June 3, 2019
Certified Mail# 7017 2620 0000 9759 1284
Return Receipt Requested
Dakota Ingram
Clay County Water & Sewer District
PO Box 838
Hayesville, NC 28904
SUBJECT: NOTICE OF DEFICIENCY
Tracking Number: NOD-2019-PC-0137
Permit No. NC0026697
Clay County WWTP
Clay County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Clay County WWTP on May 20,
2019. This inspection was conducted to verify that the facility is operating in compliance with the conditions and
limitations specified in NPDES WW Permit No. NC0026697. A summary of the findings and comments noted
during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following deficiency was noted during the inspection:
Inspection Area Description of Deficiency _________________________________________________________________________________________________________________________________________________________________________
Effluent Sampling Effluent sampler is set to constant time/constant volume. Per Part II Section A, constant
time/constant volume effluent sampling is only allowed with prior Division approval and if it can
be demonstrated flows vary <15%. _________________________________________________________________________________________________________________________________________________________________________
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
Please notify our office, in writing (email is acceptable), within the next 30 days of the District’s plans to address
the noted deficiency. Flow proportional effluent sampling is required by permit. As stated above, constant
time/constant volume effluent composite sampling is only allowed with prior Division approval and if the permittee
can demonstrate flows do not vary by more than 15%.
If you should have any questions, please do not hesitate to contact Mikal Willmer with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4686.
Sincerely,
For G. Landon Davidson, P.G., Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
EC: WQS-ARO Server
LF
G:\WR\WQ\Clay\Wastewater\Municipal\Clay County WWTP 26697\Inspections\Inspect. May 20, 2019\20190603_NC0026697_NOD2019PC0137
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0026697 19/05/20 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Clay County WWTP
NCSR 1300
Hayesville NC 28904
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:00AM 19/05/20 17/10/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Jeremy E Arrowood/ORC/828-389-1361/
Other Facility Data
12:30PM 19/05/20 22/08/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Dakota Ingram,PO Box 838 Hayesville NC 28904//828-889-1361/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Mikal Willmer Division of Water Quality//828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
6/3/2019
6/3/2019
NPDES yr/mo/day
19/05/20
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Inspector Mikal Willmer, with the Asheville Regional Office, conducted a Compliance Evaluation
Inspection of the Clay County Water & Sewer District's WWTP. This inspection was condcuted to
determine whether the facility is being operated and maintained in compliance with NPDES Permit No.
NC0026697.
Overall the facility is well operated and maintained; however, there was a noted deficiency with the
method of effluent sampling. It was mentioned in the previous compliance inspection that effluent
sampling needed to be switched to flow proportional or a variance requested. At the time of the most
recent inspection, the effluent sampler was still set to time composite. Per Part II Section A, Composite
Sampling of the Standard Conditions, effluent sampling must be flow proportional. Constant
Time/Constant Volume composite effluent sampling is only allowed with prior Division approval and if
the permittee can demonstrate flows do not vary by more than 15%.
No other permit deficiencies were noted at the time of the inspection. The following are observations
and recommendations.
Headworks: The current influent bar screen spacing allows significant debris to pass into the aeration
basin. Recommend assessing an alternative setup as budget allows.
Safety: There is no easy access to the Aeration Basin diffusers for routine maintenance. Facility staff
either must use an extension ladder or walk along the concrete edge of the basin. This presents a
significant fall/trip hazard.
Standby Power: There is only one portable generator onsite to service the WWTP and 10 lift stations. It
is highly recommended the District budget for additional generators in the event of an extended power
outage or severe weather.
NC0026697 17 (Cont.)
Page#2
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
Permit:NC0026697
Inspection Date:05/20/2019
Owner - Facility:
Inspection Type:
Clay County WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Staff routinely check MLSS. Monitor DO and check clarify sludge depth occasionally.Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Permit has DO reopener and requirement for total mercury analysis within 12 months of
permit expiration.
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Page#3
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
Permit:NC0026697
Inspection Date:05/20/2019
Owner - Facility:
Inspection Type:
Clay County WWTP
Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review?
Copies of the annual report are mailed to customers. They are also posted at the library and
post office. The District is looking to post the annual report on the new website.
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Facility has a small manual bar screen with wide grates and no grit chamber. Mr. Arrowood
places a smaller manual screen over the bar screen on occasion to help reduce excessive
pass-through debris; however, this backs up the flow at the headworks. Screen is raked and
cleaned daily.
Comment:
Influent Sampling Yes No NA NE
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is sampling performed according to the permit?
Sampler is set to time composite.Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Page#4
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
Permit:NC0026697
Inspection Date:05/20/2019
Owner - Facility:
Inspection Type:
Clay County WWTP
Compliance Evaluation
Aeration Basins Yes No NA NE
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Diffusers only run along one side of the Basins. Two diffusers were inoperable (reportedly
clogged) at the time of the inspection; however, this did not appear to be creating significant
dead spots. Mr. Arrowood states the DO is about 1 mg/L during the summer months.
Blowers run continuously during the summer and some valves are closed during the winter.
Pass-through debris could be seen in the aeration basin. Catch baskets above the basin's
discharge collects any debris/grit. These are cleaned once a day.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
These are AeroMod clarifiers with airlift RAS pumps. Weirs are below the water level so
cannot be easily evaluated. Sludge depth stays about 3' to 4' out of 16'. RAS runs off and on
throughout the day.
Comment:
Pumps-RAS-WAS Yes No NA NE
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
System utilizes air-lift pumps. Staff report spare parts are maintained on-site.Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
Page#5
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
Permit:NC0026697
Inspection Date:05/20/2019
Owner - Facility:
Inspection Type:
Clay County WWTP
Compliance Evaluation
Aerobic Digester Yes No NA NE
# Is tankage available for properly waste sludge?
Staff report there is adequate digester space to waste sludge. The digester is settled
approximately twice a year and solids are pressed and sent to a Landfill in Georgia.
Comment:
Disinfection-Gas Yes No NA NE
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-____-____)
If yes, then when was the RMP last updated?
Staff would like to switch to a liquid chlorine feed or another alternative disinfectant for safety
reasons. The fire department is notified in the event of a leak.
Comment:
De-chlorination Yes No NA NE
Type of system ?Gas
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?
Sulfur dioxide and Chlorine are stored in same building.Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Page#6
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
Permit:NC0026697
Inspection Date:05/20/2019
Owner - Facility:
Inspection Type:
Clay County WWTP
Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Facility utilizes a siemens flow meter (model has been discontinued).Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Facility's effluent sampler is set to time composite. The District has an ISCO composite
sampler and Siemens flow meter which may be incompatible. Staff will check compatibility.
Time-composite sampling is only allowed with prior Division approval and if flows only vary <
15%.
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and
sampling location)?
Sampling points are 100' upstream and downstream. Staff report no issues with access to
sampling points.
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Page#7
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
Permit:NC0026697
Inspection Date:05/20/2019
Owner - Facility:
Inspection Type:
Clay County WWTP
Compliance Evaluation
Standby Power Yes No NA NE
Portable generator kept at the WWTP can run the entire facility. Generator was recently
used to run the facility during a power outage. Fuel is maintained onsite and the District has
a contract with Parker Oil located in Hayesville. See summary for generator
recommendations.
Comment:
Solids Handling Equipment Yes No NA NE
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Facility presses the biosolids and hauls to a landfill in Georgia twice a year.Comment:
Page#8
DocuSign Envelope ID: 55CDF2BA-37DC-449C-B4FB-7181435DE5A7
Certificate Of Completion
Envelope Id: 55CDF2BA37DC449CB4FB7181435DE5A7 Status: Completed
Subject: Please DocuSign: 20190603_NC0026697_NOD2019PC0137.docx, 20190603_NC0026697_inspect.pdf
Source Envelope:
Document Pages: 10 Signatures: 2 Envelope Originator:
Certificate Pages: 2 Initials: 1 Mikal Willmer
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-05:00) Eastern Time (US & Canada)
217 W. Jones Street
Raleigh, NC 27699
Mikal.willmer@ncdenr.gov
IP Address: 149.168.204.10
Record Tracking
Status: Original
Jun 3, 2019 | 10:13
Holder: Mikal Willmer
Mikal.willmer@ncdenr.gov
Location: DocuSign
Signer Events Signature Timestamp
Mikal Willmer
mikal.willmer@ncdenr.gov
Environmental Specialist
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 149.168.204.10
Sent: Jun 3, 2019 | 10:14
Viewed: Jun 3, 2019 | 10:14
Signed: Jun 3, 2019 | 10:15
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
Zan Price
zan.price@ncdenr.gov
DWR-RO
DEQ
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 149.168.204.10
Sent: Jun 3, 2019 | 10:15
Viewed: Jun 3, 2019 | 10:25
Signed: Jun 3, 2019 | 10:25
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted Jun 3, 2019 | 10:15
Certified Delivered Security Checked Jun 3, 2019 | 10:25
Signing Complete Security Checked Jun 3, 2019 | 10:25
Envelope Summary Events Status Timestamps
Completed Security Checked Jun 3, 2019 | 10:25
Payment Events Status Timestamps