Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 15 1 3 I NCO041718 111 12 I 19/05/07 I17 18 I S I 19 I G I 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70 I g 71 I tyI 72 I r I 73 I I 174 751 I I I I I I I80
uI I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
12:09PM 19/05/07
19/04/01
Clearview at Misenheimer
48708 US Hwy 52
Exit Time/Date
Permit Expiration Date
Misenheimer NC 28109
01:19PM 19/05/07
24/02/29
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
John Walter Ritchie/ORC/704-788-4164/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Paul J Smith,85 N Hillside Dr North Myrtle Beach SC 29582//843-280-4460/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Roberto Scheller _ (-� MRO WQ//252-946-6481/ 5/13/2019
C)91C2A007838943E—
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger Division of Water Quality//704-2'
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
' 5/14/2019
AlaccsalAi=z7azs... Page#
NPDES yr/mo/day Inspection Type
NCO041718 I11 121 19/05/07 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO041718 Owner - Facility: Clearview at Misenheimer
Inspection Date: 05/07/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Current permit is for the continued operation of an existing 0.005 MGD wastewater treatment
plant. Permit became effective on April 1, 2019 and expires on February 29, 2024.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
0
❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: Records and copy of permit are stored off site due to vandalism.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Page# 3
Permit: NCO041718
Inspection Date: 05/07/2019
Owner - Facility: Clearview at Misenheimer
Inspection Type: Compliance Evaluation
Operations & Maintenance
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Yes No NA NE
■ ❑ ❑ ❑
Yes No NA NE
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
Comment: Bar screen had rusted off treatment unit and is held in place with rope. It is recommended
that bar screen be replaced with a fine screen to remove more of debris from influent and
prevent blockage of lift pumps.
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Ext. Air
Diffused
■
❑
❑
❑
❑
❑
■
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
Comment: At time of inspection aeration basin diffusers appeared to be operational and MLSS well
mixed.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
0
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
❑
❑
❑
Page# 4
Permit: NC0041718 Owner - Facility:
Inspection Date: 05/07/2019 Inspection Type:
Clearview at Misenheimer
Compliance Evaluation
Secondary Clarifier
Yes No NA NE
Is scum removal adequate?
❑
0
❑
❑
Is the site free of excessive floating sludge?
❑
0
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
❑
❑
❑
Comment: Sludge blanket on surface of secondary should be removed.
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment:
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑
Is storage appropriate for cylinders? ❑ ❑ 0 ❑
# Is de -chlorination substance stored away from chlorine containers? ❑ ❑ ❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 2
Comment:
Page# 5
Roy COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mr. Paul J. Smith
85 North Hillside Drive
Myrtle Beach, SC 29582
NORTH CAROLINA
Environmental Quality
May 14, 2019
SUBJECT: Compliance Evaluation Inspection
Clearview at Misenheimer WWTP
NPDES Permit NCO041718
Stanly County, NC
Dear Mr. Smith:
On May 7, 2019, Roberto Scheller of this Office conducted a compliance inspection at the subject
facility. This inspection was conducted as a Compliance Sampling Inspection (CSI) to insure
compliance with permit requirements and conditions.
The subject facility appeared to be well operated. We wish to thank the operating staff for
assistance regarding this inspection. The enclosed report should be self-explanatory; however,
should you have any questions, please do not hesitate to contact myself or Roberto Scheller at
(704) 235-2204 or roberto.scheller(a_ncdenr.gov.
Sincerely,
DocuSigned by:
A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: CSI Report