Loading...
HomeMy WebLinkAboutWQ0029945_Compliance Evaluation Inspection_20190502 DocuSign Envelope ID:25A4AFFB-9174-4EE3-8AB0-C945378B7F4E ROY COOPED C:�Crry�r MICHAEL S.R.EGAN .� . Seer'etQry LINDA CULPBPPER NORTH CAROLINA arrm r Environmental Quallry May 13, 2019 Edward M Caron Onslow Water and Sewer Authority 228 Georgetown Rd Jacksonville, NC 28540 SUBJECT: Compliance Inspection Report Summerhouse Wastewater Reclamation WWTF Non-discharge Permit No. WQ0029945 Onslow County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Summerhouse Wastewater Reclamation WWTF on 5/02/2019. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Non-discharge Permit No. WQ0029945. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. North Carol"DepsrtmentofEnvironmeatedQua;ity I DWsiorof Water Resources 1i'drnington Regional Office 1 127 Cardinai DFive Extension 11451m:ngton, North Caroma 25405 910-796-7215 DocuSign Envelope ID:25A4AFFB-9174-4EE3-8AB0-C945378B7F4E If you should have any questions, please do not hesitate to contact Helen Perez with the Water Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at helen.perez@ncdenr.gov. Sincerely, DocuSigned by: �lbVt��a Sa 6" E3ABA14AC7DC434... Morella Sanchez-King, Regional Supervisor Water Quality Regional Operations Section Wilmington Regional Office Division of Water Resources, NCDEQ ATTACHMENTS Cc: Uploaded to Laserfiche Mike Lutz — electronic copy North f'sroGna Department offnvironmeatadQuality I Diuisianof Water Resources Z��p Wilmington Regional Office 1127 Cardinr lDrivefxtensoo I WiHmington. North Caro ina23405 - 910-796-7215 Compliance Inspection Report Permit: WQ0029945 Effective: 05/01/15 Expiration: 04/30/20 owner: Onslow Water and Sewer Authority SOC: Effective: Expiration: Facility: Summerhouse Wastewater Reclamation WWTF County: Onslow Twining Rose Ln Region: Wilmington Holly Ridge NC 28445 Contact Person: Edward M Caron Title: Phone: 910-937-7523 Directions to Facility: Follow NC Hwy 17 north to Holly Ridge,approx.0.1 mile past the insterection of Hwy 17 and 50,turn R onto Morris Landing Rd. Travel approx. 1.7 miles to Holly Ridge Rd.on the left follow this road for approx. 1.6 miles to Kings Creek Crossing on the R System Classifications: WW3•, Primary ORC: Michael Keith Lutz Certification: 1005688 Phone: 907-539-8101 Secondary ORC(s): Mark Curtis Young 1001105 910-937-7570 On-Site Representative(s): Related Permits: WQ0034067 Onslow Water and Sewer Authority-Stump Sound Wastewater Infrastructure Improvements Sewer WQ0019907 Onslow Water and Sewer Authority-Holly Ridge WWTF Inspection Date: 05/02/2019 Entry Time: 09:OOAM Exit Time: 11:OOAM Primary Inspector: Helen I Perez Phone: 910-796-7387 Secondary Inspector(s): Reason for Inspection: Routine Inspection Type: Compliance Evaluation Permit Inspection Type: High Rate Infiltration Facility Status: Compliant ❑ Not Compliant Question Areas: Treatment Flow Measurement-Effluent Treatment Flow Measurement-Influent Miscellaneous Questions Treatment Flow Measurement-Water Treatment Treatment Barscreen Use Records Treatment Filters Record Keeping Treatment Activated Sludge Treatment Sludge Storage/Treatment Treatment Disinfection End Use-Infiltration Treatment Flow Measurement Treatment Return pumps Standby Power Coastal Requirements (See attachment summary) Page 1 of 7 Permit: WQ0029945 Owner-Facility:Onslow Water and Sewer Authority Inspection Date: 05/02/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Inspection Summary: A routine compliance inspection of the Summerhouse WWTF was conducted on May 02, 2019.The purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit WQ0029945. Mike Lutz, ORC,and Eddie Caron, ONWASA's Utilities Superintendent,was present during the inspection. This facility started up in the spring of 2017 after extensive repairs and equipment replacement.Two of the four Membrane Bio-Reactors(MBR)are in operation. Currently,the facility is treating an average of 87,000-88,000gpd of the 400,000gpd permitted flow. Effluent disposal consists of two infiltration basins located within the Summerhouse community. Infiltration Basin#2 is currently being used while Infiltration Basin#1 is waiting on work to begin in the near future to increase the hydraulic loading rate. Staff keeps organized records to include daily/weekly task check sheets, monthly data computer spreadsheets and a detailed operation/maintenance log book to monitor plant operations. ONWASA has the ability to divert flow from the Holly Ridge, Jenkins St. Pump Station to Summerhouse WWTF for treatment instead of going to Holly Ridge WWTF. Since start-up,the facility has had 4 daily fecal limit NODS, 1 daily ammonia limit NOD and a NOV for a monthly total phosphorus limit issued.There has been complaints from the residents of the Summerhouse community about the algae growth that can be seen in the summer months in the infiltration basins. ONWASA has communicated to the residents the nature of algae growth and has contacted our office for assistance in the past. The facility is compliant with non-discharge permit WQ0029945. Please review the comment sections of the inspection report for more details. Page 2 of 7 Permit: WQ0029945 Owner-Facility:Onslow Water and Sewer Authority Inspection Date: 05/02/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Recycle/Reuse ❑ Lagoon Spray, LR ❑ Single Family Drip ❑ Single Family Spray, LR ❑ Reuse(Quality) ❑ Activated Sludge Spray, HR ❑ Activated Sludge Spray, LR ❑ Activated Sludge Drip,LR ❑ Infiltration System Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑ Do all treatment units appear to be operational?(if no,note below.) 0 ❑ ❑ ❑ Comment: Two of the four treatment units are operational. The odor control system is not currently being used. Treatment Flow Measurement-Influent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? 0 ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: The influent flow meter only records flow from the Jenkins Street pump station that can be diverted to Summerhouse when needed. The meter was calibrated on 12-05-18 by Carolina Technical Services Inc. Treatment Flow Measurement-Water Use Records Yes No NA NE Is water use metered? ❑ 1:10 ❑ Are the daily average values properly calculated? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement-Effluent Yes No NA NE Is flowmeter calibrated annually? 0 ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? 0 ❑ ❑ ❑ Does flowmeter record flow? 0 ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Page 3 of 7 Permit: WQ0029945 Owner-Facility:Onslow Water and Sewer Authority Inspection Date: 05/02/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Comment: The flowmeter was calibrated on 12-05-18 by Carolina Technical Services Inc. The turbidity meter was calibrated on 7-19-18 by ONWASA staff. Standby Power Yes No NA NE Is automatically activated standby power available? ❑ ❑ ❑ Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑ Is generator operable? ❑ ❑ ❑ Does generator have adequate fuel? ❑ ❑ ❑ Comment: The generator is automatically load tested weekly and documented on the weekly data sheets. Treatment Barscreen Yes No NA NE Is it free of excessive debris? ❑ ❑ ❑ Is disposal of screenings in compliance? ❑ ❑ ❑ Are the bars spaced properly? ❑ ❑ ❑ Is the unit in good condition? ❑ ❑ ❑ Comment: The headworks consists of dual mechanically cleaned fine screens, an auxiliary manually cleaned bar screen and a Hydro International GritCup and SpiraSnail grit removal and dewatering system. In addition, each train has a 2 mm drum screen at the inlet to protect the operation of the membranes. Treatment Activated Sludge Yes No NA NE Is the aeration mechanism operable? 0 ❑ ❑ ❑ Is the aeration basin thoroughly mixed? 0 ❑ ❑ ❑ Is the aeration equipment easily accessed? ❑ ❑ ❑ Is Dissolved Oxygen adequate? ❑ ❑ ❑ Are Settleometer results acceptable? ❑ ❑ ❑ Is activated sludge an acceptable color? ❑ ❑ ❑ Comment: The Membrane Bio-Reactors consist of an anoxic basin, aeration basin and the membrane tank. A carbon source is added in the anoxic basin. Mixed liquor averages 8000-9000 mg/I. Process control includes testing of the influent BOD and nutrients and mixed liquor once a week. Treatment Return pumps Yes No NA NE Are they in place? ❑ ❑ ❑ Are they operational? ❑ ❑ ❑ Comment: No comment. Treatment Filters Yes No NA NE Is the filter media present? ❑ ❑ ❑ Is the filter media the correct size and type? ❑ ❑ ❑ Is the air scour operational? ❑ ❑ ❑ Is the scouring acceptable? ❑ ❑ ❑ Page 4 of 7 Permit: WQ0029945 Owner-Facility:Onslow Water and Sewer Authority Inspection Date: 05/02/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Is the clear well free of excessive solids? ❑ ❑ ❑ Is the mud well free of excessive solids and filter media? ❑ ❑ ❑ Does backwashing frequency appear adequate? ❑ ❑ 0 ❑ Comment: Once every 6 months the membranes are cleaned with ctric acid and every 90 days, they are cleaned with a NaOCI solution. Treatment Sludge Storage/Treatment Yes No NA NE Is the aeration operational? ❑ ❑ ❑ Is the aeration pattern even? ❑ ❑ ❑ If required,are Sanitary"Ts"present in tankage? ❑ ❑ 0 ❑ Comment: The aerobic digester solids are removed by Lewis Farms. Treatment Disinfection Yes No NA NE Is the system working? 0 ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time(-30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas,does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ 0 ❑ If tablets,are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge,solids,and growth? ❑ ❑ ❑ If UV,are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ #Is it a dual feed system? 0 ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine(CAS No.7782-50-5)? ❑ ❑ ❑ If yes,then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes,then what is the EPA twelve digit ID Number?(1000- ) If yes,then when was the RMP last updated? Comment: Each MBR train has an UV unit. If needed, sodium hypochlorite solution can be used for disinfection. Record Keeping Yes No NA NE Is a copy of current permit available? ❑ ❑ ❑ Are monitoring reports present: NDMR? ❑ ❑ ❑ NDAR? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are flow rates less than of permitted flow? 0 ❑ ❑ ❑ Page 5 of 7 Permit: WQ0029945 Owner-Facility:Onslow Water and Sewer Authority Inspection Date: 05/02/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Are application rates adhered to? 0 ❑ ❑ ❑ Is GW monitoring being conducted,if required(GW-59s submitted)? ❑ ❑ 0 ❑ Are all samples analyzed for all required parameters? ❑ ❑ ❑ Are there any 2L GW quality violations? ❑ ❑ ❑ Is GW-59A certification form completed for facility? ❑ ❑ ❑ Is effluent sampled for same parameters as GW? ❑ ❑ ❑ Do effluent concentrations exceed GW standards? ❑ ❑ ❑ Are annual soil reports available? ❑ ❑ ❑ #Are PAN records required? ❑ ❑ ❑ #Did last soil report indicate a need for lime? ❑ ❑ ❑ If so,has it been applied? ❑ ❑ ❑ Are operational logs present? ❑ ❑ ❑ Are lab sheets available for review? ❑ ❑ ❑ Do lab sheets support data reported on NDMR? ❑ ❑ ❑ Do lab sheets support data reported on GW-59s? ❑ ❑ ❑ Are Operational and Maintenance records present? ❑ ❑ ❑ Were Operational and Maintenance records complete? ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ ❑ No treatment units bypassed since last inspection? 0 ❑ ❑ ❑ Comment: Monitoring reports, lab results and COCs are organized and complete as well as the operation and maintenance logs. The ONWASA in house lab (Cert#539)does the majority of the monitoring report testing and Envirochem (Cent#94)does the remainder. End Use-Infiltration Yes No NA NE #Is the application High Rate or Low Rate? High Rate Are buffers maintained? ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ Is municipal water available in the area? 0 ❑ ❑ ❑ Are GW monitoring wells required? ❑ ❑ ❑ Are GW monitoring wells located properly w/respect to RIB and CB? ❑ ❑ ❑ Are GW monitoring wells properly constructed,including screened interval? ❑ ❑ ❑ Is a usable green area maintained? ❑ ❑ ❑ Is the disposal site acceptable? ❑ ❑ ❑ Is the distribution equipment acceptable? ❑ ❑ ❑ Is the disposal site free of ponding? ❑ ❑ ❑ Is the disposal site free of breakout? 0 ❑ ❑ ❑ Page 6 of 7 Permit: WQ0029945 Owner-Facility:Onslow Water and Sewer Authority Inspection Date: 05/02/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Are the disposal sites free of solids,algae,etc.? 0 ❑ ❑ ❑ Do the records show that the fields are properly maintained? ❑ ❑ ❑ Are the disposal sites free of vegetation? ❑ ❑ ❑ Do any surface water features appear to be adversely impacted by GW discharge? ❑ ❑ ❑ No chemicals or rototiller used to eliminate vegetation,solids,algae,etc.? ❑ ❑ 0 ❑ Comment: There are 2 infiltration basins located within the Summerhouse community. Infiltration Basin #2 is currently being used. Work on Infiltration Basin#1 will be started in the near future to increase the hydraulic loading rate. Basins do not have restrictive signs to prevent public access and signs will need to be posted as soon as possible. The groundwater lowering effluent pond (Spicer Lake) and the surface water monitoring station, located at a tributary of Kings Creek, are sampled 3 times a year. Each infiltration basin has a groundwater lowering pump station with a flow meter to measure application to the basin. Both flow meters were calibrated on 12-05-18 by Carolina Technical Services Inc. Each pump station is equipped with a generator that automatically load tests every week. Coastal Requirements Yes No NA NE Are essential treatment units provided in duplicate? ❑ ❑ ❑ Is an adequately sized aerated equalization basin present? ❑ ❑ ❑ If so, is it operable? ❑ ❑ ❑ If present,are diffusers cleaned regularly? ❑ ❑ ❑ Is the equalization capacity adequate? 0 ❑ ❑ ❑ Comment: No comment. Page 7 of 7