce copper by installing MetaLoxx socks in catch basins that
collect stormwater at outfall SWO04. New MetaLoxx socks are also planned to be installed.
Letter to Mr. Zahid Khan
Page 2 of 2
If you have any questions or need additional information please contact Robert Wylie at (704)
382-4669 or Michael Disch at (828) 657-2200
I certify, under penalty of law, that this document and all attachments were prepared under my
direction or supervision in accordance with a system designed to assure that qualified personnel
properly gather and evaluate the information submitted. Based on my inquiry of the person or
persons who manage the system, or those persons directly responsible for gathering the
information, the information submitted is, to the best of my knowledge and belief, true, accurate,
and complete. I am aware that there are significant penalties for submitting false information,
including the possibility of fines and imprisonment for knowing violations.
Sincerely,
David P. Barnhardt
General Manager II, Cliffside Steam Station
Fossil/Hydro Operations - Carolinas Coal Generation
LISPS Certified Mail Tracking:
7017 3380 0000 5159 9044 (Mooresville DEMLR-extra copy)
Electronic copy:
Robert Wylie
Tina Woodward
Andrew Stroud