United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0024431 19/05/29 J S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Kanuga Conferences WWTP
Kanuga Conference Dr
Hendersonville NC 28793
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:00AM 19/05/29 15/12/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
11:00AM 19/05/29 20/11/30
Name, Address of Responsible Official/Title/Phone and Fax Number
Richard David Varnadore,PO Box 250 Hendersonvlle NC 287930250//828-692-9136/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance Self-Monitoring Program Facility Site Review
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Daniel J Boss ARO WQ//828-296-4658/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: A605A4F0-F135-4A9D-A0DC-B9B914E9BA12
6/14/2019
6/14/2019
NPDES yr/mo/day
19/05/29
Inspection Type
J3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
I met with Dwayne Owens and Glenn Griffith for an complaint investigation and follow up inspection of
the Kanuga Conferences WWTP on May 29, 2019. Ricky Varnadore, the former ORC had resigned
his post just days prior to this inspection.
Neither Mr. Owens or Mr. Griffith have any wastewater certifications at the moment, so I advised them
to seek a contract operator to be ORC of the facility until one of them can acquire a WW-1 license.
There is water emerging from a slope between the upper and lower sand filter beds. According to Mr.
Griffith, the water has been tested and determined to be a natural spring. I asked them to retest the
emerging water for fecal coliform, BOD, and ammonia, and to send me the lab reports.
The sampling conducted at the facility is still all grab sampling despite the permit requirement that
BOD, TSS, and ammonia all be composite sampled. This needs to be addressed and will probably
require the installation of a new flow meter as well as a sampler.
NC0024431 17 (Cont.)
Page#2
DocuSign Envelope ID: A605A4F0-F135-4A9D-A0DC-B9B914E9BA12
Permit:NC0024431
Inspection Date:05/29/2019
Owner - Facility:
Inspection Type:
Kanuga Conferences WWTP
Complaint
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment:
Sand Filters (Low rate)Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re-circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1)
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Page#3
DocuSign Envelope ID: A605A4F0-F135-4A9D-A0DC-B9B914E9BA12
Permit:NC0024431
Inspection Date:05/29/2019
Owner - Facility:
Inspection Type:
Kanuga Conferences WWTP
Complaint
Disinfection-Tablet Yes No NA NE
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Composite sampling is still not being performed.Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Page#4