HomeMy WebLinkAboutWQCSD0283_Inspection_20190514Compliance Inspection Report
Permit:WQCSD0283 Effective:10/31/07 Expiration:Owner :A&D Water Service Inc
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Henderson
Asheville
Patty Carland
Effective:Expiration:Facility:Mountain Valley WWTP
NCSR 1171
Etowah NC 28729
Title:Phone:828-890-4810
Secondary ORC(s):
Phone:Certification:Primary ORC:
System Classifications:
On-Site Representative(s):
Related Permits:
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
05/14/2019 10:45AM 11:45AM
Daniel J Boss 828-296-4658
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Deemed permitted collection system management and operation
Collection System Inspect Non Sampling
Question Areas:
Miscellaneous Questions Records Inspections
Pump Station Manhole
(See attachment summary)
Page 1 of 5
DocuSign Envelope ID: 365EE6D8-B465-49B2-9CF7-707C0ECD8517
5/15/2019
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQCSD0283
05/14/2019 Collection System Inspect Non Sampling
A&D Water Service Inc
Routine
Inspection Summary:
I met with Aubrey Deaver Jr. for a compliance evaluation inspection of the Mountain Valley Collection System on 5/14/2019.
The system has 1 lift station and 7 manholes. The lift station's telemetry was not fully functional and the visual alarm was
not working. These items were noted in the last inspection report in August of 2014 as well. We looked at 5 of the 7
manholes and they all appeared in fine condition including the manhole at 310 Windy Knoll which had been cited for
excessive grease in the prior inspection report.
Mr. Deaver did not have a map of the system, O&M plan, or logs of high priority line inspections.
Grease education materials have not been distributed in the last 6 months, this needs to be done every 6 months.
Page 2 of 5
DocuSign Envelope ID: 365EE6D8-B465-49B2-9CF7-707C0ECD8517
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQCSD0283
05/14/2019 Collection System Inspect Non Sampling
A&D Water Service Inc
Routine
Inspections Yes No NA NE
Are maintenance records for sewer lines available?
Are records available that document pump station inspections?
Are SCADA or telemetry equipped pump stations inspected at least once a week?
Are non-SCADA/telemetry equipped pump stations inspected every day?
Are records available that document citizen complaints?
# Do you have a system to conduct an annual observation of entire system?
# Has there been an observation of remote areas in the last year?
Are records available that document inspections of high-priority lines?
Has there been visual inspections of high-priority lines in last six months?
High priority line inspections have not been taking place.Comment:
Records Yes No NA NE
Are adequate records of all SSOs, spills and complaints available?
Are records of SSOs that are under the reportable threshold available?
Do spill records indicate repeated overflows (2 or more in 12 months) at same location?
If yes, is there a corrective action plan?
Is a map of the system available?
Does the map include:
Pipe sizes
Pipe materials
Pipe location
Flow direction
Approximate pipe age
Number of service taps
Pump stations and capacity
If no, what percent is complete?
List any modifications and extensions that need to be added to the map
# Does the permittee have a copy of their permit?
There was not a map available. Mr. Deaver said that he believes that they have one, but they
have not yet located it in their files.
The pump station inspections are conducted by Vincent Edwards who was not present at the
time of the inspection.
Comment:
1 - Mountain Valley Dr.
Pump Station Yes No NA NE
Pump station type Duplex
Page 3 of 5
DocuSign Envelope ID: 365EE6D8-B465-49B2-9CF7-707C0ECD8517
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQCSD0283
05/14/2019 Collection System Inspect Non Sampling
A&D Water Service Inc
Routine
Are pump station logs available?
Is it accessible in all weather conditions?
# Is general housekeeping acceptable?
Are all pumps present?
Are all pumps operable?
Are wet wells free of excessive debris?
Are upstream manholes free of excessive debris/signs of overflow?
Are floats/controls for pumps/alarms operable?
Is "auto polling" feature/SCADA present?
Is "auto polling" feature/SCADA operational?
Is simple telemetry present?
Is simple telemetry operational?
Are audio and visual alarms present?
Are audio and visual alarms operable?
Is the Pump station inspected as required?
Are backflow devices in place?
Are backflow devices operable?
Are air relief valves in place?
Are air relief valves operable?
# Is an emergency generator available?
Can the emergency generator run the pumps?
Is the pump station equipped for quick hook-up?
Is the generator operable?
# Is fuel in tank and sufficient?
Is the generator inspected according to their schedule?
Is a 24-hour notification sign posted?
Does it include:
Instructions for notification?
Pump station identifier?
Emergency phone number
Is public access limited?
Is pump station free of overflow piping?
Is the pump station free of signs of overflow?
Are run times comparable for multiple pumps?
The telemetry was not working and the visual alarm did not work. These items were also noted
in the August 2014 inspection.
Comment:
Page 4 of 5
DocuSign Envelope ID: 365EE6D8-B465-49B2-9CF7-707C0ECD8517
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQCSD0283
05/14/2019 Collection System Inspect Non Sampling
A&D Water Service Inc
Routine
1 - 310 Windy Knoll
Manhole Yes No NA NE
Is manhole accessible?
# Is manhole cover/vent above grade?
Is the manhole free of visible signs of overflow?
Is the manhole free of sinkholes and depressions?
Is manhole cover present?
# Is manhole properly seated?
# Is manhole in good condition?
# Is invert in good condition?
Is line free-flowing and unrestricted in manhole?
Is manhole free of excessive amounts of grease?
Is manhole free of excessive roots?
Is manhole free of excessive sand?
Is manhole's extended vent screened?
Are vents free of submergence?
Are manholes free of bypass structures or pipes?
This manhole is fed by a service line that had a sag in it which had been causing solids and
grease to build in the manhole. The pipe sag was fixed and there is no longer a solids build up in
the manhole.
Comment: