HomeMy WebLinkAboutNC0023884_Compliance Evaluation Inspection_20190626ROY COOPER
Governor
MICHAEL S. REGAN
Secretory
LINDA CULPEPPER
Director
Ms. Sonja Basinger
Environmental Services Manager
City of Salisbury
1915 Grubb Ferry Road
Salisbury, NC 28144
Dear Ms. Basinger:
NORTH CAROLINA
Environmental Quality
June 26, 2019
SUBJECT: Compliance Evaluation Inspection
Grant Creek/Town Creek WWTP
NPDES Permit NCO023884
Rowan County, NC
On June 13, 2019, Roberto Scheller of this Office conducted a compliance inspection at the
subject facilities. This inspection was conducted as a Compliance Evaluation Inspection (CEI) to
insure compliance with permit requirements and conditions. The subject facility appeared to be
well operated and we wish to thank the operating staff for assistance regarding this inspection.
The enclosed report should be self-explanatory; however, should you have any questions,
please do not hesitate to contact myself or Roberto Scheller at (704) 235-2204 or
roberto.scheller(o-)ncdenr.gov.
Sincerely,
DocuSigned by:
A#'. uv f/ P:" for
F161FB69A2D84A3...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: CEI Report
D Q
�� North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
None-icanauNn i
nwm,em of eemwoviRv 704,663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NCO023884 111 12 I 19/06/13 I17 18 I S i 19 i G i 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved -------------------
671
70II 71 I I 72 I r I 73I I 74 75I I I I I I I I80
I —I I� I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:17AM 19/06/13
14/12/01
City of Salisbury WWTP
1915 Grubb Ferry Rd
Exit Time/Date
Permit Expiration Date
Salisbury NC 281444261
12:25PM 19/06/13
19/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Sonja Basinger,1915 Grubb Ferry Rd Salisbury NC 281444261/Env. Services
Manager/704-638-5375/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Compliance Schedules
Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s�of Inspector(s) Agency/Office/Phone and Fax Numbers Date
by:
ocuSigned
('
Roberto SchellerCV+ MRO WQ//252-946-6481/ 6/25/2019
91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone d Fax°%iurn6ers y' Date
4-0 ' fi P44-ft for WC13 6.26.19
W. Corey Basinger Division of Water Quality//704-2;
L!F161FB69A2D84A3..
.
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO023884 I11 12, 19/06/13 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO023884 Owner - Facility: City of Salisbury WWTP
Inspection Date: 06/13/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
❑
❑
0
❑
# Are there any special conditions for the permit?
M
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Renewal application was received by the Division on December 20, 2018. Permit is for the
operation of two wastewater treatment trains. Grant Creek wastewater treatment train,
wihich is a 7.5 MGD, and Town Creek which is a 5.0 MGD wastewater treatment train with a
common discharge (Outfall #001) into the Yadkin River.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: Reviewed annual report on-line for 2018.
Page# 3
Permit: NCO023884 Owner - Facility: City of Salisbury WWTP
Inspection Date: 06/13/2019 Inspection Type: Compliance Evaluation
Compliance Schedules Yes No NA NE
Is there a compliance schedule for this facility? ❑ ❑ 0 ❑
Is the facility compliant with the permit and conditions for the review period? ❑ ❑ 0 ❑
Comment: Review of 12 month comDliance history for subiect facilitv found 3 - NOD's issued for
Monthly Average Flow violations durinq months of 12/2018, 01/2019, 02/2019 (All flows were
<20%). NOD was issued for Weekly Average BOD violation during month of 04/2019.
Reported weekly average limit violation was 9.3% over permit limit value.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
M
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ❑
Comment: Grant Creek WWTP has an on -site laboratory, Certification #112, and also uses contract lab
Research Analytical Laboratory Certification #34. Meter calibration sheets should indicate
meter serial number to link meter to calibration sheet for both Grant Creet and Town Creek
WWTP's.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Page# 4
Permit: NCO023884
Inspection Date: 06/13/2019
Owner - Facility: City of Salisbury WWTP
Inspection Type: Compliance Evaluation
Grit Removal
Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment:
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
M
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: At time of inspection Grant Creek influent sampler was recorded at 0 degrees Celsius.
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment:
Primary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Page# 5
Permit: NCO023884 Owner - Facility:
City of Salisbury WWTP
Inspection Date: 06/13/2019 Inspection Type:
Compliance Evaluation
Primary Clarifier
Yes No NA NE
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the sludge blanket level acceptable?
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
❑
❑
❑
Comment:
Trickling Filter
Yes No NA NE
Is the filter free of ponding?
❑
❑
0
❑
Is the filter free of leaks at the center column of filter's distribution arms?
❑
❑
0
❑
Is the distribution of flow even from the distribution arms?
❑
❑
0
❑
Is the filter free of uneven or discolored growth?
❑
❑
0
❑
Is the filter free of sloughing of excessive growth?
❑
❑
0
❑
Are the filter's distribution arms orifices free of clogging?
❑
❑
0
❑
Is the filter free of excessive filter flies, worms or snails?
❑
❑
0
❑
Comment: 2 trickling filters located at Grant Creek WWTP are being converted into EQ basins.
Chemical Feed
Yes No NA NE
Is containment adequate?
0
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Are backup pumps available?
0
❑
❑
❑
Is the site free of excessive leaking?
0
❑
❑
❑
Comment: Defoamer (Polytec - 318) is being added to control foam in aeration basin.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Surface
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
0 ❑
❑
❑
Are the diffusers operational?
❑ ❑
0
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
❑ ❑
❑
Page# 6
Permit: NCO023884 Owner - Facility: City of Salisbury WWTP
Inspection Date: 06/13/2019 Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑
Comment:
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
0
❑
❑
❑
Comment:
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Comment: The Grant Creek facility has 2 sets of screw lift pumps.
Disinfection -Liquid
Yes No NA NE
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
(Sodium Hypochlorite) Is pump feed system operational?
M
❑
❑
❑
Is bulk storage tank containment area adequate? (free of leaks/open drains)
0
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Page# 7
Permit: NCO023884
Inspection Date: 06/13/2019
Disinfection -Liquid
Owner - Facility: City of Salisbury WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: At time of Grant Creek inspection effluent from 2 rectanaular secondary clarifiers was clear
with few visible suspended soilds. Effluent from #4 circular secondary clarifier was clear
with few visible suspended solids. Effluent from #3 circular secondary clarifier contained
large amounts of suspended solids going over weirs. Suspended solids were noted in
chlorine contact basin.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
❑
❑
❑
■
Comment: At time of inspection effluent sampler was recorded at 2.5 degrees Celsius. Effluent at
outfall #001 was clear with random particles of suspended solids. Effluent temperature was
recorded at 21.0 to 20.9 degrees Celsius. Dissolved Oxygen (DO) was recorded at head of
step aeration at 6.67 mg/I. TRC was recorded at 14 ug/I.
Pump Station - Effluent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
❑
❑
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment: Effluent is pumped to a common discharge with Town Creek WWTP at Outfall #001.
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Yes No NA NE
Liquid
❑
❑
❑
■
❑
❑
■
❑
■
❑
❑
❑
❑
❑
■
❑
Page# 8
Permit: NCO023884
Inspection Date: 06/13/2019
De -chlorination
Are tablet de -chlorinators operational?
Number of tubes in use?
Owner - Facility: City of Salisbury WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
❑ ❑ ■ ❑
Comment: At time of inspection effluent TRC, collected at head of step aeration, was recorded at 14
uq/I.
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Comment: New flow meters have been installed at Grants Creek and Town Creek. Calibration records
from installation for both meters were reviewed.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
❑
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: Bio-solids are moved through digester for volatile reduction and pumped to belt -filter press
to
dewater. Solids are land applied under Water Quality
Permit #WQ001956. Solids are stored
on covered pad until land appication.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment:
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 9