HomeMy WebLinkAboutWQ0001664_Compliance Evaluation Inspection_20190517ROY COOPER
Co{frlar
K41C fAEL S. R.EGAN
Secretary
LINDA CULPEPPER
arwtoy
Tony Konsul
Carolina Water Service Inc. of North Carolina
PO Box 240908
Charlotte, NC 28224-0908
NORTH CAROUNA
Environmental Qual"
July 05, 2019
SUBJECT: Compliance Inspection Report
Belvedere Plantation WWTF
Non -discharge Permit No. WQ0001664
Pender County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Belvedere Plantation WWTF on
5/17/2019. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non -discharge Permit No. WQ0001664. The findings and comments noted
during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection
Report" (CIR). The facility was found compliant.
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required. However, notice that in the summary of the CIR it is requested the following:
*Future wetland annual reports be submitted (e-mail preferable) to the Wilmington Regional Office.
Attention: Water Quality Regional Operations Section- Morelia Sanchez King.
Subject line: Belvedere WWTF - WQ0001664- Wetland Annual Report.
•The Wetland Annual Report must include a narrative describing findings during the period, impacts (if any),
conclusions, future sampling plans, etc.
If you should have any questions, please do not hesitate to contact Morelia Sanchez -King with the Water Quality
Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
morella.sanchez-king@ncdenr.gov.
ATTACHMENTS (CIR)
Laserfiche
Sincerely,
DocuSigned by:
E��� Sa�7 6"
E3ABA14AC7DC434...
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
North CaroLrns Departrrent of Err r-Dr. mamtsd Qual.kv I D7W57on of Water Resources
Wilrningom Reg mLa:Offw 1 127 CarMfnlDrive Extertsoo 115Farnngtoa, North CaTofrna.23445
910-796-7215
Compliance Inspection Report
Permit: WQ0001664
SOC:
County: Pander
Region: Wilmington
Contact Person: Tony Konsul
Directions to Facility:
Effective: 02/14/17 Expiration: 01/31/20 owner: Carolina Water Service Inc of North Carolina
Effective: Expiration: Facility: Belvedere Plantation WWTF
128 Fairway Dr
System Classifications: SI, WW3,
Primary ORC: Eddie Ray Baldwin
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Title: Regional Manager
Certification: 18533
Hampstead NC 28443
Phone: 704-319-0523
Phone: 910-376-4175
Inspection Date: 05/17/2019 Entry Time: 02:30PM Exit Time: 04:OOPM
Primary Inspector: Morella Sanchez -King Phone: 910-796-7218
Secondary Inspector(s): Docusigned by:
ElbV�A Sa.. ,1.. ^ 64 7/5/2019
E3ABA14AC7DC434_
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Treatment Barscreen
Use Records
Treatment Filters Record Keeping Treatment Activated Sludge
Treatment Clarifiers Treatment Disinfection End Use -Infiltration
Treatment Flow Measurement Treatment Return pumps Standby Power
Coastal Requirements
(See attachment summary)
Page 1 of 7
Permit: WQ0001664 Owner - Facility: Carolina Water Service Inc of North Carolina
Inspection Date: 05/17/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A file review and a facility compliance inspection (5/17/2019) were conducted to verify compliance with conditions specified
in permit WQ0001664. The assistance provided by Mr. Eddie Baldwin and Gregory Spillman during the inspection is greatly
appreciated. The facility was found compliant.
File Review
a) Effluent monitoring
Since the last inspection in June 2017, the facility has not shown non-compliance issues in the NDMRs or NDARs. If any
non-compliance issue is observed, please contact Helen Perez (910 796 7323) within 24 hours.
b) Groundwater monitoring
GW-59 records for the period 2017-2019 show compliance with monitoring requirements and 2L standards. Nitrate
concentrations in all wells are regularly below detection limits, except in MW-7 (located around the spray fields) that have
shown concentrations of 5.42 and 5.45 mg/I in March 2018 and 2019, respectively.
c) Wetland Annual Report
The writer could not find the wetland annual report in our regional office file and requested that future reports (next to be
submitted January 31, 2020) be e-mailed to the Wilmington Regional Office indicating in the subject line: Belvedere WWTF
— WQ0001664- Wetland Annual Report. The report should include a narrative documenting findings, impacts, future
sampling plans, etc.
Site Compliance Inspection
a) Operation and maintenance: The facility uses the three high rate infiltration basins for effluent disposal while the spray
irrigation fields at the golf course are used as a backup disposal option. Irrigation has not been used in the last two years.
All equipment is still in place, if needed. The writer did not inspect the irrigation fields.
b) Equipment testing: The standby generator was tested during the inspection, it worked well. The generator is tested
weekly, every Wednesday. The standby generator worked without interruption for 2.5 days during hurricane Florence. It is
assumed, therefore, that servicing of the equipment is appropriate.
c) Effluent quality: clear and odorless.
In summary, the facility looks very well operated and maintained. Records are organized.
Page 2 of 7
Permit: WQ0001664
Inspection Date: 05/17/2019
Owner - Facility: Carolina Water Service Inc of North Carolina
Inspection Type : Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Lagoon Spray, LR
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Single Family Drip
❑
Recycle/Reuse
❑
Infiltration System
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: The facility consists of a BNR system with effluent limits of TN=7mg/I and TP=3 mq/I; two
anaerobic zones, two pre -anoxic zones, and two post -anoxic zones. The BNR system and the
rest of the facility components are operational and consistent with their description in the permit.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ 0 ❑
Is flowmeter operating properly?
❑
❑ 0 ❑
Does flowmeter monitor continuously?
❑
❑ 0 ❑
Does flowmeter record flow?
❑
❑ 0 ❑
Does flowmeter appear to monitor accurately?
❑
❑ 0 ❑
Comment
Treatment Flow Measurement -Water Use Records
Yes No NA NE
Is water use metered? ❑ ❑ 0 ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
0
❑
❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
0
❑
❑ ❑
Does flowmeter appear to monitor accurately?
0
❑
❑ ❑
Comment: Flow meter was calibrated 01/09/2019
Page 3 of 7
Permit: WQ0001664 Owner - Facility: Carolina Water Service Inc of North Carolina
Inspection Date: 05/17/2019 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Standby Power
Yes No NA NE
Is automatically activated standby power available?
0
❑
❑ ❑
Is generator tested weekly by interrupting primary power source?
❑
❑ ❑
Is generator operable?
❑
❑ ❑
Does generator have adequate fuel?
❑
❑
❑
Comment: The standbv aenerator was activated and produced adeauate Dower to run the Dlant. It also
performed well for almost 3 days during hurricane Florence.
Treatment Barscreen
Yes No NA NE
Is it free of excessive debris?
0
❑
❑ ❑
Is disposal of screenings in compliance?
0
❑
❑ ❑
Are the bars spaced properly?
0
❑
❑ ❑
Is the unit in good condition?
0
❑
❑ ❑
Comment: The facility has a bar screen and a fine mesh screen. The bar screen is not in use. The mesh
screen receives maintenance periodically, as needed.
Treatment Activated Sludge
Is the aeration mechanism operable?
Is the aeration basin thoroughly mixed?
Is the aeration equipment easily accessed?
Is Dissolved Oxygen adequate?
Are Settleometer results acceptable?
Is activated sludge an acceptable color?
Comment: On inspection day/time the DO was 2.49 mg/I. The ORP meter is constantly recording. Jar
tests are performed daily for process control.
Treatment Clarifiers
Are the weirs level?
Are the weirs free of solids and algae?
Is the scum removal system operational?
Is the scum removal system accessible?
Is the sludge blanket at an acceptable level?
Is the effluent from the clarifier free of excessive solids?
Yes No NA NE
■❑❑❑
■❑❑❑
■❑❑❑
■❑❑❑
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
■❑❑❑
■❑❑❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Only one clarifier is in use. It looked well maintained on insDection day. The second clarifier is
operational and would be used as backup if required.
Treatment Return pumps Yes No NA NE
Are they in place? ❑ ❑ ❑
Are they operational? ❑ ❑ ❑
Comment: Return pumps were operational on inspection date.
Page 4 of 7
Permit: WQ0001664 Owner - Facility: Carolina Water Service Inc of North Carolina
Inspection Date: 05/17/2019 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Treatment Filters
Yes No NA NE
Is the filter media present?
❑
❑
❑
Is the filter media the correct size and type?
❑
❑
❑
Is the air scour operational?
❑
❑
❑
Is the scouring acceptable?
0
❑
❑ ❑
Is the clear well free of excessive solids?
0
❑
❑ ❑
Is the mud well free of excessive solids and filter media?
0
❑
❑ ❑
Does backwashing frequency appear adequate?
0
❑
❑ ❑
Comment: Filter backwashing is automatic
Treatment Disinfection
Yes No NA NE
Is the system working?
0
❑
❑ ❑
Do the fecal coliform results indicate proper disinfection?
0
❑
❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑
❑
Is the system properly maintained?
0
❑
❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑
0 ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑
0 ❑
Is the chlorinator accessible?
0
❑
❑ ❑
If tablets, are tablets present?
❑
❑
0 ❑
Are the tablets the proper size and type?
❑
❑
0 ❑
Is contact chamber free of sludge, solids, and growth?
0
❑
❑ ❑
If UV, are extra UV bulbs available?
❑
❑
0 ❑
If UV, is the UV intensity adequate?
❑
❑
0 ❑
# Is it a dual feed system?
❑
❑
0 ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑
0 ❑
If yes, then is there a Risk Management Plan on site?
❑
❑
0 ❑
If yes, then what is the EPA twelve digit ID Number? (1000-_ _)
If yes, then when was the RMP last updated?
Comment: Since the last inspection in 2017, there have not been fecal coliform violations. Therefore,
disinfection seems to be adequate. Liquid sodium hypochlorite is used for disinfection.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
0
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑ ❑ ❑
NDAR?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Page 5 of 7
Permit: WQ0001664 Owner - Facility: Carolina Water Service Inc of North Carolina
Inspection Date: 05/17/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is GW monitoring being conducted, if required (GW-59s submitted)?
0
❑
❑ ❑
Are all samples analyzed for all required parameters?
0
❑
❑ ❑
Are there any 2L GW quality violations?
❑
0
❑ ❑
Is GW-59A certification form completed for facility?
❑
❑
0 ❑
Is effluent sampled for same parameters as GW?
0
❑
❑ ❑
Do effluent concentrations exceed GW standards?
❑
0
❑ ❑
Are annual soil reports available?
❑
❑
0 ❑
# Are PAN records required?
❑
❑
0 ❑
# Did last soil report indicate a need for lime?
❑
❑
0 ❑
If so, has it been applied?
❑
❑
0 ❑
Are operational logs present?
0
❑
❑ ❑
Are lab sheets available for review?
0
❑
❑ ❑
Do lab sheets support data reported on NDMR?
0
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑
❑
Are Operational and Maintenance records present?
❑
❑ ❑
Were Operational and Maintenance records complete?
0
❑
❑ ❑
Has permittee been free of public complaints in last 12 months?
❑
❑
❑
Is a copy of the SOC readily available?
❑
❑
0 ❑
No treatment units bypassed since last inspection?
❑
❑
0 ❑
Comment: Records were complete and well kept. The operation and maitenance
plan was e-mailed to the
regional office after the site inspection.
End Use -Infiltration
Yes No NA NE
# Is the application High Rate or Low Rate?
High Rate
Are buffers maintained?
E
❑
❑ ❑
Are any supply wells within the CB?
❑
0
❑ ❑
Are any supply wells within 250' of the CB?
❑
0
❑ ❑
Is municipal water available in the area?
0
❑
❑ ❑
Are GW monitoring wells required?
0
❑
❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
0
❑
❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
0
❑
❑ ❑
Is a usable green area maintained?
0
❑
❑ ❑
Is the disposal site acceptable?
0
❑
❑ ❑
Is the distribution equipment acceptable?
0
❑
❑ ❑
Is the disposal site free of ponding?
0
❑
❑ ❑
Is the disposal site free of breakout?
0
❑
❑ ❑
Are the disposal sites free of solids, algae, etc.?
0
❑
❑ ❑
Page 6 of 7
Permit: WQ0001664 Owner - Facility: Carolina Water Service Inc of North Carolina
Inspection Date: 05/17/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Do the records show that the fields are properly maintained?
0
❑
❑ ❑
Are the disposal sites free of vegetation?
0
❑
❑ ❑
Do any surface water features appear to be adversely impacted by GW discharge?
❑
0
❑ ❑
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
❑
❑
❑
Comment: High -rate infiltration basins looked well maintained. Their operation was observed during
site
visit.
Coastal Requirements
Are essential treatment units provided in duplicate?
Is an adequately sized aerated equalization basin present?
If so, is it operable?
If present, are diffusers cleaned regularly?
Is the equalization capacity adequate?
Comment:
Yes No NA NE
■❑❑❑
■❑❑❑
■❑❑❑
❑❑❑■
■❑❑❑
Page 7 of 7