HomeMy WebLinkAboutNC0023604_Fact Sheet (revised)_20190618DEQ/DWR/NPDES
FACT SHEET FOR NPDES PERMIT RENEWAL
NPDES Permit NCO023604
Table 1-- Facility Information
Applicant / Facility Name:
Ronnie D. Bolt / Wilderness NC, Inc. Lumber Plant
Applicant Address:
P.O. Box 2136 Lexington 27293
Facility Address:
7578 US Hwy 64 E., Thomasville, NC 27360
Permitted Flow / Average:
0.0124 MGD Outfall 001 ; Outfall 002 not limited
Type of Waste:
SIC Codes 321912 & 32113 [principal process Kiln -drying lumber]
Facility / Permit Status:
Minor Industry, Class WW-2 / renewal
County:
Davidson
Permit Special Conditions:
Biocide Condition; eDMR required; High Rock Lake Re -Opener
Miscellaneous
Receiving Stream:
UT to
Flat Swamp Creek
Regional Office:
Winston-Salem
Stream Class / Segment:
C / 12-123
State Grid / USGS Quad:
D18SE / Fair Grove
303 d Listed?
No
Permit Writer:
Joe R. Corporon PG
HUC:
03040101
Date:
18Jun2019
Drainage Area (mi2):
0.0
Lat. 350 46' 30" N Long. 800 07' 12" W
Summer 7Q 10 (cfs)
0.0
Winter 7 10 cfs
0.0
Average Flow cfs :
0.0
IWC (%):
Assume 100%
Facility Summary: Wilderness NC, Inc. (Wilderness) produces kiln -dried lumber. Freshly
milled lumber is delivered to their facility from offsite sources. Wilderness employees generate
100% domestic wastewater treated onsite by a Class WW-2 plant discharging via Outfall 001 and
kiln condensate from the lumber -drying process via Outfall 002. These both discharge to a UT to
Flat Swamp Creek. WWTP facilities include:
• aeration chamber
• sludge holding tank
• clarifier
• recirculating sand filter
• 5:1 flow splitter
• 1,500-gallon recirculation tank with air diffuser
• filter screens
• dual (2) pumps
• tablet chlorination and dechlorination
• polishing / settling pond (54-day retention)
Receiving Stream: This facility discharges to a UT to Flat Swamp Creek, a Class C waterbody
within the Yadkin -Pee Dee River Basin. This creek supports designated uses; not impaired — not
listed on the 2018 NC 303(d) list.
Compliance History & DMR Data Review - Jun2016 thru Jun2019: March and October of
2016 showed frequency violations for Temperature (no action — amended DMR). WSRO (Paul
DiMatteo) proceeded to NOD for Fecal Coliform violation in Nov2017. BIMS notes multiple
TRC violations, ignored per TRC policy as < 50 ug/L. WSRO (Paul DiMatteo) notes missing
Fact Sheet
NPDES NC0006548 Permit Renewal Jun2019
Page 1
Outfall 002 monitoring (semiannually) explained as calc error due to sample timing, as
documented by ORC.
Table 2 -Parameters of Concern (POCs) Compliance Summary - Jan2016-Jun2019
Parameter
Units
Averages
Maximum
Minimum
Limit
Exceedance /
Count
Temperature Ef
°C
16.2
27
4
No / 874
Temperature U
°C
14.5
25
< 2
- / 177
Temperature (D)
°C
14.4
25
< 2
- / 178
Dissolved 02 Ef
m /L
8.5
11.5
6.3
No / 177
Dissolved 02
m /L
4.9
11.3
< 1
- / 178
Dissolved 02 D
m /L
5.0
11.6
<1
- / 177
Chlorine TRC
L
22.7
50
4.7
No / 362
BOD-5 summer
in /L
2.02
5
0.1
No / 100
BOD-5 winter
in /L
2.04
3.19
< 2
No / 77
Ammonia (summer)
in /L
0.15
5
0.01
No / 101
Ammonia (winter)
m /L
0.16
1.63
0.1
No / 77
Solids (TSS)
5.1
19.8
<5
No / 178
Fecal Coliform
n / 100 nil
16.5
2,420
< 1
2 / 178
TN
m /L
2.5
4.78
< 1
No / 14
TP
m /L
1 0.94
1 1.26
1 0.45
1 No / 14
Flow
MGD
1 0.0007
1 0.0012
1 0.0001
1 No / 185
WET -Testing and Instream Monitoring: This permit requires instream monitoring for
Temperature and Dissolved Oxygen upstream and downstream. Data is consistently similar at both
monitoring stations, and within water -quality standards. This permit does not require Whole
Effluent Toxicity (WET) testing - no permit changes recommended.
Renewal Change Summary: The Permittee has made no changes in processes or WWTP facilities
since last renewal. Monitoring and sampling include BOD-5 and Ammonia (summer / winter
limits consistent with similar Class -2 WWTPs) plus effluent and instream monitoring for
Dissolved Oxygen and Temperature. According to the renewal application, production volumes for
kiln drying are identical to those presented for the previous permit cycle - no permit changes
recommended.
Proposed Schedule for Issuance:
Draft Permit to Public Notice: June 26, 2019
Tentative Scheduled to Issue: August 9, 2019
NPDES Contact:
If you have questions regarding the above information or the attached permit, please contact
Joe R. Corporon P.G. Uoe.corporon@ncdenr.gov] or call his direct line 919-707-3617.
NAME:
DATE:
Fact Sheet
NPDES NC0006548 Permit Renewal Jun2019
Page 2
Joe Corporon
NOTE: data (hidden here)
indicate limit exceedences for
lance
COril lance
Comp
18Jun2O19
TRC (< 50 ug/L) --not
Jan2016-Jun2019
considered violations under
current TRC policy.
PERMIT
FACILITY
MONTH
YEAR
OUTFALL
PARAMETER
VIOL DATE
UNITS
LIMIT
CALC VAL
% OVER
VIOL TYPE
VIOL ACTION
VIOL COMMENT
UPDATED BY
NC0023604
Wilderness -NC Lumber Plant
3
2016
001
Temperature, Water Deg.
03/05/2016
deg c
Frequency Violation
No Action, BPJ
april.norton
Centigrade
NC0023604
Wilderness -NC Lumber Plant
10
2016
001
Temperature, Water Deg.
10/01/2016
deg c
Frequency Violation
No Action, Facility Rep,
will submit an amended DMR
april.norton
Centigrade
NC0023604
Wilderness -NC Lumber Plant
11
2017
001
Coliform, Fecal MF, MFC Broth,
11/29/2017
#/100ml
400
2420
505
Daily Maximum
Proceed to NOD
paul.dimatteo
44.5 C
Exceeded
NC0023604
Wilderness -NC Lumber Plant
1
2019
002
03/03/2019
Outfall Missing
None
bimsprod.cron
NC0023604
Wilderness -NC Lumber Plant
3
2019
002
05/01/2019
Outfall Missing
None
bimsprod.cron
No Action, BIMS
10/30/2018 PMD I spoke with the
Calculation Error
ORC, semiannual monitoring for
NC0023604
Wilderness -NC Lumber Plant
7
2018
002
08/31/2018
Outfall Missing
this outfall was conducted in April
paul.dimatteo
and will be done again this week.
No Action, Facility
12/14/18 PMD - semiannual
NC0023604
Wilderness -NC Lumber Plant
9
2018
002
10/31/2018
Outfall Missing
Reporting Error
monitoring @ outfall 002
paul.dimatteo
conducted in 10/18
NC0023604
Wilderness -NC Lumber Plant
1 11
1 2018
1 002
1
1 12/31/2018
1
1
1
1
1 Outfall Missing
None
I