HomeMy WebLinkAboutNCG510535_Compliance Evaluation Inspection_20190607ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mr. Brad Schroeder (via email)
YRC Trucking
1077 George Boulevard
Suite B-471
Akron, Ohio 44310-2408
Dear Mr. Schroeder:
NORTH CAROLINA
Environmental Quality
June 7, 2019
Subject: Compliance Evaluation Inspection
YRC Trucking Terminal
NPDES Permit NCG510535
Groundwater Remediation
Charlotte, Mecklenburg County
On May 30, 2019, staff from the Mooresville Regional Office (MRO) performed a compliance
inspection of the Groundwater Remediation system at the subject site to determine compliance
with the permit.
Enclosed is a copy of the inspection report. Please see the MRO suggestions for on maintenance
in the inspection report.
The system is online and performing at levels consist with the permit for this facility.
Should you have any questions with the site inspection report or the findings list herein, I may be
reached by phone at (704) 663-1699 or by email at edward.watson@ncdenr.gov, should you
have questions.
Sincerely,
EA
DocuSigned by:
w N p4ff .
F161 F669A2D84A3...
Andrew H. Pitner, P.G.
Assistant Regional Supervisor
Mooresville Regional Office
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Attachment: Compliance Inspection Report
CC: DWR Files (Laserfiche)
D Q
� North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOAn-icJwauNn i
nwm,em of eem—woviRv 704,663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCG510535 111 12 I 19/05/30 I17 18 I S J 19 L G] 201 I
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
1.0 70 71 [„ I 72 n 73 L_LJ74 751
u I I I I I I I80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:OOAM 19/05/30
16/11/03
YRC Trucking Terminal
11010 Reames Rd
Exit Time/Date
Permit Expiration Date
Charlotte NC 28269
12:30PM 19/05/30
20/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Chris Masoner,10990 Roe Ave Ms-A650 Overland Park KS 66211//913-696-9192/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance Records/Reports Self -Monitoring Program
Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Edward Watson MRO GW///
Docusigned by: Agency/Office/Phone and Fax Numbers Date
Signature of Management Q A Reviewe[A*-.uw
N P44
6.7.19
F161F969A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCG510535 I11 121 19/05/30 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On May 30, 2019, MRO staff conducted a compliance inspection of the YRC Trucking groundwater
remediation system operating under permit NCG510535. MRO staff met with Mr. Matt Westendorf.
During the inspection, RW-1 was experiencing problems with a blocked line. This blockage may be the
result of a damaged stinger. A repair of the stinger in RW-1 was being performed after the site visit
was completed. Please notify this office to alert us that the repair has been successfully completed.
The effluent meter calibration records were reviewed during the site visit. The calibration appears to be
within the allowable error for the flow meter.
The gallery at RW-2 was observed to be flooded. MRO suggests that a mat could be used as a cover
to prevent flooding of the gallery so the wash fluid does not accidentally get pumped through the
treatment system.
It was also observed that the fiberglass coating of the Activated Carbon canister has become
compromised. The MRO suggested the Carbon Canisters be replaced as a part of regular system
maintenance.
The treatment system has an oil and water separator that discharges free product to a 55-gallon drum.
During the date of the inspection, no free product was in the 55-gallon drum.
The ORC has pH field certification. The pH certification paperwork was available for review. All other
procedures are performed by a contract laboratory.
Overall, the treatment system is operating within the guidelines of the NPDES permit.
Please notify the MRO, DWR should you be contacted by the Trust Fund to turn-off this treatment
system.
Page#
Permit: NCG510535 Owner - Facility: YRC Trucking Terminal
Inspection Date: 05/30/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
0
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The current permit was present during the inspection. This permit is scheduled to renew at
the end of September 2020.
Please be sure to submit the renewal application 180 days prior to the permit expiration
date.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: O&M records were available for review durina the site visit. The records aDDear to be
complete and up-to-date.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: Due to the low amount of water in the post -treatment collection tank, the flow was not
observed during the site visit. However, the effluent sample port
was used to view the
treatment water. The sample collected from the effluent sample
port was clear, free of
solids, odor, and foam.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: A review of the laboratory analytical data indicates the treatment system is effectively
treating the plume. Effluent discharge reports no elevated 2L constituents.
Page# 3
Permit: NCG510535
Inspection Date: 05/30/2019
Owner - Facility: YRC Trucking Terminal