HomeMy WebLinkAboutNC0020664_Compliance Evaluation Inspection_20190619
June 19, 2019
Scott Webber, Town Manager
Town of Spindale
PO Box 186
Spindale, NC 28160
SUBJECT: Compliance Inspection Report
Spindale WWTP
NPDES WW Permit No. NC0020664
Rutherford County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Spindale WWTP on
6/11/2019. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0020664. Please specifically review any
findings and comments noted under the “summary” of the inspection report.
There were no significant issues noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me at 828-296-4500 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist I
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
EC: WQS Asheville Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
G:\WR\WQ\Rutherford\Wastewater\Municipal\Spindale WWTP 20664\Inspections\Inspect. June 11, 2019\20190619_NC0020664_CEI
DocuSign Envelope ID: 6956656F-5853-4588-A695-EEFDBBC2ABC9
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0020664 19/06/11 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Spindale WWTP
Ecology St
Spindale NC 28160
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
02:30PM 19/06/11 15/10/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Robert Eugene Lipscomb/ORC/828-286-3407/
Other Facility Data
04:40PM 19/06/11 18/07/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Robert Eugene Lipscomb,132 Wilkins St Forest City NC 28043//828-286-3407/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Mikal Willmer Division of Water Quality//828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 6956656F-5853-4588-A695-EEFDBBC2ABC9
6/19/2019
6/19/2019
NPDES yr/mo/day
19/06/11
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Inspector Mikal Willmer, with the Asheville Regional Office, conducted a compliance evaluation
inspection of the Spindale WWTP on June 11, 2019. This inspection was conducted to determine
whether the facility is being operated and maintained in compliance with NPDES Permit No.
NC0020664. Robert Lipscomb, back-up ORC, was present and assisted in the inspection.
Overall the facility is being well operated and maintained. Spindale's WWTP has been undergoing
upgrades for over a year and the new basins were recently placed into service. The last few upgrades
are currently being finalized (EQ basin mixers, pumps and wiring). Mr. Lipscomb reports the influent
composite sampler will be replaced soon due to issues with the old sampler. DMRs since the last
inspection in 2017 were reviewed for any violations. No recurring violations or issues noted during the
review. Some monitoring and one limit violation due to flow changes during construction.
It was noted, at the time of the inspection, the new basins appear to have "dead" spots along the
sloped edge. Debris collects along this side and has to be skimmed off by the operators. Currently this
does not appear to be affecting treatment. There appears to be adequate mixing and aeration by the
fine-bubble diffusers. The DO meters in the basin were reading from 0.8 to 2 mg/L. Operators are
slowly regaining a healthy biota within the facility. Some floating solids were noted in the clarifiers, but
did not appear to be flowing over the weir.
Mr. Lipscomb states the effluent sampler was set to flow proportional by their calibration company.
Recommend Spindale staff go over the process for setting the sampler to flow proportional with the
calibration firm during their next visit.
As a reminder, Spindale should continue to actively seek a Grade IV ORC replacement. Currently the
only full-time Spindale operational staff are a Grade III and Grade I.
NC0020664 17 (Cont.)
Page#2
DocuSign Envelope ID: 6956656F-5853-4588-A695-EEFDBBC2ABC9
Permit:NC0020664
Inspection Date:06/11/2019
Owner - Facility:
Inspection Type:
Spindale WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Facility staff monitor DO, pH, chlorine residual and utilize a sludge judge as part of their
process control.
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Spindale's permit expired July 31, 2018. The renewal application was submitted on January
26, 2018. The Permit is currently under review in central office. Facility is in the process of
finalizing upgrades. Upgrades were added to the permit in 2015. Facility was required to
develop a mercury minimization plan within 180 days of the previous permit issuance.
Comment:
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Influent flow meter was reading approximately 1 MGD at the time of the inspection. The
influent flow meter is used for permit compliance.
Comment:
Influent Sampling Yes No NA NE
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is sampling performed according to the permit?
Mr. Lipscomb indicated a new composite sampler would be installed at the headworks.
Influent sampling is time composite.
Comment:
Page#3
DocuSign Envelope ID: 6956656F-5853-4588-A695-EEFDBBC2ABC9
Permit:NC0020664
Inspection Date:06/11/2019
Owner - Facility:
Inspection Type:
Spindale WWTP
Compliance Evaluation
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Grit removal system was upgraded and appears to handle increased flows better than the
previous system.
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
EQ basin was recently used during heavy rains; however, the basin's aerators and pumps
are in the process of being wired. EQ basin equipment is not fully operational, but will be
soon.
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Page#4
DocuSign Envelope ID: 6956656F-5853-4588-A695-EEFDBBC2ABC9
Permit:NC0020664
Inspection Date:06/11/2019
Owner - Facility:
Inspection Type:
Spindale WWTP
Compliance Evaluation
Aeration Basins Yes No NA NE
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Currently only Basin 2 is in use. Diffusers appear to be operating properly and DOs appear
adequate for the treatment process (0.8 to 2.3 mg/L). There were dead spots noted along
the far wall due to the sloped sides. There is stagnation and collection of pass-through
debris which the operators skim off. It currently does not appear to be adversely affecting
treatment.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Clarifiers 1&2 are in operation. Number 3 clarifier is not currently in use. ORC reports there
are very little solids in the facility and they are slowly reestablishing biology. Sludge blankets
are only a foot in either clarifier. Some floating solids were noted in the clarifier, but did not
appear to be flowing over the weir.
Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
Page#5
DocuSign Envelope ID: 6956656F-5853-4588-A695-EEFDBBC2ABC9
Permit:NC0020664
Inspection Date:06/11/2019
Owner - Facility:
Inspection Type:
Spindale WWTP
Compliance Evaluation
Aerobic Digester Yes No NA NE
# Is tankage available for properly waste sludge?
Spindale holds a Class B land application permit (WQ0001953) and contracts Southern Soil
Builders for land application events. There appears to be adequate storage to properly waste
when needed. Facility staff indicated they currently do not have high enough sludge blankets
to waste.
Comment:
Disinfection-Gas Yes No NA NE
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-____-____)
If yes, then when was the RMP last updated?
Chlorine gas is used on-site. Spindale may eventually move to another means of
disinfection. Mr. Lipscomb reports they test residuals prior to dechlorination. No issues
reported.
Comment:
De-chlorination Yes No NA NE
Type of system ?Gas
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Manual feed system currently. Spindale is looking to change this to flow proportional. Facility
has not had issues maintaining adequate chlorine feed for disinfection.
Comment:
Are tablet de-chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Page#6
DocuSign Envelope ID: 6956656F-5853-4588-A695-EEFDBBC2ABC9
Permit:NC0020664
Inspection Date:06/11/2019
Owner - Facility:
Inspection Type:
Spindale WWTP
Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Spindale reports influent flow measurements. New effluent meter was calibrated by
manufacturer and recently installed as part of the upgrades.
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Sampling is occurring as required by permit. Composite sampling is flow proportional.
Calibration company programs the auto-sampler. Recommend facility staff go through the
programing with the company during the next calibration.
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and
sampling location)?
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
New generator tests automatically and is maintained by camp electric.Comment:
Page#7
DocuSign Envelope ID: 6956656F-5853-4588-A695-EEFDBBC2ABC9
Certificate Of Completion
Envelope Id: 6956656F58534588A695EEFDBBC2ABC9 Status: Completed
Subject: Please DocuSign: 20190619_NC0020664_CEI.ltr.docx, 20190619_NC0020664_CEI.pdf
Source Envelope:
Document Pages: 8 Signatures: 3 Envelope Originator:
Certificate Pages: 2 Initials: 0 Mikal Willmer
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-05:00) Eastern Time (US & Canada)
217 W. Jones Street
Raleigh, NC 27699
Mikal.willmer@ncdenr.gov
IP Address: 149.168.204.10
Record Tracking
Status: Original
Jun 19, 2019 | 09:45
Holder: Mikal Willmer
Mikal.willmer@ncdenr.gov
Location: DocuSign
Signer Events Signature Timestamp
Mikal Willmer
mikal.willmer@ncdenr.gov
Environmental Specialist
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 149.168.204.10
Sent: Jun 19, 2019 | 09:46
Viewed: Jun 19, 2019 | 09:46
Signed: Jun 19, 2019 | 09:46
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
G. Landon Davidson
landon.davidson@ncdenr.gov
Asheville Regional Office, Regional Supervisor
DEQ, Division of Water Resources, Water Quality
Regional Operatoins
Security Level: Email, Account Authentication
(None)
Signature Adoption: Uploaded Signature Image
Using IP Address: 149.168.204.10
Sent: Jun 19, 2019 | 09:46
Resent: Jun 19, 2019 | 14:39
Viewed: Jun 19, 2019 | 14:42
Signed: Jun 19, 2019 | 14:42
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted Jun 19, 2019 | 14:39
Certified Delivered Security Checked Jun 19, 2019 | 14:42
Signing Complete Security Checked Jun 19, 2019 | 14:42
Envelope Summary Events Status Timestamps
Completed Security Checked Jun 19, 2019 | 14:42
Payment Events Status Timestamps