May 13, 2019
Chad Simmons, Town Manager
Town of Murphy
PO Box 130
Murphy, NC 28906-0130
SUBJECT: Compliance Inspection Report
Murphy WWTP
NPDES WW Permit No. NC0020940
Cherokee County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Murphy WWTP on
5/03/2019. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0020940. The findings and comments noted
during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection
Report". Please carefully reviews any comments and recommendations noted within the summary. There were
no significant issues or findings noted during the inspection and therefore, a response to this inspection report
is not required.
If you should have any questions, please do not hesitate to me at 828-296-4686 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist I
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
EC: WQS-ARO Server
LF
G:\WR\WQ\Cherokee\Wastewater\Municipal\Murphy WWTP 20940\Inspections\May 3, 2019\20190513_NC0020940_CEI
DocuSign Envelope ID: 03688CF9-84A1-4755-9A20-33556BC49934
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0020940 19/05/03 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Murphy WWTP
Payne St
Murphy NC 28906
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:00AM 19/05/03 13/12/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Tyler B White/ORC/828-837-5035/
Other Facility Data
11:15PM 19/05/03 17/08/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Tyler White,PO Box 130 Murphy NC 289060130//828-837-5035/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Mikal Willmer Division of Water Quality//828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 03688CF9-84A1-4755-9A20-33556BC49934
5/13/2019
5/13/2019
NPDES yr/mo/day
19/05/03
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Inspector Mikal Willmer, with the Asheville Regional Office, conducted a compliance evaluation
inspection of the Town of Murphy's WWTP. This inspection was conducted to determine whether the
facility is being operated and maintained in compliance with NPDES Permit No. NC0020940. Tyler
White, ORC, was present and assisted in the inspection.
Overall the facility is being operated and maintained in compliance.
Records were organized and up to date. Staff are performing routine maintenance and general
housekeeping around the facility. There were only a few items noted during the inspection that should
be considered for further review.
Annual Calibration: If not already being provided, the Town needs to request a calibration report from
Carolina Technical Services. This report verifies the flow measuring device is reading within 10% of the
true value.
Headworks: Staff have attempted to contain debris from the mechanical bar screen as best as
possible; however, debris is still leaving the concrete pad directly under the screen and dumpster. This
needs to be addressed in future budgets to prevent the generation of nuisance conditions and to help
staff more easily dispose of debris.
Hypochlorite: The bulk hypochlorite tank sits on a concrete pad; however, there is no additional means
of containment should the tank rupture or a leak occur. Recommend secondary containment to prevent
a significant spill to the ground or surface waters.
Drying Bed: Recommend an alternative backup solids storage solution during future upgrades, if
additional solids storage is needed for the facility. The current bed does not appear to be easily
maintainable.
NC0020940 17 (Cont.)
Page#2
DocuSign Envelope ID: 03688CF9-84A1-4755-9A20-33556BC49934
Permit:NC0020940
Inspection Date:05/03/2019
Owner - Facility:
Inspection Type:
Murphy WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Setteable Solids and DO are monitored.Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Permit expired August 31, 2017 and is currently under review in Raleigh. A staff report will be
generated for reference and made available to the permit writers.
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Page#3
DocuSign Envelope ID: 03688CF9-84A1-4755-9A20-33556BC49934
Permit:NC0020940
Inspection Date:05/03/2019
Owner - Facility:
Inspection Type:
Murphy WWTP
Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review?
Annual report is posted on the Town's website and is available at Town Hall.Comment:
Influent Sampling Yes No NA NE
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is sampling performed according to the permit?
influent sampling is set to time composite.Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
The mechanical screen keeps most of the debris out of the SBRs; however, there is no
additional grit chamber and the screened debris is difficult to transfer to the dumpster with
the current setup. The ORC, Tyler White, reports issues with excessive rags from the jail. A
significant amount of debris is still making it on the ground. Staff have attempted to create an
easier conveyance for the debris, but it does not completely contain all items.
Comment:
Sequencing Batch Reactors Yes No NA NE
Type of operation:Duplex
Is the reactor effluent free of solids?
Does minimum fill time correspond to the peak hour flow rate of the facility?
Is aeration and mixing cycled on and off during fill?
The operator understands and can explain the process?
Page#4
DocuSign Envelope ID: 03688CF9-84A1-4755-9A20-33556BC49934
Permit:NC0020940
Inspection Date:05/03/2019
Owner - Facility:
Inspection Type:
Murphy WWTP
Compliance Evaluation
Sequencing Batch Reactors Yes No NA NE
SBRs mix/fill, react, settle and decant. One fills while the other settles. SBRs contain mixers
and diffusers for aeration. A batch is approximately 6 hours. Diffusers have not been
replaced/repaired since system was installed. Town is budgeting to rebuild/replace
diffusers. Transducers with float back-ups are used as high-level alarms. No remote
notification, operators must manually check PLC. Significant grease noted in SBRs at the
time of the inspection. The Town is starting a FOGs program to help reduce O&G. Several
restaurants may need to pump grease traps more frequently.
Comment:
Pumps-RAS-WAS Yes No NA NE
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Staff waste from SBRs about once a day.Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Do not have to press solids very often. When needed, solids are pressed and sent to the
landfill.
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Two basins gravity feed to chlorine contact chamber. If level rises, both basins are
connected to handle overflow.
Comment:
Disinfection-Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant?
Page#5
DocuSign Envelope ID: 03688CF9-84A1-4755-9A20-33556BC49934
Permit:NC0020940
Inspection Date:05/03/2019
Owner - Facility:
Inspection Type:
Murphy WWTP
Compliance Evaluation
Disinfection-Liquid Yes No NA NE
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Liquid chlorine feed is flow proportional. Recommend additional containment around the
hypochlorite bulk storage container to prevent major leak/spill to the ground or surface
waters. Tank sits approximately 100' from the Hiwassee.
Comment:
De-chlorination Yes No NA NE
Type of system ?Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?
System is flow proportional. Sodium bisulfite has containment in the event of a leak.Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Meter was last calibrated on 5/2/2018 by Mr. Kruchkow with Carolina Technical Services.
ORC reports they are scheduled to come out to recalibrate this month. If not already done
so, the Town needs to obtain a calibration report from Carolina Technical for their records.
This helps to demonstrate the meter is recording measurements within 10% of the true
value.
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Page#6
DocuSign Envelope ID: 03688CF9-84A1-4755-9A20-33556BC49934
Permit:NC0020940
Inspection Date:05/03/2019
Owner - Facility:
Inspection Type:
Murphy WWTP
Compliance Evaluation
Effluent Sampling Yes No NA NE
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Environmental Inc. is collecting samples for the Town of Murphy. The fridge was reading 0.5
degrees Celsius at the time of the inspection.
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Effluent pipe is located under water; however, access down to the river bank is maintained.Comment:
Drying Beds Yes No NA NE
Is there adequate drying bed space?
Is the sludge distribution on drying beds appropriate?
Are the drying beds free of vegetation?
# Is the site free of dry sludge remaining in beds?
Is the site free of stockpiled sludge?
Is the filtrate from sludge drying beds returned to the front of the plant?
# Is the sludge disposed of through county landfill?
# Is the sludge land applied?
(Vacuum filters) Is polymer mixing adequate?
One of the original drying beds was closed out during upgrades, but the other was kept
open. Doesn't appear new sludge has been placed within the bed. Recommend finding an
alternative solution to the drying bed during future upgrades if additional solids storage
capacity is needed. The bed has debris and weeds growing in it and doesn't appear easily
maintainable.
Comment:
Page#7
DocuSign Envelope ID: 03688CF9-84A1-4755-9A20-33556BC49934
Certificate Of Completion
Envelope Id: 03688CF984A147559A2033556BC49934 Status: Completed
Subject: Please DocuSign: 20190513_NC0020940_CEI.ltr.docx, 20190510_NC0020940_CEI.inspect.pdf
Source Envelope:
Document Pages: 8 Signatures: 3 Envelope Originator:
Certificate Pages: 2 Initials: 0 Mikal Willmer
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-05:00) Eastern Time (US & Canada)
217 W. Jones Street
Raleigh, NC 27699
Mikal.willmer@ncdenr.gov
IP Address: 149.168.204.10
Record Tracking
Status: Original
May 13, 2019 | 10:50
Holder: Mikal Willmer
Mikal.willmer@ncdenr.gov
Location: DocuSign
Signer Events Signature Timestamp
Mikal Willmer
mikal.willmer@ncdenr.gov
Environmental Specialist
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 149.168.204.10
Sent: May 13, 2019 | 10:51
Viewed: May 13, 2019 | 10:51
Signed: May 13, 2019 | 10:51
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
G. Landon Davidson
landon.davidson@ncdenr.gov
Asheville Regional Office, Regional Supervisor
DEQ, Division of Water Resources, Water Quality
Regional Operatoins
Security Level: Email, Account Authentication
(None)
Signature Adoption: Uploaded Signature Image
Using IP Address: 149.168.204.10
Sent: May 13, 2019 | 10:51
Viewed: May 13, 2019 | 10:58
Signed: May 13, 2019 | 10:58
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp