Subject: Compliance Evaluation Inspection
Louisburg Collection System
WWCS Permit WQCS00113
Franklin County
Dear Mayor Pernell:
On May 14, 20I9, Vanessa Manuel from the Raleigh Regional Office conducted an inspection of
the town's wastewater collection system to evaluate compliance with the operation and
maintenance of the subject wastewater collection system permit. The cooperation and assistance
of Ray Patterson, Carlton Tabron, Mike Ayscue, Jr., and Daniel Nobles during the inspection
were greatly appreciated.
Our records indicate the wastewater collection system is classified as a Grade II collection
system and consists of approximately 35 miles of gravity sewer, approximately 24 miles of force
main, 7 duplex pump stations, and b high priority sewer lines.
The subject permit is effective from February 9, 2018 until September 30, 2024, and is subject to
specific conditions and limitations. The items below show what conditions were noted during
the inspection:
1. Reported Sanitary Sewer Overflows. During the 2-year period ending April 30, 2019,
there were no reported SSOs from the town's wastewater collection system.
2. Fats, Oils and Grease Program. The Town of Louisburg, hereinafter referred to as the
Town, has developed and implements an educational fats, oils and grease (FOG)
program. Mr. Patterson stated educational material about the Town's FOG program is
located on the Town's website. Within 45-days of receiving this letter, please provide a
written response to this office with the website address where the FOG educational
material is located and state how the Town meets the requirement within Section L4 of
the subject permit of distributing educational material to residential and non-
residential users at least semi-annually.
3. Capital Improvement Plan. The Town has adopted and implements a Capital
Improvement Plan to designate funding for reinvestment into the wastewater collection
North Carolina Department of Environmental Quality I Division of Water Resources
•�yi Raleigh Regional Office i 3800 Barrett Drive Raleigh, North Carolina 27609
919.7914200
Town of Louisburg, WQCSOO1 13
June 7, 2019
system infrastructure. The CIP covers fiscal years 2018-2023, includes a goal statement,
description of the project area, description of the existing facilities, known deficiencies
and forecasted future needs. The annual budget for the collection system is $426,717.
4. Pump Stations Inspected. The Town's 7 duplex pump stations listed in the subject
permit were inspected. The inspector's observations noted in the next 5 items refer to the
pump stations inspected. Overall, the pump stations were well maintained. The wet
wells were free of excessive debris and grease, and the inspector did not observe any
signs of recent sewer overflow.
5. Pump Station Signage. Each pump station has signage clearly and conspicuously posted
that identifies the pump station, provides an emergency 24-hour contact telephone
number(s), and provides instructions for notification if the visual alarm illuminates and/or
the audible alarm sounds, or if an emergency is apparent.
6. Pump Station Restricted Access. The pump station sites, equipment and components
were observed to have restricted access.
7. Pump Stations Automatic Polling Feature. Each pump station is equipped with a
Supervisory Control and Data Acquisition (SCADA) system that allows the Town routine
contact with the pump station from a central location to check the operational status of
the communication system. When the high-water alarm was checked at the lift stations,
the SCADA system functioned as required except at the Horseshoe Lift Station. The
inspector observed smoke coming from the SCADA control panel after the high water
alarm was activated at the Horseshoe Lift Station. In response to the smoke, the operator
turned the breaker off. The operator stated he has experienced a few mal-functions with
the SCADA system at the Horseshoe Lift Station. In addition, he stated the SCADA
system does not always call out in response to a trigger event (ex., power loss, high water
alarm, etc.) due to the age of the system and the remote location, which can interfere with
transmissions. Within 45-days of receiving this letter, please update this office
regarding the status of the SCADA system at tl►e Horseshoe Lift Station and the
actions the Town will take to ensure the SCADA system functions as required.
8. Pump Station High Water Alarms. The pump stations are equipped with audible and
visual high water alarms. During the inspection, these alarms functioned properly.
9. Pump Station Inspection Program. The Town has developed and implements a routine
inspection of each pump station that includes the following maintenance activities:
cleaning and removing debris from the pump station area and wet well; inspecting all
valves; inspecting pumps and other mechanical equipment; and verifying the proper
operation of the alarms, SCADA system and auxiliary equipment. The inspector
reviewed the inspection logs and observed adequate entries of the date and time of the
operator's inspection, observations made, and any maintenance, repairs, or corrective
actions taken.
10. Designated Operators. The Town's wastewater collection system is classified as a
Grade 11 collection system, and the designated certified Operator in Responsible Charge
(ORC) and back-up ORC on record are Carlton Tabron and Ray Patterson, respectively.
2 of
Town of Louisburg, WQCS001 13
June 7, 2019
The certification status for each operator is reflected as active in the Division's data
system.
11. Cleaning Sewer Lines. The Town has developed and implements a program for cleaning
the sewer lines. As required by Section I1.8 of the subject permit, at least 10% of the
wastewater collection system should be cleaned each year. Preventative cleaning is not
required for sewer lines less than five years old, unless an inspection reveals the need for
cleaning. The collection system operator provided maintenance records showing 23,070
linear feet (4.37 miles) of sewer line was cleaned during calendar year 2018.
12. Spill Response Action Plan. The Town has developed and maintains a Spill Response
Action Plan that includes 24-hour contact numbers, response time, equipment list and
spare parts inventory, access to cleaning equipment, access to construction crews, site
sanitation and cleanup materials, and post-SSO assessment.
13. Comprehensive Sewer Map. The Town maintains an comprehensive electronic map of
its sewer collection system. The map includes pipe size, pipe material, pipe location,
flow direction, number of active service taps, and each pump station identification,
location and capacity.
14. Inspection of High Priority Lines. As required by Section VA of the subject permit, an
inspection of all high priority sewer lines shall be performed at least once every six -
months. The collection system operators inspect the lines and clean the siphons monthly.
The last HPL inspections were conducted during March and April 2019. During the
subject state inspection, the following high priority lines were inspected: Prison Pump
Station aerial line; Sunrise Biscuit aerial line; Tar River Siphon Bickett Blvd.; and Tar
River Siphon South Main Street. No compliance issues with the high priority lines were
observed.
Within 45-days of receiving this letter, please provide this office with a response to items 2
and 7 above. If you have questions or comments about this inspection or the requirements to
take corrective action if applicable, please contact Vanessa Manuel at 919-7914255.
Sincerely,
Rick Bolich, L.G., Assistant Supervisor
Water Quality Regional Supervisor
Raleigh Regional Office
Attachment(s): Collection System Inspection Report
Cc: RRO;`SWP Files
Laserfiche
3 of
Compliance Inspection Report
Permit: WQCS00113 Effective: 02/09/18 Expiration: 09/30/24 Owner: Town of Louisburg
SOC: Effective: Expiration: Facility: Louisburg Collection System
County: Franklin 110 W Nash St
Region: Raleigh
Louisburg NC 276492526
Contact Person: Jonathan Franklin Title: Town Administrator Phone: 919496-3406
Directions to Facility:
System Classifications: CS2,
Primary ORC: Carlton Earl Tabron Certification: 16193 Phone: 919-496-3406
Secondary ORC(s):
Thomas Ray Patterson 986886 919-496-3406
On -Site Representative(s):
Related Permits:
NCO020231 Town of Louisburg - Tar River Water Reclamation Facility WWTP
Inspection Date: 05/14/2019 Entry Time: 09.30AM Exit Time: 02 45PM
Primary Inspector: Vanessa E Manuel -1ti�'. Phone: A1& 6E-59�
Secondary Inspectors): 9Q
/ 9" � //- 4/7 5-
Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Collection system management and operation
Facility Status: Compliant Not Compliant
Question Areas:
Miscellaneous Questions Performance Standards Operation & Maint Reqmts
Records Monitoring & Rpting Regmts Inspections
Pump Station Lines
(Set: attachment summary)
Page 1 of 15
permit: WOCS0011 3 Owner - Facility: Town of Louisburg
Inspection Date: 05114/2019 Inspection Type: Collection System Inspect Nan Sampling Reason for Visit Routine
Inspection Summary:
See attached inspection report.
Page 2 of 15
Permit: WOCS00113 Owner - Facility: Town of Louisburg
Inspection Data: 05114/2019 Inspection Type: Collection System Inspect Non Sampling Reason for Visit Routine
Perfortnance Standards
Yes No NA NE
Is Public Education Program for grease established and documented?
What educational tools are used?
The Assistant Town Administrator of Operations slated FOG information is provided on the town's website,
Is Sewer Use Ordinance/Legal Authority available?
Does it appear that the Sewer Use Ordinance is enforced?
M ❑ El F1
Is Grease Trap Ordinance available?
0 El 0 ❑
Is Septic Tank Ordinance available (as applicable, i.e. annexation)
List enforcement actions by permittee, if any, in the last 12 months
Has an acceptable Capital Improvement Plan (CIP) been implemented?
0 ❑ El El
Does CIP address short term needs and long term Vmaster plant" concepts?
Does CIP cover three to five year period?
Does CIP include Goal Statement?
Does CIP include description of project area?
0 El El
Does CIP include description of existing facilities?
M
Does CIP include known deficiencies?
M El El 11
Does CIP include forecasted future needs?
Is CIP designated only for wastewater collection and treatment?
❑
Approximate capital improvement budget for collection system?
$1 158 230.ao
Total annual revenue for wastewater collection and treatment?
CIP Comments
Is system free of known points of bypass?
If no, describe type of bypass and location
Is a 24-hour notification sign posted at ALL pump stations?
M ❑ ❑
# Does the sign include:
Instructions for notification?
Pump station identifier?
24-hour contact numbers
If no, list deficient pump stations
# Do ALL pump stations have an "auto poling' feature/SCADA?
Number of pump stations
7
Number of pump stations that have SCADA
7
Number of pump stations that have simple telemetry
0
Number of pump stations that have only audible and visual alarms
0
Number of pump stations that do not meet permit requirements
0
# Does the permittee have a root control program?
Page 3 of 15
permit: WrOCS00113 owner - Facility: Town of Louisburg
Inspection Date: 05/14/2019 Inspection Typo: Collection System Inspect Non Sampling Reason for Visit: Roubne
# If yes, date implemented?
Describe:
Comment:
Inspections Yes No NA NE
Are maintenance records for sewer lines available? 0 ❑ ❑ ❑
Are records available that document pump station inspections? 0 ❑ ❑ ❑
Are SCADA or telemetry equipped pump stations inspected at least once a week? 0 ❑ ❑ ❑
Are non-SCADAItelemetry equipped pump stations inspected every day? ❑ ❑ N ❑
Are records available that document citizen complaints? ❑ ❑ ❑
# Do you have a system to conduct an annual observation of entire system? ❑ ❑ ❑
# Has there been an observation of remote areas in the last year? 0 ❑ ❑ ❑
Are records available that document inspections of high -priority lines? E ❑ ❑ ❑
Has there been visual inspections of high -priority lines in last six months? 0 ❑ ❑ ❑
Comment:
Operation & Maintenance Reguirements
Yes No_NANZ
Are all log books available?
E 11110
Does supervisor review all log books on a regular basis?
0 ❑ ❑ ❑
Does the supervisor have plans to address documented short-term problem areas?
N ❑ ❑ ❑
What is the schedule for reviewing inspection, maintenance, & operations logs and problem areas?
Are maintenance records for equipment available?
❑ ❑ ❑ E
Is a schedule maintained for testing emergency/standby equipment?
M000
What is the schedule for testing emergencylstandby equipment?
Monthly
Do pump station logs include:
Inside and outside cleaning and debris removal?
N ❑ ❑ ❑
Inspecting and exercising all valves?
E ❑ ❑ ❑
Inspecting and lubricating pumps and other equipment?
N ❑ ❑ ❑
Inspecting alarms, telemetry and auxiliary equipment?
E ❑ ❑ ❑
Is there at least one spare pump for each pump station w/o pump reliability?
❑ ❑ 0 ❑
Are maintenance records for right-of-ways available?
❑ ❑ ❑
Are right-of-ways currently accessible in the event of an emergency?
E ❑ ❑ ❑
Are system cleaning records available?
0 ❑ ❑ ❑
Has at least 10% of system been cleaned annually?
E ❑ ❑ ❑
What areas are scheduled for cleaning in the next 12 months?
Is a Spill Response Action Plan available?
0 ❑ ❑ ❑
Does the plan include
24-hour contact numbers
0 ❑ ❑ ❑
Page 4 of 15
permit: WOCSO0113 Owner - Facility: Town or Louisburg
Inspection Date: 05/14/2019 Inspection Type: Collection System Inspect Non Sampling Reason for Visit- Routine
Response time ■ ❑ Cl ❑
Equipment list and spare parts inventory 0❑ ❑
Access to cleaning equipment M❑ ❑ ❑
Access to construction crews, contractors, and/or engineers M ❑ ❑ ❑
Source of emergency funds El❑ ❑
Site sanitation and cleanup materials
Post-overflow/spill assessment 0 El El F1
Is a Spill Response Action Plan available for all personnel?
Is the spare parts inventory adequate?
Comment:
Records
Yes N,Q NA NE
Are adequate records of all SSOS, spills and complaints available? M❑ Elm
Are records of SSOs that are under the reportable threshold available? ❑ El M ❑
Do spill records indicate repeated overflows (2 or more in 12 months) at same location? ❑ ❑ 0 ❑
1f yes, is there a corrective action plan? 0 1:111
Is a map of the system available?
Does the map Include
Pipe sizes
M 1:1 El El
Pipe materials
■
Pipe location
Flow direction
Approximate pipe age
Number of service taps
Pump stations and capacity
0❑ ❑
If no, what percent is complete?
List any modifications and extensions that need to be added to the map
# Does the permittee have a copy of their permit? M ❑ ❑ ❑
Comment:
Monitoring and Reporting Requirements
Yes No NA NE
Are copies of required press releases and distribution lists available? M ❑
Are public notices and proof of publication available? ❑ ❑ ■ El
# Is an annual report being prepared in accordance with G.S. 143-215.iC? ❑ ❑ ❑ ❑
# Is permittee compliant with all compliance schedules in the permits? 11 El 0 El
If no, which one(s)?
Comment:
GREENHILL L. S. -
Page 5 of 15
permit: WQCS00113 Owner - Facility: Town of Louisburg
Inspection Date: 05114/2019 Inspection Type: Collection System Inspect Non Sampl ng
Reason for Visit Routine
Pump Station
Yes No NA NE
Pump station type
Duplex
Are pump station logs available?
0 ❑ ❑ ❑
Is it accessible in all weather conditions?
M ❑ ❑ ❑
# Is general housekeeping acceptable?
M ❑ ❑ ❑
Are all pumps present?
0 ❑ ❑ ❑
Are all pumps operable?
0 ❑ ❑ ❑
Are wet wells free of excessive debris?
0 ❑ ❑ ❑
Are upstream manholes free of excessive debristsigns of overflow?
❑ ❑ ❑
Are floats/controls for pumpslalarms operable?
❑ ❑ ❑
Is "auto polling" featurelSCADA present?
M ❑ ❑ ❑
Is "auto polling" featurelSCADA operational?
M ❑ ❑ ❑
Is simple telemetry present?
❑ ❑ M ❑
Is simple telemetry operational?
❑ ❑ 0 ❑
Are audio and visual alarms present?
0 ❑ ❑ ❑
Are audio and visual alarms operable?
M ❑ ❑ ❑
Is the Pump station inspected as required?
0 ❑ ❑ ❑
Are backflow devices in place?
❑ ❑ ❑ M
Are backflow devices operable?
❑ ❑ ❑ M
Are air relief valves in place?
❑ ❑ ❑ 0
Are air relief valves operable?
❑ ❑ ❑ 0
# Is an emergency generator available?
❑ 0 ❑ ❑
Can the emergency generator run the pumps?
❑ ❑ ❑
Is the pump station equipped for quick hoots -up?
❑ M ❑ ❑
Is the generator operable?
❑ ❑ 0 ❑
# Is fuel in tank and sufficient?
❑ ❑ M ❑
Is the generator inspected according to their schedule?
❑ ❑ M ❑
Is a 24-hour notification sign posted?
0 ❑ ❑ ❑
Does it include:
Instructions for notification?
0 ❑ ❑ ❑
Pump station identifier?
❑ ❑ ❑
Emergency phone number
❑ ❑ ❑
Is public access limited?
❑ ❑ ❑
Is pump station free of overflow piping?
❑ ❑ ❑
Is the pump station free of signs of overflow?
M ❑ ❑ ❑
Are run times comparable for multiple pumps?
Page 6 of 15
Permit: WOCS00113 Owner -Facility: Town ofLouisGurg
Inspection pate: 0511412019 Inspection Type: Collection System Inspect Non Sampling Reason for Visit:
Routine
Comment: The pump station is not equipped with a quick hookup for a Portable generator.
HORSESHOE L. S. -
Pump Station
Yes No NA NE
Pump station type
Duplex
Are pump station logs available?
M❑ ❑ ❑
Is it accessible in all weather conditions?
0 ❑ 0 ❑
# Is general housekeeping acceptable?
E ❑ El 0
Are all pumps present?
E ❑ ❑ ❑
Are all pumps operable?
■ ❑ ❑
Are wet wells free of excessive debris?
0❑ ❑
Are upstream manholes free of excessive debristsigns of overflow?
❑ ❑
Are floatsicontrols for pumpslalarms operable?
0 ❑ ❑ ❑
Is "auto polling" featurelSCADA present?
E
Is "auto polling" featurelSCADA operational?
0 0❑ ❑
IS simple telemetry present?
El El ■ ❑
Is simple telemetry operational?
❑ ❑ E
Are audio and visual alarms present?
Are audio and visual alarms operable?
❑
Is the Pump station Inspected as required?
❑ ❑
Are backflow devices in place?
❑ ❑ ❑ ■
Are backflow, devices operable?
El 0 ❑
Are air relief valves in place?
❑ 0 El ■
Are air relief valves operable?
# Is an emergency generator available?
Can the emergency generator run the pumps?
Is the pump station equipped for quick hook-up?
0 El El
Is the generator operable?
# Is fuel in tank and sufficient?
Is the generator inspected according to their schedule?
❑ ❑ 0 El
Is a 24-hour notification sign posted?
Does it include:
Instructions for notification?
Pump station identifier?
E
Emergency phone number
■El❑ ❑
Is public access limited?
. ❑ ❑
Is pump station free of overflow piping?
W❑
Page 7 of 15
permit: WQCS00113 owner - Facility: Town of Louisburg
Inspection Date: 0511412019 Inspection Type, Collection System Inspect Non Sampling Reason for Visit: Routine
Is the pump station free of signs of overflow? 0 ❑ ❑ ❑
Are run times comparable for multiple pumps?
Comment: The inspector observed smoke coming from the SCADA control panel after the high water float
was activated. In response to the smoke the operator turned the breaker off. The o erator also
stated the SCADA system at the Horseshoe Lift Station does not always call out in res oonse to
a trigger event ex., power loss high water alarm etc. due to the age of the system and the
remote location which can interfer with transmission. The currents stem operates on a radio
system. Newer SCADA systems operates off cellular telephone towers Mission SCADA
systems) and get better transmissionsper the o erator.
The pump station is not equipped with aguick_hookuo for a portable generator.
PRISON PUMP STATION -
Lines/Ri ht-of-Wa slAeriel Lines
Yes No NA NE
Is right-of-way accessible for emergency?
E ❑ ❑ ❑
Is right-of-way free of sinkholes or depressions?
0 ❑ ❑ ❑
Is linelright-of-way free of evidence of leakage?
0 ❑ ❑ ❑
# Are there areas of exposed line?
0 ❑ ❑ ❑
# Is any exposed line constructed of ductile iron or other approved material?
E ❑ ❑ ❑
Are water crossing and supports in good condition?
E ❑ ❑ ❑
# Is right-of-way free of non -utility motorized traffic?
N ❑ ❑ ❑
Is line free of visible damage?
E ❑ ❑ ❑
# Are there siphons in this system?
❑ E ❑ ❑
If yes. are they maintained and documented?
Comment- Aerial line crosses a small stream feature
SUNRISE BISCUIT - Sunris
Lines/Right-of-WayslAeriel Lines
Yes No NA NE
Is right-of-way accessible for emergency?
N ❑ ❑ ❑
Is right-of-way free of sinkholes or depressions?
M ❑ ❑ ❑
Is linelright-of-way free of evidence of leakage?
N ❑ ❑ ❑
# Are there areas of exposed line?
0 ❑ ❑ ❑
# Is any exposed line constructed of ductile iron or other approved material?
E ❑ ❑ ❑
Are water crossing and supports in good condition?
❑ ❑ N ❑
# Is right-of-way free of non -utility motorized traffic?
E ❑ ❑ ❑
Is line free of visible damage?
0 ❑ ❑ ❑
# Are there siphons in this system?
❑ N ❑ ❑
If yes. are they maintained and documented?
Comment' 24-inch aerial line made of Ductile iron Ope. The line is connected by
4 inter ersed manholes
(line to manholes with 90 degree turns).
Page 8 of 15
permit; VVQCS00113 Owner -Facilty.Town of Louisburg
Inspection Date; 05/14/2019 Inspection Type : Collection System Inspect Non Sampl ng Reason for Visit: Routine
TAR RIVER SIPHON #1 - 8
LineslRiaht-of-WayslAeriel Lines Yes No NA NE
Is right-of-way accessible for emergency?
Is right-of-way free of sinkholes or depressions?
Is lineldght-of-way free of evidence of leakage? ❑
# Are there areas of exposed line? ❑
# Is any exposed line constructed of ductile iron or other approved material? 0 []
Are water crossing and supports In good condition? 11 11 0 El
# Is right-of-way free of non -utility motorized traffic? 0 ❑ ❑ ❑
Is line free of visible damage? M M ❑ ❑
# Are there siphons in this system? 0 ❑ El 0
If yes, are they maintained and documented?
Yes, siphon cleaned monthly,
Comment:
TAR RIVER SIPHON #2 - S
Lines/Right-of-WaysfAeriel Lines
Yes No NA NE
Is right-ol-way accessible for emergency?
■
Is right-of-way free of sinkholes or depressions?
0
Is lineldght-of-way free of evidence of leakage?
M ❑
# Are there areas of exposed line?
❑
# Is any exposed line constructed of ductile iron or other approved material?
13 0 ❑
Are water crossing and supports in good condition?
❑ El M ❑
# Is right-of-way free of non -utility motorized traffic?
0 11❑ ❑
Is line free of visible damage?
M 0❑ ❑
# Are there siphons in this system?
■ ❑ ❑ ❑
If yes, are they maintained and documented?
Yes, siphon cleaned monthly.
Comment:
PRISON L. S. - T. Kemp Ro
Pump Station
Yes No NA NE
Pump station type Duplex
Are pump station logs available? M ❑ 0
Is it accessible in all weather conditions? 0 11 ❑
# Is general housekeeping acceptable? 0 Cl 0 ❑
Are all pumps present?
Are all pumps operable? ❑ ❑
Are wet wells free of excessive debris? M ❑ ❑ ❑
Page 9 of 15
permit; WOCS00113 owner - Facllky:Town of Louisburg
Inspection Date. 0511412019 Inspection Type. Collection System Inspect Non Sampling
Reason for Visit Routine
Are upstream manholes free of excessive debris/signs of overflow?
❑ ❑ ❑ E
Are floats/controls for pumpslalarms operable?
0 ❑ ❑ ❑
Is "auto polling" featurelSCADA present?
E ❑ ❑ ❑
Is "auto polling" featurelSCADA operational?
■ ❑ ❑ ❑
Is simple telemetry present?
❑ ❑ 0 ❑
Is simple telemetry operational?
❑ ❑ 0 ❑
Are audio and visual alarms present?
■ Cl ❑ ❑
Are audio and visual alarms operable?
E ❑ ❑ ❑
Is the Pump station inspected as required?
0 ❑ Cl ❑
Are backflow devices in place?
❑ ❑ ❑
Are backflow devices operable?
❑ ❑ ❑
Are air relief valves in place?
❑ ❑ ❑ 0
Are air relief valves operable?
❑ ❑ ❑ 0
# Is an emergency generator available?
❑ ❑ ❑
Can the emergency generator run the pumps?
0 ❑ ❑ ❑
Is the pump station equipped for quick hook-up?
❑ ❑ E ❑
Is the generator operable?
N ❑ ❑ ❑
# is fuel in tank and sufficient?
0 ❑ ❑ ❑
Is the generator inspected according to their schedule?
E ❑ ❑ ❑
Is a 24-hour notification sign posted?
0 ❑ ❑ ❑
Does it include
Instructions for notification?
E ❑ ❑ ❑
Pump station identifier?
0 ❑ ❑ ❑
Emergency phone number
■ ❑ ❑ ❑
Is public access limited?
■ ❑ ❑ ❑
Is pump station free of overflow piping?
0 ❑ ❑ ❑
Is the pump station free of signs of overflow?
0 ❑ ❑ ❑
Are run times comparable for multiple pumps?
Comment:
FOX SWAMP L. S. -
Pub Yes No NA NE
Pump station type Duplex
Are pump station logs available? ❑ ❑ ❑
1s it accessible In all weather conditions? ❑ ❑ ❑
# Is general housekeeping acceptable? 0 ❑ ❑ ❑
Are all pumps present? E ❑ ❑ ❑
Page 10 of 15
permit: WOCS00113 Owner- Facility: Town of Louisburg
Inspection Date: 05/1412019 Inspection Type: Collection System Inspect Non Sampling
Reason for Visit: Routine
Are all pumps operable?
M❑ ❑ ❑
Are wet wells free of excessive debris?
Are upstream manholes free of excessive debrislsigns of overflow?
[�
Are floatslcontrols for pumpstalarms operable?
0❑ ❑
Is "auto polling" featurelSCADA present?
0❑ ❑
Is "auto polling" featurelSCADA operational?
0 ❑ ❑ ❑
Is simple telemetry present?
❑ El M ❑
Is simple telemetry operational?
11
Are audio and visual alarms present?
[!
Are audio and visual alarms operable?
El
Is the Pump station inspected as required?
0 ❑ El El
Are backflow devices in place?
❑ ❑ ❑
Are backflow devices operable?
❑
Are air relief valves in place?
Are air relief valves operable?
11
# Is an emergency generator available?
11
Can the emergency generator run the pumps?
M
Is the pump station equipped for quick hook-up?
Is the generator operable?
# Is fuel in tank and sufficient?
Is the generator inspected according to their schedule?
Is a 24-hour notification sign posted?
M
Does it include
Instructions for notification? 0 11 0❑
Pump station Identifier?
Emergency phone number 0 ❑ 11 ❑
Is public access limited? M 11 ❑ ❑
Is pump station free of overflow piping? 0 ❑ ❑ ❑
Is the pump station free of signs of overflow?
Are run times comparable for multiple pumps?
Comment: The Pump station is not equipped with a ouick hookup for a portable generator.
HON L. S. -
Pump, Station
Yes No NA NE
Pump station type Duplex
Are pump station logs available? ■
Is it accessible in all weather conditions? M 1111 El
Page 11 of 15
permit; WOCSOU113 owner - Facility: Town of Louisburg
Inspection Date; 0511412019 Inspection Type : Collection System Inspect Non Sampling
Reason for Visit: Routine
# Is general housekeeping acceptable?
M ❑ ❑ ❑
Are all pumps present?
0 ❑ ❑ ❑
Are all pumps operable?
M ❑ ❑ ❑
Are wet wells free of excessive debris?
M ❑ ❑ ❑
Are upstream manholes free of excessive debris/signs of overflow?
❑ ❑ ❑
Are floats/controls for pumps/alarms operable?
❑ ❑ ❑
Is "auto polling" featurelSCADA present?
0 ❑ ❑ ❑
1s "auto polling" featurelSCADA operational?
❑ ❑ ❑
Is simple telemetry present?
❑ ❑ ❑
Is simple telemetry operational?
❑ ❑ ❑
Are audio and visual alarms present?
0 ❑ ❑ ❑
Are audio and visual alarms operable?
M ❑ ❑ ❑
Is the Pump station Inspected as required?
0 ❑ ❑ ❑
Are backflow devices in place?
❑ ❑ ❑
Are backflow, devices operable?
❑ ❑ ❑
Are air relief valves in place?
❑ ❑ ❑ 0
Are air relief valves operable?
❑ ❑ ❑
# Is an emergency generator available?
❑ M ❑ ❑
Can the emergency generator run the pumps?
❑ ❑ 0 ❑
Is the pump station equipped for quick hook-up?
❑ 0 ❑ ❑
Is the generator operable?
❑ ❑ M ❑
# Is fuel in tank and sufficient?
❑ ❑ ❑
Is the generator inspected according to their schedule?
❑ ❑ ❑
Is a 24-hour notification sign posted?
❑ ❑ ❑
Does it include
Instructions for notification? ❑ ❑ ❑
Pump station identifier? ❑ ❑ ❑
Emergency phone number ❑ ❑ ❑
Is public access limited? ❑ ❑ ❑
Is pump station free of overflow piping? M ❑ ❑ ❑
Is the pump station free of signs of overflow? ■ ❑ ❑ ❑
Are run times comparable for multiple pumps?
Comment: The lift station is not equipped with quick hook-up for portable Generators.
WOLF PEN L. S. -
Pumo Station Yes No NA NE
Pump station type Duplex
Page 12 of 15
Permit: WOCS00113 Owner -Facility: Town of Louisburg
Inspection Date: 0511412019 Inspection Type: Collection System Inspect Non Sampling
Reason for Visit: Routine
Are pump station logs available?
M 0❑ ❑
Is it accessible in all weather conditions?
M❑ ❑ El
# Is general housekeeping acceptable?
M El 11 El
Are all pumps present?
M El El 0
Are all pumps operable?
M 1:1 El El
Are wet wells free of excessive debris?
Are upstream manholes free of excessive debrislsigns of overflow?
[l 0 ❑ M
Are floats/controls for pumpslalarms operable?
0❑ ❑ ❑
Is "auto polling" featurelSCADA present?
0 ❑ ❑
Is "auto palling" featurelSCADA operational?
Is simple telemetry present?
0
Is simple telemetry operational?
Are audio and visual alarms present?
Are audio and visual alarms operable?
Is the Pump station inspected as required?
Are backflow devices in place?
Are backflow devices operable?
Are air relief valves in place?
Are air relief valves operable?
# Is an emergency generator available?
m ci Ein
Can the emergency generator run the pumps?
0 ❑ ❑ 11
Is the pump station equipped for quick hook-up?
❑
Is the generator operable?
11
# Is fuel in lank and sufficient?
o Ei❑
Is the generator inspected according to their schedule?
Is a 24-hour notification sign posted?
0 El El 0
Does it include:
Instructions for notification?
0 El ❑ El
Pump station identifier?
Emergency phone number
Is public access limited?
Is pump station free of overflow piping?
Is the pump station free of signs of overflow?
m ❑ ❑ ❑
Are run limes comparable for multiple pumps?
Comment:
BRITHAVEN L. S. - Britthav,
Page 13 of 15
Permit: WOCS00113 owner - Facility: Town of Louisburg
Inspection Date: 05/14/2019 Inspection Type : Collection System Inspect Non Sampling
Reason for Visit Routine
Pump Station
Yes No NA NE
Pump station type
Duplex
Are pump station logs available?
M ❑ ❑ ❑
Is it accessible in all weather conditions?
M ❑ ❑ ❑
# Is general housekeeping acceptable?
❑ ❑ ❑
Are all pumps present?
❑ ❑ ❑
Are all pumps operable?
M ❑ ❑ ❑
Are wet wells free of excessive debris?
M ❑ ❑ ❑
Are upstream manholes free of excessive debrisisigns of overflow?
❑ ❑ ❑
Are floats/controls for pumpslalarms operable?
❑ ❑ ❑
Is "auto polling" feature/SCAOA present?
❑ ❑ ❑
Is "auto polling" featurelSCADA operational?
0 ❑ ❑ ❑
Is simple telemetry present?
❑ ❑ 0 ❑
Is simple telemetry operational?
❑ ❑ M ❑
Are audio and visual alarms present?
M ❑ ❑ ❑
Are audio and visual alarms operable?
M ❑ ❑ ❑
Is the Pump station inspected as required?
M ❑ ❑ ❑
Are backflow, devices in place?
❑ ❑ ❑ M
Are backflow devices operable?
❑ ❑ ❑
Are air relief valves in place?
❑ ❑ ❑
Are air relief valves operable?
❑ ❑ ❑
# Is an emergency generator available?
❑ 0 ❑ ❑
Can the emergency generator run the pumps?
❑ ❑ 0 ❑
Is the pump station equipped for quick hook-up?
❑ M ❑ ❑
Is the generator operable?
❑ ❑ 0 ❑
# Is fuel in tank and sufficient?
❑ ❑ M ❑
Is the generator inspected according to their schedule?
❑ ❑ M ❑
Is a 24-hour notification sign posted?
0 ❑ ❑ ❑
Does it include'
Instructions for notification?
0 ❑ ❑ ❑
Pump station identifier?
0 ❑ ❑ ❑
Emergency phone number
M ❑ ❑ ❑
Is public access limited?
M ❑ ❑ ❑
Is pump station free of overflow piping?
M ❑ ❑ ❑
Is the pump station free of signs of overflow?
M ❑ ❑ ❑
Are run times comparable for multiple pumps?
Page 14 of 15
Permit: WOCS00113 Owner • Facility: Town of Louisburg
Inspection Date: 0511412019 Inspection Type: Collection System Inspect Non Sampling Reason for Visit RQ.b-;e
Comment: Public access to the pump station a ui ment is restricted with the use of locks on the wet well
SCADA box and control panels. There is no fence surrounding the Dump station.
Although the Dump station does not have a dedicated emergency enerator the operator stated
Britthaven Nursing Home is equipped with a backup generator in the event of power loss, which
would operate the Dump station. The pump station is not equipped with a quick hookup for a
amble generator.
Page 15 of 15