HomeMy WebLinkAboutWQ0033804_Compliance Evaluation Inspection_20190507
May 7, 2019
Kathleen A Drysdale
NC Asset Mgnt LLC
12502 Carriage Hill
Houston, TX 77077
SUBJECT: Compliance Inspection Report
Laurel Mountain Retreat
Non-discharge Permit No. WQ0033804
Buncombe County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Laurel Mountain Retreat
on 4/17/2019. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in Non-discharge Permit No. WQ0033804. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Mikal Willmer with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist I
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
EC: WQS-ARO Server
LF
Bob Barr
G:\WR\WQ\Buncombe\Wastewater\Non-discharge\Laurel Mountain Retreat formerly Deerborne Cottages, LLC\Inspections\20190507_WQ0033804_CEI
DocuSign Envelope ID: 8B8B394E-3C4B-41D6-87C1-D7728515AD15
Compliance Inspection Report
Permit:WQ0033804 Effective:02/21/17 Expiration:01/31/22 Owner :NC Asset Mgnt LLC
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Buncombe
Asheville
Kathleen A Drysdale
Effective:Expiration:Facility:Laurel Mountain Retreat
6 Deerborne Ln
Weaverville NC 28787
Title:Phone:281-900-6248Member
From I-26 take the Marshall exit (US Hwy 70/25). Go approximately 3.5 miles and exit right onto Sheppard Branch Road (SR 1741).
Go 0.25 miles to Lower Sheppard Branch Road. Facility is on the left.
Secondary ORC(s):
Phone:993157Certification:Richard Morgan SwillingPrimary ORC:
SI,System Classifications:
On-Site Representative(s):
Related Permits:
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
04/17/2019 09:20AM 11:00AM
Mikal Willmer 828-296-4686
Beverly Price
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Wastewater Irrigation
Compliance Evaluation
Question Areas:
Treatment Flow Measurement-Effluent Treatment Flow Measurement-Influent Miscellaneous Questions
Treatment Flow Measurement-Water
Use Records
Treatment Treatment Filters
Record Keeping End Use-Irrigation Treatment Disinfection
Treatment Flow Measurement Storage Standby Power
(See attachment summary)
Page 1 of 7
DocuSign Envelope ID: 8B8B394E-3C4B-41D6-87C1-D7728515AD15
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0033804
04/17/2019 Compliance Evaluation
NC Asset Mgnt LLC
Routine
Inspection Summary:
Inspectors Mikal Willmer and Beverly Price, with the Asheville Regional Office, conducted a compliance evaluation
inspection of the wastewater drip irrigation system that services Laurel Mountain Retreat. This inspection was conducted to
determine whether the system is being operated and maintained in compliance with Non-discharge Permit No. WQ0033804.
Bob Barr (RPB Systems), Rick Swilling (ORC) and Mike Schraver (Facility Maintenance Manager) were present and
assisted in the inspection.
Overall the system is being operated and maintained in compliance with Permit No. WQ0033804. The following additional
items were noted at the time of the inspection.
Vegetation: It is highly recommended vegetation be cut back and removed from around the treatment units. This would allow
easier accessibility to the treatment units for routine maintenance and observation. Additionally, woody vegetation could
potentially compromise precast concrete tanks as the seams begin to deteriorate.
Calibration: Turbidimeter and flow meter were both calibrated in April 2019 by RPB Systems.
Rain Sensor: This did not appear to be working at the time of the inspection and was replaced. Staff should begin checking
this sensor periodically to determine if it's operational.
Recirculation Tank: The visual alarm was working at the time of the inspection. Audible alarm appeared to be inoperable. The
audible alarm should be fixed. Inspectors recommend moving the visual alarm to a more conspicuous location or removing
the vegetation directly in front of the panel.
Dosing Tank: Permit indicates there is an audible and visual alarm associated with the dosing tank high water alarm. The
visual alarm was tested and operable; however, there did not appear to be an audible alarm installed. Recommend installing
an audible alarm if not already present.
Drip Fields: Currently only field 6 is being utilized. Recommend utilizing all certified fields for more even hydraulic and
nutrient loading. Additionally, the facility's current floating annual total is approximately 19.3 inches. This should be
monitored closely so the yearly max (23.53) is not exceeded.
Wet-weather Pond: The pond had more than adequate freeboard. Inspectors noted several minor tears within the liner above
the normal high-water line. These should be monitored and/or repaired to prevent further damage.
Earthen bank: Please note, any woody vegetation has the potential to structurally compromise the dam and inhibits staff’s
ability to inspect the integrity of the dam. It is recommended any small trees and shrubs be removed from the bank and
reseeded with grass. Removal of any larger trees from the dam should be assessed by an engineer.
Page 2 of 7
DocuSign Envelope ID: 8B8B394E-3C4B-41D6-87C1-D7728515AD15
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0033804
04/17/2019 Compliance Evaluation
NC Asset Mgnt LLC
Routine
Type Yes No NA NE
Reuse (Quality)
Infiltration System
Activated Sludge Spray, LR
Lagoon Spray, LR
Single Family Spray, LR
Activated Sludge Spray, HR
Recycle/Reuse
Single Family Drip
Activated Sludge Drip, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
The wet-weather storage pond has a synthetic liner (permit description says clay). Staff should
verify the effluent filters are being checked regularly to ensure the tanks are functioning as
designed. Facility staff report solids have never been removed from system. Staff should also
verify solids depth within all the tanks to determine if they need to be pumped. Floating sludge
was visible in the dosing tank. No expansion, still only four cabins on system. Zones 1A, 1B, 2, 3,
4 and 5 have not been certified.
Comment:
Treatment Flow Measurement-Influent Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment:
Treatment Flow Measurement-Water Use Records Yes No NA NE
Is water use metered?
Are the daily average values properly calculated?
Facility staff are taking weekly water meter readings for a more accurate monthly average flow.Comment:
Treatment Flow Measurement-Effluent Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Page 3 of 7
DocuSign Envelope ID: 8B8B394E-3C4B-41D6-87C1-D7728515AD15
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0033804
04/17/2019 Compliance Evaluation
NC Asset Mgnt LLC
Routine
Does flowmeter appear to monitor accurately?
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is generator tested weekly by interrupting primary power source?
Is generator operable?
Does generator have adequate fuel?
Log indicates the generator is being tested monthly. Liquid propane fuel tank on-site. Fuel level
was approximately 90% at the time of the inspection.
Comment:
Treatment Filters Yes No NA NE
Is the filter media present?
Is the filter media the correct size and type?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids?
Is the mud well free of excessive solids and filter media?
Does backwashing frequency appear adequate?
System utilizes EZ Treat pods which contain Styrofoam media. System does not backwash,
media is replaced as needed.
Comment:
Treatment Disinfection Yes No NA NE
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-____-____)
Page 4 of 7
DocuSign Envelope ID: 8B8B394E-3C4B-41D6-87C1-D7728515AD15
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0033804
04/17/2019 Compliance Evaluation
NC Asset Mgnt LLC
Routine
If yes, then when was the RMP last updated?
UV is used for disinfection. Six ballasts are installed, staff recently replaced two. #5 was turned
off at the time of the inspection. Facility staff have no easy indicators that bulbs are going bad (no
intensity reading and/or light indicator). Higher fecal numbers and burned bulbs are the only
indication bulbs have failed.
Comment:
Record Keeping Yes No NA NE
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
The ORC had a draft copy of the most recent permit. A finalized copy should be kept on file to
avoid any discrepancies.
Comment:
End Use-Irrigation Yes No NA NE
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Page 5 of 7
DocuSign Envelope ID: 8B8B394E-3C4B-41D6-87C1-D7728515AD15
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0033804
04/17/2019 Compliance Evaluation
NC Asset Mgnt LLC
Routine
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
Permit does not specify crop type. Crop is mainly Pines and hardwoods. Closest supply wells
are >500' away from the certified drip fields. Staff recently cleared out brush and weeds to more
easily inspect and repair damaged drain lines.
Comment:
ST-1 -
Storage Yes No NA NE
Storage Type?Pond
Gallons
Storage amount?77600
# At what point is side-stream wastewater returned to treatment?
Is there a Spill Control Plan?
Aerated or Mixed?NONE
If aeration is present, is it adequate?
If present, are diffusers cleaned regularly?
Is influent structure acceptable?
Are banks/berms free of seepage and erosion?
Are banks/berms free of excessive vegetation?
Is pond lined?
Liner Type Apron, synthetic
Is liner acceptable?
Are baffles/curtains acceptable?
Does the pond have a freeboard marker?
Required freeboard?2
Page 6 of 7
DocuSign Envelope ID: 8B8B394E-3C4B-41D6-87C1-D7728515AD15
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0033804
04/17/2019 Compliance Evaluation
NC Asset Mgnt LLC
Routine
Feet
Feet
Actual freeboard?7
Is there suitable grassed vegetation?
Is the vegetation maintained?
Is the area free of excessive weeds and/or woody species?
Is the area free from signs of overflow?
Is color acceptable?
Are floating mats acceptable?
No excessive buildup of solids?
Are aerators/mixers acceptable?
Is effluent structure acceptable?
If present, is pond cover acceptable?
Less than two feet of water in the wet weather storage pond. The system was automatically
dosing the drip field at the time of the inspection. Staff report there is currently no means of
irrigating directly from the wet weather storage pond. There is an established stand of grass on
the earthen dam; however, pines are growing along the bank. See summary for further details.
Comment:
Page 7 of 7
DocuSign Envelope ID: 8B8B394E-3C4B-41D6-87C1-D7728515AD15
Certificate Of Completion
Envelope Id: 8B8B394E3C4B41D687C1D7728515AD15 Status: Completed
Subject: Please DocuSign: 20190507_WQ0033804_CEI.ltr.docx, 20190507_WQ0033804_CEI.pdf
Source Envelope:
Document Pages: 8 Signatures: 1 Envelope Originator:
Certificate Pages: 2 Initials: 2 Mikal Willmer
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-05:00) Eastern Time (US & Canada)
217 W. Jones Street
Raleigh, NC 27699
Mikal.willmer@ncdenr.gov
IP Address: 149.168.204.10
Record Tracking
Status: Original
May 6, 2019 | 15:53
Holder: Mikal Willmer
Mikal.willmer@ncdenr.gov
Location: DocuSign
Signer Events Signature Timestamp
Mikal Willmer
mikal.willmer@ncdenr.gov
Environmental Specialist
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 149.168.204.10
Sent: May 6, 2019 | 15:54
Viewed: May 6, 2019 | 15:54
Signed: May 6, 2019 | 15:54
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
Beverly Price
bev.price@ncdenr.gov
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)Signature Adoption: Pre-selected Style
Using IP Address: 149.168.204.10
Sent: May 6, 2019 | 15:54
Viewed: May 6, 2019 | 16:25
Signed: May 6, 2019 | 16:25
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted May 6, 2019 | 15:54
Certified Delivered Security Checked May 6, 2019 | 16:25
Signing Complete Security Checked May 6, 2019 | 16:25
Envelope Summary Events Status Timestamps
Completed Security Checked May 6, 2019 | 16:25
Payment Events Status Timestamps