HomeMy WebLinkAboutWQ0018352_BIMS Report_20190507Compliance Inspection Report
Permit: WQ0018352
SOC:
County: Cleveland
Region: Mooresville
Contact Person: Mike Gibert
Directions to Facility:
Effective: 02/06/15 Expiration: 12/31/19 owner: Town of Boiling Springs
Effective: Expiration: Facility: Town of Boiling Springs Residuals Land Application
PO Box 1014
System Classifications: LA,
Primary ORC: Michael Todd Humphries
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Title:
Certification: 994587
Boiling Springs NC 28017
Phone: 704-434-2357
Phone: 704-300-8641
Inspection Date: 04/25/2019 Entry Time: 11:39AM Exit Time: 12:39PM
Primary Inspector: Maria Schutte Phone: 704-663-1699
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Land Application of Residual Solids (503)
Facility Status: Compliant Not Compliant
Question Areas:
Miscellaneous Questions Record Keeping Treatment
Land Application Site Pathogen and Vector Attraction Storage
(See attachment summary)
Page 1 of 5
Permit: WQ0018352 Owner - Facility: Town of Boiling Springs
Inspection Date: 04/25/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Staff of the Mooresville Regional Office met with Boiling Springs WWTP staff on April 25th, 2019 to conduct a compliance
inspection including a residuals land application. Active application was halted due to spreader truck maintenance; however,
field site JP-1 was viewed for residuals application conducted the previous day. Plant storage, paperwork, field site
conditions and buffers appeared to meet program requirements at the time of inspection.
There is a typing error in the permit which states an expiration date of December 31 st, 2020. However, the cover letter and
our permitting data base show the permit is due to expire on December 31 st, 2019. A renewal application is due 6 months
prior to expiration on June 30th, 2019.
Please contact maria.schutte@ncdenr.gov or 704-663-1699 should you have any questions.
Sincerely,
Maria Schutte
Page 2 of 5
Permit: WQ0018352 Owner - Facility: Town of Boiling Springs
Inspection Date: 04/25/2019 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Distribution and Marketing
❑
Land Application
Record Keeping
Yes No NA NE
Is GW monitoring being conducted, if required?
❑
❑ ❑
Are GW samples from all MWs sampled for all required parameters?
❑
❑ ❑
Are there any GW quality violations?
❑
❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is a copy of current permit on -site?
❑ ❑ ❑
Are current metals and nutrient analysis available?
❑ ❑ ❑
Are nutrient and metal loading calculating most limiting parameters?
❑ ❑ ❑
a. TCLP analysis?
❑ ❑ ❑
b. SSFA (Standard Soil Fertility Analysis)?
❑ ❑ ❑
Are PAN balances being maintained?
❑ ❑ ❑
Are PAN balances within permit limits?
❑ ❑ ❑
Has land application equipment been calibrated?
❑
❑ ❑
Are there pH records for alkaline stabilization?
❑
❑ ❑
Are there pH records for the land application site?
❑ ❑ ❑
Are nutrient/crop removal practices in place?
❑ ❑ ❑
Do lab sheets support data reported on Residual Analysis Summary?
❑ ❑ ❑
Are hauling records available?
❑ ❑ ❑
Are hauling records maintained and up-to-date?
❑ ❑ ❑
# Has permittee been free of public complaints in last 12 months?
❑ ❑ ❑
Has application occurred during Seasonal Restriction window?
❑
0 ❑ ❑
Comment: There were no new analytical results at the time of inspection.
The most current data was
reviewed in the 2018 Annual Report.
Pathogen and Vector Attraction
Yes No NA NE
a. Fecal coliform SM 9221 E (Class A or B)
0
❑ ❑ ❑
Class A, all test must be <1000 MPN/dry gram
❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
Fecal coliform SM 9222 D (Class B only)
❑ ❑ ❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
b. pH records for alkaline stabilization (Class A)
❑
❑ ❑
c. pH records for alkaline stabilization (Class B)
❑
❑ ❑
Temperature corrected
❑
Page 3 of 5
Permit: WQ0018352 Owner - Facility: Town of Boiling Springs
Inspection Date: 04/25/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
d. Salmonella (Class A, all test must be < 3MPN/4 gram day) ❑ ❑ 0 ❑
e. Time/Temp on: ❑ ❑ 0 ❑
Digester (MCRT) ❑
Compost ❑
Class A lime stabilization ❑
f. Volatile Solids Calculations ❑ ❑ 0 ❑
g. Bench -top Aerobic/Anaerobic digestion results ❑ ❑ 0 ❑
Comment: PVAR is demonstrated by fecal and SOUR testing.
Treatment
Yes No NA NE
Check all that apply
Aerobic Digestion
Anaerobic Digestion
❑
Alkaline Pasteurization (Class A)
❑
Alkaline Stabilization (Class B)
❑
Compost
❑
Drying Beds
❑
Other
❑
Comment:
Land Application Site
Yes No NA NE
Is a copy of the permit on -site during application events?
❑ ❑ ❑
Is the application site in overall good condition?
❑ ❑ ❑
Is the site free of runoff/ponding?
❑ ❑ ❑
If present, is the application equipment in good operating condition?
❑
❑ ❑
Are buffers being maintained?
❑ ❑ ❑
Are limiting slopes buffered?
10% for surface application
❑ ❑ ❑
18% for subsurface application
❑ ❑ ❑
Are there access restrictions and/or signs?
❑ ❑ ❑
Is the application site free of odors or vectors?
❑ ❑ ❑
Have performance requirements for application method been met?
For injection?
❑
❑ 0 ❑
For incorporation?
❑
❑ ❑
Does permit require monitoring wells?
❑
❑ ❑
Have required MWs been installed?
❑
❑ ❑
Are MWs properly located w/ respect to RB and CB?
❑
❑ ❑
Are MWs properly constructed (including screened interval)?
❑
❑ ❑
Page 4 of 5
Permit: WQ0018352 Owner - Facility: Town of Boiling Springs
Inspection Date: 04/25/2019 Inspection Type : Compliance Evaluation
Is the surrounding area served by public water?
If Annual Report indicates overapplication of PAN, are wells nearby that may be impacted?
Are soil types consistent w/ Soil Scientist report/evaluation?
Is the water table greater than 173' bls.
Is application occurring at the time of the inspection?
Reason for Visit: Routine
Comment: Their spreader truck was in the shop for repairs. Land application conducted yesterday was
viewed. Site conditions and flapped buffers at field JP-1 appeared to meet program
requirements at the time of inspection.