HomeMy WebLinkAboutNC0022900_Inspection_20190510EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0022900 19/05/09 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Sugar Mountain WWTP
291 Norwood Hollow Rd
Banner Elk NC 28604
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
11:00AM 19/05/09 17/10/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Christian Alexander Montgomery/ORC/828-260-7936/
Other Facility Data
11:45AM 19/05/09 22/09/30
Name, Address of Responsible Official/Title/Phone and Fax Number
J Bryce Mendenhall,4944 Parkway Plz Blvd Charlotte NC 28217/VP/704-319-0517/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenance
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Daniel J Boss ARO WQ//828-296-4658/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 3BAE30C0-86A2-4A5B-B11E-EB6D4F265E09
5/13/2019
5/13/2019
NPDES yr/mo/day
19/05/09
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
I met with Christian Montgomery and conducted a compliance evaluation inspection at the Sugar
Mountain WWTP on 5/9/2019. This was a follow up inspection to the August 2018 inspection.
The chlorine contact chambers have not been repaired. A makeshift fence has been put up around the
contact chambers to keep people from walking on them. This is an appropriate temporary measure,
but not an adequate permanent measure. I have not received any information from Carolina Water
Service with regards to a permanent solution to this structural deficiency. If CWS does not feel that the
deteriorating concrete is a safety concern, please send our office an evaluation by an engineer
assuring its current structural integrity.
The wasting lines, air line to the digester, and skimmer for the clarifier have all been repaired.
The screening areas should be kept cleaner as there were some rags strewn around the ground near
the bar screens.
NC0022900 17 (Cont.)
Page#2
DocuSign Envelope ID: 3BAE30C0-86A2-4A5B-B11E-EB6D4F265E09
Permit:NC0022900
Inspection Date:05/09/2019
Owner - Facility:
Inspection Type:
Sugar Mountain WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
The bar screen area did not have acceptable housekeeping. The rest of the plant looked
fine as far as cleanliness.
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
The bar screen areas should be kept cleaner.Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Page#3
DocuSign Envelope ID: 3BAE30C0-86A2-4A5B-B11E-EB6D4F265E09
Permit:NC0022900
Inspection Date:05/09/2019
Owner - Facility:
Inspection Type:
Sugar Mountain WWTP
Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Clarifier skimmer had been repaired.Comment:
Disinfection-Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Chlorine contact chambers still have deteriorating concrete and appear to be a safety risk.
This was also noted in the August 2018 inspection. The cable fences are only appropriate
as a temporary measure.
Comment:
Page#4
DocuSign Envelope ID: 3BAE30C0-86A2-4A5B-B11E-EB6D4F265E09