HomeMy WebLinkAboutNC0004944_Compliance Evaluation Inspection_20190508ROY COOPED
66weilar
K41C lAEL S. REGAN
Secretary
LINDA CULPEPPER
Cb7{CfiOr
Mr. Huston Roberts
Salisbury Investments I, LLC
5320 Old Pineville Road
Charlotte, NC 28217
NORTH CAROUNA
Environmental Qual"
May 8, 2019
SUBJECT: Compliance Inspection Report
Edge Water Treating, LLC WWTP
NPDES WW Permit No. NC0004944
Rowan County
Dear Mr. Roberts:
The North Carolina Division of Water Resources conducted an inspection of the Edge Water Treating WWTP on
April 30, 2019. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0004944. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
During the subject compliance inspection there was noted an accumulation of algae and aquatic vegetation in
the treatment ponds or lagoons. Please note that under low flow conditions die -off of aquatic vegetation may
result in elevated BOD and ammonia readings with lower pH levels. Algae and aquatic vegetation should be
managed to keep aquatic vegetation and a minimum.
If you should have any questions, please do not hesitate to contact Roberto Scheller with the Water
Quality Regional Operations Section in the Mooresville Regional Office at 704-663-1699 or via email at
roberto.scheller@ncdenr.gov.
ATTACHMENT
Cc: Laserfiche
Sincerely,
DocuSigned by:
for
F161FB69A2D84A3...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
NorthCaro I,naDepartirentofErv:ror.irerts'Qua: ly I MrsonofWater Resources
Woo reav:15ERegom:Off.-oe 1 610 Ea2l DeDler Avenue, Su;te 3011 Mooresv �e,North 03rodina28115
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NC0004944 111 12 I 19/04/30 I17 18 I S I 19 I G I 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70I�_71 I 72 r 73I i74 751 I I I I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:OOAM 19/04/30
18/07/01
Edge Water Treating, LLC
7401 Statesville Blvd
Exit Time/Date
Permit Expiration Date
Salisbury NC 28147
11:10AM 19/04/30
22/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
William Keith McDonald/ORC/336-905-1717/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Greg Coleman,5320 Old Pineville Rd Charlotte NC 28217//704-609-7971/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Roberto Scheller 5,u MRO WQ//252-946-6481/ 5/1/2019
91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone an �ftSiA%ygd by: Date
CA*-.uo H P44-t4
W. Corey Basinger Division of Water Quality//704-2; 5.8.19
for WCB
1`1611`1369AMUA3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0004944 I11 121 19/04/30 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NC0004944 Owner -Facility: Edge Water Treating, LLC
Inspection Date: 04/30/2019 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: New permit becomes effective May 1, 2019 and expires November 30, 2022.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: Analysis conducted by Statesville Analytical and field analysis conducted under field lab
certification #200.
Bar Screens
Type of bar screen
Yes No NA NE
Page# 3
Permit: NC0004944
Inspection Date: 04/30/2019
Owner -Facility: Edge Water Treating, LLC
Inspection Type: Compliance Evaluation
Bar Screens
Yes No NA NE
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Grit Removal
Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
0
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment:
Equalization Basins
Yes No NA NE
Is the basin aerated?
❑
❑
0
❑
Is the basin free of bypass lines or structures to the natural environment?
❑
❑
❑
Is the basin free of excessive grease?
❑
❑
❑
Are all pumps present?
❑
❑
❑
Are all pumps operable?
❑
❑
❑
Are float controls operable?
❑
❑
❑
Are audible and visual alarms operable?
❑
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment: EQ tanks not in use at time of inspection.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Surface
Is the basin free of dead spots? ❑ ❑ 0 ❑
Are surface aerators and mixers operational? 0 ❑ ❑ ❑
Page# 4
Permit: NC0004944
Inspection Date: 04/30/2019
Owner -Facility: Edge Water Treating, LLC
Inspection Type: Compliance Evaluation
Aeration Basins
Yes No NA NE
Are the diffusers operational?
❑
❑
0
❑
Is the foam the proper color for the treatment process?
❑
❑
0
❑
Does the foam cover less than 25% of the basin's surface?
❑
❑
0
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Comment: One aeration basin running aerator on timer. Facility has low flow of around 2000 gals. per
day with Dermitted flow of 0.5 MGD. One of the three aeration basins in oDeration.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
❑
❑
0
❑
Are pumps operational?
❑
❑
0
❑
Are there adequate spare parts and supplies on site?
❑
❑
0
❑
Comment: RAS pumps are to be replaced or repaired.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
❑
❑
❑
Is the site free of evidence of short-circuiting?
❑
❑
❑
Is scum removal adequate?
❑
❑
❑
Is the site free of excessive floating sludge?
❑
❑
❑
Is the drive unit operational?
❑
❑
❑
Is the return rate acceptable (low turbulence)?
❑
❑
0
❑
Is the overflow clear of excessive solids/pin floc?
❑
❑
0
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
❑
❑
❑
Comment: Three secondary clarifiers with one out of service.
Page# 5
Permit: NC0004944 Owner -Facility: Edge Water Treating, LLC
Inspection Date: 04/30/2019 Inspection Type: Compliance Evaluation
Lagoons
Yes No NA NE
Type of lagoons?
Aerated
# Number of lagoons in operation at time of visit?
3
Are lagoons operated in?
Series
# Is a re -circulation line present?
❑
❑
0
❑
Is lagoon free of excessive floating materials?
❑
0
❑
❑
# Are baffles between ponds or effluent baffles adjustable?
❑
❑
0
❑
Are dike slopes clear of woody vegetation?
0
❑
❑
❑
Are weeds controlled around the edge of the lagoon?
0
❑
❑
❑
Are dikes free of seepage?
0
❑
❑
❑
Are dikes free of erosion?
0
❑
❑
❑
Are dikes free of burrowing animals?
0
❑
❑
❑
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple
0
❑
❑
❑
locations?
# If excessive algae is present, has barley straw been used to help control the growth?
❑
0
❑
❑
Is the lagoon surface free of weeds?
0
❑
❑
❑
Is the lagoon free of short circuiting?
0
❑
❑
❑
Comment: At time of inspection algae growth was present on ponds. Please note that algea die -off may
result in elevated effluent BOD's and ammonia readinas.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: At time of inspection sampler was recorded at 4 degrees Celsius.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
rims ► rem ►/_m►1=0
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 6
Permit: NC0004944
Inspection Date: 04/30/2019
Flow Measurement - Effluent
Owner -Facility: Edge Water Treating, LLC
Inspection Type: Compliance Evaluation
Comment: Flow meter last calibrated on 08/09/2018. At time of i
discharge.
Yes No NA NE
ction there was no effluent
Page#