HomeMy WebLinkAboutNC0070289_Compliance Evaluation Inspection_20190531United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCO070289 111 12 I 19/05/21 I17 18 I S I 19 I G I 201 I
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70 I g 71 I tyI 72 I r I 73 I I 174 751 I I I I I I I80
uI I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:02AM 19/05/21
14/02/01
Ridgewood Farms Subdivision
Olde Creek Trl
Exit Time/Date
Permit Expiration Date
Concord NC 28025
11:31AM 19/05/21
18/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Braden Joshua Cook/ORC/704-788-4164/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Braden Joshua Cook,7000 Stinson Hartis Rd Indian Trail NC
28079/ORC/980-202-2377/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Compliance Schedules
Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Roberto Scheller S�Ge,/r!ati MRO WQ//252-946-6481/ 6/5/2019
91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger Division of Water Quality//704-2'
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
' 6/5/2019
AlaccsalAFvazs... Page#
NPDES yr/mo/day Inspection Type
NCO070289 I11 121 19/05/21 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
- As of the date of this inspection the Division has not received a complete renewal permit application.
- Diffusers in aeration basin require repair or replacement.
- Bulkhead between aeration basin and sludge holding tank requires repairs.
- Holes rusted through treatment unit require repairs.
- Facility has two (2) outstanding civil penalties LV-2019-0309 and LV-2019-0325.
Page#
Permit: NCO070289 Owner - Facility: Ridgewood Farms Subdivision
Inspection Date: 05/21/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Facility is operating under permit that expired on November 30, 2018. A complete permit
renewal application has not been submitted.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
M
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
0
❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: All records reviewed were current and available for review.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑
Page# 3
Permit: NCO070289 Owner - Facility: Ridgewood Farms Subdivision
Inspection Date: 05/21/2019 Inspection Type: Compliance Evaluation
Laboratory
Yes No NA NE
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Field Darameters are conducted under Field Certification #5695. K&W Laboratories
(Certification #559) is used as the contract lab.
Compliance Schedules Yes No NA NE
Is there a compliance schedule for this facility? ❑ ❑ E ❑
Is the facility compliant with the permit and conditions for the review period? ❑ 0 ❑ ❑
Comment: Review of compliance history from April 2018 throuah March 2019 show three (3) Notice of
Violations issued for the subject facility: 4/2018 NOV-2018-LV-0633, 10/2018
NOV-2018-LV-0861, 11/2018 NOV-2019-LV-0021
Review of compliance history also found two civil penaltys issued to subject facility; Case
Number LV-2017-0309 issued on November 3, 2017 for the amount of $453.62 and Case
Number LV-2017-0325 issued on November 28, 2017 for the amount of $703.62. Both of the
civil penalties remain unpaid.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Is the basin free of dead spots?
E ❑
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
❑ ❑
0
❑
Page# 4
Permit: NCO070289
Inspection Date: 05/21/2019
Owner - Facility: Ridgewood Farms Subdivision
Inspection Type: Compliance Evaluation
Aeration Basins
Yes No NA NE
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Comment: Diffusers should be repaired or replaced in aeration basin.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
❑
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
❑
❑
❑
Comment: Scum baffle should be cleaned out.
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ 0 ❑
Is storage appropriate for cylinders? ❑ ❑ 0 ❑
Page# 5
Permit: NCO070289 Owner - Facility: Ridgewood Farms Subdivision
Inspection Date: 05/21/2019 Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
# Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 4
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Comment:
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: At time of inspection sample storage was recorded at 4 degrees Celsius.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
0
❑
❑
❑
Comment: At time of inspection effluent was clear with few visible suspended soids.
Aerobic Digester Yes No NA NE
Is the capacity adequate? ❑ ❑ 0 ❑
Is the mixing adequate? ❑ ❑ 0 ❑
Page# 6
Permit: NCO070289
Owner - Facility: Ridgewood Farms Subdivision
Inspection Date: 05/21/2019
Inspection Type: Compliance Evaluation
Aerobic Digester
Yes No NA NE
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
❑
N
❑
❑
Comment: TOD of bulkhead between diaester and aeration basin has rusted out and bulkhead ma
collapse if digester is pumped out. Rusted out holes in bulkhead makes it ineffective to
waste and dewater sludge at this facility. Holes rusted through end of treatment unit allows
waste to exit treatment unit via holes during high flow. Rusted out holes in treatment plant
that allows untreated wastewater to excape is considered a by-pass of treatment and a
violation of your NPDES permit.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: At time of inspection facility appeared to be well operated. It was noted that rusted out holes
in treatment plant and issues with diffusers in areation basin hamper plant performance and
the ability of operator to effectively and efficiently operate WWTP at peak performance.
Page# 7
ROY COOPED
66 filar
K41CHAEL S. R.EGAN
Secretary
LINDA CULPEPPER
Cb7{CfiOr
NORTH CAROUNA
Environmental Qual"
Certified Mail # 7017 2620 0000 6788 5702
Return Receipt Reauested
June 05, 2019
Mr. Wayne Huntley
Stones Throw Homeowners Association
Post Office Box 690725
Charlotte, NC 28227
SUBJECT: Compliance Inspection Report
Ridgewood Farms Subdivision
NPDES WW Permit No. NCO070289
Cabarrus County
Dear Mr. Huntly:
The North Carolina Division of Water Resources conducted an inspection of the Ridgewood Farms
Subdivision on May 21, 2019. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0070289. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
Please respond in writing to this office within 30 days of your receipt of this letter regarding your plans
or measures to be taken to address the following issues:
• As of the date of the subject inspection, the Division has not received a complete permit renewal application.
• Diffusers in aeration basin require repair or replacement.
• Bulkhead between aeration basin and sludge holding tank requires repairs.
• Holes rusted through treatment unit allowing wastewater to by-pass treatment require repairs.
• Facility has two (2) outstanding civil penalties LV-2017-0309 and LV-2019-0325. This Office should be
contacted as soon as possible regarding these civil penalties.
NorthCaro I,na6epartmentofErv:rar.merts'Qua: ;tw I MrsanofWater Resources
Woo reav:15ERegom:Off.-oe 1510 Ea2l,enterAvenue, Se;te3011 Mooresv �e,North 03rodina2S115
If you should have any questions, please do not hesitate to contact Roberto Scheller with the Water
Quality Regional Operations Section in the Mooresville Regional Office at 704-663-1699 or via email at
roberto.scheller@ncdenr.gov.
Sincerely,
DocuSigned by:
A14CCWAF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Mooresville Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
Laserfiche
No rth Carolina Department of E nvuon iaents! Quairty I Dimsion of Water Resources
D—E Mooresvlle Regbfm! Office 1 610 Es3 Center Avenue, Suite 301 I Mooresvit, North Carcdina 2S115
�L f •'—!F 7fA-6 3-168f}