HomeMy WebLinkAboutNC0089290_Compliance Evaluation Inspection_20190318ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mr. Will Marklin, Mayor
Town of Mocksville
171 S Clement St.
Mocksville, NC 27028
e+
ww
NORTH CAROLINA
Environmental Qaato
March 18, 2019
SUBJECT: Compliance Evaluation Inspection
Hugh A. Lagle WTP
NPDES Permit No. NCO089290
Davie County
Dear Mr. Marklin,
Water Resources
P®rrnitting Section
On March 7, 2019, Kelli Park of this office, met with Joshua Powers, Operator in Responsible
Charge (ORC), to perform a Compliance Evaluation Inspection at the Hugh A. Lagle water
treatment plant. This type of inspection consists of two basic parts: an in -office file review and an
on -site inspection of the treatment facility. The attached EPA inspection form details the areas
that were evaluated during this inspection. Some pertinent findings from the inspection are
described in the inspection summary.
The inspection of the facility was satisfactory. If you have any questions regarding the inspection
or this report, please contact Kelli Park or me at (336) 776-9800 or by email at
kelli.parkCa-ncdenr.gov or Ion. sniderCa-ncdenr.gov.
Sincerely,
Lon Snider
Assistant Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments: EPA Water Compliance Inspection Report
cc: Central Files
WSRO
N' PPDE:i mn-�
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 2 15 1 3 I NC0089290 I11 12 19/03/07 17 18 ICJ 19 I G j 20I
211 1 1 1 1 1 I I I I I I I I I I I I I I I I I I I I i l l l l I I I I I I I I I I I �6
Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 CIA Reserved
67
70I � 71 I I 72 I N 1 731 I 174 75III
LJ L_I I I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
11:OOAM 19/03/07
17/06/01
Hugh A. Lagle WTP
Exit Time/Date
Permit Expiration Date
771 Sanford Ave
01:OOPM 19/03/07
21/12/31
Mocksville NC 27028
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
Joshua Powers/ORC/704-775-612B/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Christine W Bralley,171. S Clement St Mocksville NC
No
2702BH336-751-2259/3367519187
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Kelli A Park WSRO WQ//336-776-9689/
�64-14
Signature of M agement Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev /94) Previous editions are obsolete.
Page#
0
NPDES yr/mo/day Inspection Type (Cont.) 1
31 NCO089290 I11 12 19/03/07 17 18 1,. I
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On March 7, 2019, Kelli Park of this office, met with Joshua Powers, Operator in Responsible Charge
(ORC), to perform a Compliance Evaluation Inspection at the Hugh A. Lagle water treatment plant.
This type of inspection consists of two basic parts: an in -office file review and an on -site inspection of
the treatment facility. The attached EPA inspection form details the areas that were evaluated during
this inspection. Some pertinent findings from the inspection are described in the inspection summary.
The inspection of the facility was satisfactory. If you have any questions regarding the inspection or
this report, please contact Kelli Park or me at (336) 776-9800 or by email at kelli.park@ncdenr.gov or
lon.snider@ncdenr.gov.
Page# 2
r
Permit: NCO089290 Owner - Facility: Hugh A. Lagle WTP
Inspection Date: 03/07/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
M
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
M
❑
El
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Permit expires in 2021
Operations & Maintenance Yes, No NA NE
Is the plant generally clean with acceptable housekeeping? M. ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El ❑ 0 ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and,current?
❑
❑
❑
Are all records maintained for• 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
M
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
r
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
M
❑
on each shift?
Is the OFC visitation log available and current?
M
❑
❑
❑
Is the ORG certified at grade equal to or higher than the facility classification?
M
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Page# 3
Permit: NCO089290
Inspection Date: 03/07/2019
Record Keeping
Facility has copy of previous year's Annual Report on file for review?
Owner - Facility: Hugh A. Lagle wTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: EMA resources removes sludge from the decant tanks and are land applied under permit
WQ0039552. The annual report from EMA was available during the inspection
It is suggested that a log of any sludge pumping be maintained with the date and how much
sludge was pumped.
Sludge was pumped last in September 2017 and was reported by the ORC to need done
again soon. They are also planning on setting up a dewatering bag that sludge can be
pumped into if there is ever a delay in pumping and sludge builds up
Meritech is used for toxicity testing.
Calibration records were available for the chlorine temperature and pH meters
Disinfection -Gas
Yes No NA NE
Are cylinders secured adequately?
0
❑
❑
❑
Are cylinders protected from direct sunlight?
E
❑
❑
❑
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑
0
❑
If yes, then is there a Risk Management Plan on site?
❑
❑
0
0-
If yes, then what is the EPA twelve digit ID Number? (1 000--_)
If yes, then when was the RMP last updated?
Comment: There is a maximum of 1400 Ibs of chlorine gas on site at a time In the winter about 3-5 Ibs
of gas are used each day, and in the summer about 6-9 Ibs of gas are used each day
De -chlorination
Yes No NA NE
Type of system ?
Gas
Is the feed ratio proportional to chlorine amount (1 to 1)?
0
❑
❑
❑
Is storage appropriate for cylinders?
N
❑
❑
❑
# Is de -chlorination substance stored away from chlorine containers?
❑
❑
❑
Are the tablets the proper size and type?
❑
❑
0
❑
Comment: Calcium thiosulfate is used.
Are tablet de -chlorinators operational?
❑
❑
N
❑
Number of tubes in use?
Page#' 4
l�
Permit: NCO089290 Owner - Facility: Hugh A. Lagle WTP
Inspection Date: 03/07/2019 Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
M
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
M
❑
❑
❑
Comment: SCADA records flow constantly.
Flow meter was calibrated on 2/12/2019
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
M
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
M
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: Grab samples are taken and stored on ice
Statesville Analytical analyzes the water samples.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ M ❑
Comment:
Page# 5