HomeMy WebLinkAboutNC0087106_Inspection_20190625EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0087106 19/05/30 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Champion Hills WWTP
1000 Indian Cave Rd
Hendersonville NC 28739
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
09:30AM 19/05/30 16/01/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Danielle Ann Hunter/ORC/828-251-1900/
Other Facility Data
10:00AM 19/05/30 20/11/30
Name, Address of Responsible Official/Title/Phone and Fax Number
Craig Galloway,1 Hagen Dr Hendersonville NC 28739/Director of Grounds &
Facilities/828-696-1662/8286962097
Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenance Self-Monitoring Program
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Beverly Price ARO WQ//828-296-4500/
Daniel J Boss ARO WQ//828-296-4658/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: EBB2D674-5E25-4DAD-AB80-F328103D6254
6/26/2019
6/26/2019
6/26/2019
NPDES yr/mo/day
19/05/30
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Bev Price and I (Daniel Boss) conducted a compliance evaluation inspection of the Champion Hills
WWTP on May 30, 2019. We met with Bob Barr, Danielle Hunter (ORC), and Craig Galloway
(Grounds Manager) during the inspection.
The tertiary filters are in the process of being repaired.
The effluent sampling is now flow proportional. The composite samples are still being drawn from the
chlorine contact chamber, but they are planning to move the sampling location to a wet well that is
beyond all treatment units.
The airlift pumps in the EQ basin are set to be replaced by submersible pumps.
The clarifiers seemed to be functioning better. There was less pin floc coming over the weirs and the
effluent appeared much clearer for one of the two clarifiers.
------------------------------------------------------------------------
On 6/25/2019 Bev Price and I conducted an additional follow up inspection with Bob Barr and Danielle
Hunter. The compliance issues from the 5/30/2019 inspection have been resolved. The tertiary filters
are now online, fully functional, and have a modified and improved backwash mechanism. The EQ
basin pumps have been replaced with submersible pumps which are keeping the basin at lower level,
allowing for greater moderation of flow at the facility. The composite sampling location is now beyond
all treatment units.
NC0087106 17 (Cont.)
Page#2
DocuSign Envelope ID: EBB2D674-5E25-4DAD-AB80-F328103D6254
Permit:NC0087106
Inspection Date:05/30/2019
Owner - Facility:
Inspection Type:
Champion Hills WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
New basin pumps have been purchased and just need to be installed. The new pumps are
submersibles rather than airlift pumps. Mr. Barr said that the EQ basin has had to be kept at
a high level because the airlift pumps are not capable of pumping for the needed lift.
*6/25/2019: The new submersible pumps have been installed and are keeping the EQ basin
at a lower level.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
One of the clarifiers appeared to be clearer than during my previous inspection. The other
clarifier was still murky with some pin floc coming over the weirs.
Comment:
Page#3
DocuSign Envelope ID: EBB2D674-5E25-4DAD-AB80-F328103D6254
Permit:NC0087106
Inspection Date:05/30/2019
Owner - Facility:
Inspection Type:
Champion Hills WWTP
Compliance Evaluation
Filtration (High Rate Tertiary)Yes No NA NE
Type of operation:Down flow
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
The tertiary filters are in the process of being repaired. Mr. Barr is having the air scour
repositioned to completely below the media rather in the middle of it, so the air scour will
clean the entire media.
*6/25/2019: The tertiary filters are now online and fully functional.
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Flow proportional composite sampling is now taking place at the facility. The location of the
sampling is in the process of being changed so that it is beyond all treatment units.
*6/25/2019: The sampling location is now beyond all treatment units.