HomeMy WebLinkAboutNC0061204_Compliance Evaluation Inspection_20190619ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPE .
Director
Thomas M. Alphin, Jr.
P.O. Box 5
Walkertown, NC 27051-0005
NORTH CAROLINA
Environmental Quality
June 20, 2019
SUBJECT: Compliance Evaluation Inspection
Scarlett Acres Mobile Home Park Wastewater Treatment Plant, NCO061204
Forsyth County
Dear Mr. Alphin:
Ron Boone, of the NC Division of Water Resources (DWR), Winston-Salem Regional Office,
visited the Scarlett Acres Mobile Home Park Wastewater Treatment Plant on June 6th, 2019. Your
assistance and cooperation during the inspection, as well as that of Mr. Randy Bell, Operator in
Responsible Charge, was greatly appreciated. Details of the inspection are detailed on the attached
EPA Water Compliance Inspection Report.
You're reminded that failure to comply with all conditions of the NCO061204 permit subject
you to civil penalties not to exceed $25,000.00 per violation, per day.
If you have any questions or require further assistance, please contact Mr. Boone by phone at
336-776-9690, or by email at ron.boone@ncdenr.gov. You may also contact me by phone at 336-776-
9700, or by email at lon.snider@ncdenr.gov.
Sincerely,
DocuSigned by:
OD2D3CE3F1 B7456_.
for Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
cc: NCDWR WSRO File
NCDWR Central Files
D E Q�p North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 Hanes Mill Road, Suite 300 1 Winston-Salem, North Carolina 27105
NORTH C. 0LINA
o•o•°^•mme""°""•"viu"•i� /� 336.776.9800
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO061204 111 12 I 19/06/06 I17 18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I 73 � 74 75I I I I I I I I80
u ty I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:OOAM 19/06/06
14/07/01
Scarlett Acres M H P WWTP
5528 Sherene Ln
Exit Time/Date
Permit Expiration Date
Walkertown NC 27051
11:00AM 19/06/06
19/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Randall Keith Bell/ORC/336-373-7514/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Thomas M Alphin,PO Box 5 Walkertown NC 270510005//336-655-8287/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone DocuSigned by: WSRO WQ//336-776-9690/
o*%,Z& Boone, 6/19/2019
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
6/19/201914.
"-OD2D3CE3F1B7456.-
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCO061204 I11 121 19/06/06 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
This plant is quite old and could use a lot of improvement, although the owner has done some work
recently, such as replacing the bar screen. A settleability test taken shortly before the inspection began
showed only about 200 mis within the first 30 minutes and then the sludge blanket rose to the top of the
container within the first 45 minutes. Although plant effluent monitoring records show minimal violations
over the past 18 months, and these settleability results only represent a single day, it may be prudent
for the operator and owner to take action to more finely tune the activated sludge process in this plant.
Page#
Permit: NCO061204 Owner -Facility: Scarlett Acres MHP WWTP
Inspection Date: 06/06/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
0
❑
❑
application?
Is the facility as described in the permit?
❑
0
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Plant description needs to be updated to reflect the effluent pump station and that the fixed
media is only in the northern most aeration basin.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
❑
Are DMRs complete: do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
0
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
0
❑
❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: APR not required, flow <200k GPD.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑
Page# 3
Permit: NCO061204 Owner -Facility: Scarlett Acres MHP WWTP
Inspection Date: 06/06/2019 Inspection Type: Compliance Evaluation
Laboratory
Yes No NA NE
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
❑
Comment: Did not inspect during sampling event. Did not inspect laboratory.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: No composite sampling required.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and 0 ❑ ❑ ❑
sampling location)?
Comment: None
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
❑
❑
❑
Is the wet well free of excessive grease?
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
❑
0
❑
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment: Influent pump station and EQ basin are one in the same. These is a lot of grease build
Page# 4
Permit: NCO061204
Inspection Date: 06/06/2019
Owner -Facility: Scarlett Acres MHP WWTP
Inspection Type: Compliance Evaluation
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Yes No NA NE
❑
■
❑
❑
■
❑
❑
❑
❑
■
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: Influent pump station and EQ basin are one in the same. These is a lot of -grease build up.
The influent pump station's/equalization basin's blower is inoperable. The owner and
operator say it is unnecessary to achieve sufficient treatment.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: Barscreen recently replaced along with flow splitter box.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
N ❑
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
0 ❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0 ❑
❑
❑
Comment: None
Page# 5
Permit: NC0061204 Owner -Facility:
Inspection Date: 06/06/2019 Inspection Type:
Scarlett Acres MHP WWTP
Compliance Evaluation
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
❑
❑
❑
Comment: None
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
❑
❑
0
❑
Comment: Sludge removal accomplished through air lift .
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment: None
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
0 ❑
❑
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
0 ❑
❑
❑
Page# 6
Permit: NCO061204 Owner -Facility: Scarlett Acres MHP WWTP
Inspection Date: 06/06/2019 Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Comment: None
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 2
Comment: None
Anaerobic Digester
Yes No NA NE
Type of operation:
No cover
Is the capacity adequate?
0
❑
❑
❑
# Is gas stored on site?
❑
❑
0
❑
Is the digester(s) free of tilting covers?
❑
❑
0
❑
Is the gas burner operational?
❑
❑
0
❑
Is the digester heated?
❑
0
❑
❑
Is the temperature maintained constantly?
❑0
❑
❑
Is tankage available for properly waste sludge?
❑
❑
❑
Comment: None
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Comment: Meter calibrated 6/3/2019.
Pump Station - Effluent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
❑
0
❑
❑
Is audible and visual alarm available and operational?
❑
0
❑
❑
Comment: Audible alarm is operational. Visual alarm is not.
Page# 7
Permit: NCO061204 Owner -Facility:
Inspection Date: 06/06/2019 Inspection Type:
Scarlett Acres MHP WWTP
Compliance Evaluation
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: None
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The aeration basin DO was 1.56 mql, according to the operator's meter during the
inspection. The settleability test read only about 200 after about 30 minutes and then rose to
the top a short time thereafter. It would be prudent for the operators to spend some time in
fine tuning the activated sludge process.
Page# 8