HomeMy WebLinkAboutNC0089095_Inspection_20190510EPA United States Environmental Protection Agency Washington, D.C. 20460 Water Compliance Inspection Report Form Approved. OMB No. 2040-0057 Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 N 52 NC0089095 19/05/03 C S31112171819 20 21 66 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved------------------- N67707172 73 74 75 80 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES permit Number) High Vista Falls WWTP Creasman Hill Rd Mills River NC 28759 Entry Time/Date Permit Effective Date Exit Time/Date Permit Expiration Date 09:30AM 19/05/03 15/11/01 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) /// Vincent L Edwards/ORC/828-697-3077/ Other Facility Data 10:00AM 19/05/03 20/10/31 Name, Address of Responsible Official/Title/Phone and Fax Number Patty Carland,117 Kira Ln Hendersonville NC 28739//828-890-4810/Contacted No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Flow Measurement Operations & Maintenance Self-Monitoring Program Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date Daniel J Boss ARO WQ//828-296-4658/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page#1 DocuSign Envelope ID: ABA80685-6956-4815-8B9C-E19C87533D5B 5/10/2019 5/10/2019 NPDES yr/mo/day 19/05/03 Inspection Type C3111218 1 Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On May 3, 2019 I met with Vince Edwards for a follow up inspection of the High Vista Falls WWTP. Mr. Edwards said that both blowers had been tripping out due to overheating, but that issue has now been corrected and now he is getting lower ammonia numbers in the effluent. The equalization basin had 7000 gallons pumped out of it, but there is still a lot of grease in it. Mr. Edwards said that it is scheduled to be pumped again on 5/7/19. *On 5/8/19 I visited the WWTP again and the EQ basin had been pumped out again. This time the EQ basin was relatively clear of grease and rags.* The sampling is still not flow proportional and there is no indication of any progress toward flow proportional sampling. The tertiary filters are still broken. Mr. Edwards says he is researching a solution for them. Mr. Edwards reports that he is still having daily flows that exceed the permitted flow, despite relatively dry weather in the last couple weeks. The collection system needs to be thoroughly inspected for sources of I&I. NC0089095 17 (Cont.) Page#2 DocuSign Envelope ID: ABA80685-6956-4815-8B9C-E19C87533D5B Permit:NC0089095 Inspection Date:05/03/2019 Owner - Facility: Inspection Type: High Vista Falls WWTP Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Equalization Basins Yes No NA NE Is the basin aerated? Is the basin free of bypass lines or structures to the natural environment? Is the basin free of excessive grease? Are all pumps present? Are all pumps operable? Are float controls operable? Are audible and visual alarms operable? # Is basin size/volume adequate? Mr. Edwards said that the basin had 7000 gallons pumped out of it on 5/1/19. There is still a substantial amount of grease remaining and it is scheduled to be pumped out again on 5/7/19. Comment: Filtration (High Rate Tertiary)Yes No NA NE Type of operation: Is the filter media present? Is the filter surface free of clogging? Is the filter free of growth? Is the air scour operational? Is the scouring acceptable? Is the clear well free of excessive solids and filter media? The tertiary filters are still broken.Comment: Effluent Sampling Yes No NA NE Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Page#3 DocuSign Envelope ID: ABA80685-6956-4815-8B9C-E19C87533D5B Permit:NC0089095 Inspection Date:05/03/2019 Owner - Facility: Inspection Type: High Vista Falls WWTP Compliance Evaluation Effluent Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Sampling is still not flow proportional. There is no indication of any progress being made on this issue. Comment: Page#4 DocuSign Envelope ID: ABA80685-6956-4815-8B9C-E19C87533D5B