Loading...
HomeMy WebLinkAboutNC0024911_NOV-2019-PC-0251 Response_20190422Metropolitan Sewerage District OF BUNCOMBE COUNTY, NORTH CAROLINA VF ONNTY, 0\" April 22; 2019 Landon Davidson, P.G. Regional Supervisor Asheville Regional Office Water Quality Regional Operations Section NCDEQ - Division of Water Resources 2090 U.S. Hwy. 70 Swannanoa, N.C. 28711 Dear Mr. Davidson: Metropolitan Sewerage District (MSD) received the Notice of Violation & Intent to Assess Civil Penalty dated April 11th, for the bypass occurring February 26, 2019, at the new headworks fine screens. The bypass occurred following a sequence of over -torque alarms on all three (3) fine screens placed in service February 19th. The new PLC control logic, commanding automated actions of moving parts, was thoroughly tested in the last week of January. That testing did not indicate any issues with the proper operation of the screens, flow control gates, or any associated appurtenances. The over -torque alarms experienced are related below: Fine Screen 1 had a screen over -torque alarm at: 3:47:19 2/26/19 Fine Screen 3 had a screen over -torque alarm at: 3:53:22 2/26/19 Fine Screen 2 had a screen over -torque alarm at: 4:04:26 2/26/19 Based on the duty assignment of the fine screens; Screen 1, should have been the last screen to fault since it was assigned Lag2 responsibility. Screen 3 was the assigned the Lead responsibility, Screen 2 the Lag responsibility. After the by-pass occurred, MSD promptly contacted the General Contractor (Judy Construction), equipment supplier (EnviroCare) and the systems integrator, (CITI). This initial contact was to begin scheduling additional logic and equipment troubleshooting and testing. The scheduling proved difficult due to the heavy workload of the equipment supplier and system integrator. The earliest all parties could be on site was not until March 11th. In the interim, MSD has placed one fine screen channel in a constant open/operational state to prevent the possibility of another bypass. On -March 11, 2019, representatives from EnviroCare and CITI,along with MSD staff conducted equipment and,control logic testing. This testing carried over to March 12, 2019, -with no deficiencies identified. Below is the list of testing, changes and outcomes; • .The logic of PLC14 was re -checked but no changes to the program were made before the test. . • For, testing, Screen 3 was the lead, Screen 2 the lag and Screen 1 was lag2. Protecting Our Natural Resources 2028 RIVERSIDE DRIVE, ASHEVILLE, NORTH CAROLINA28804 TELEPHONE: (828)254-9646 FAX: (828)254-3299 WEBSITE: www.msdbc.org • Jeff (Envirocare) lowered the trip set point for the over -torque relay on the LCP panels so that the screen would fail in an over -torque each time it was turned on. • We ran different scenarios where only the lead failed, then the lead and lag failed, and finally all the screens. In addition, tests were performed only with the lead running and then, by changing the influent flow set point, with two screens running. In every test, PLC14 behave' as expected. When one of the screens failed, the influent and effluent gates remained open for 5 minutes, while the next screen opened its gates. • A critical high level situation was simulated, all screen gates opened under this condition, even when the screens were faulted. • It was found that the set point for the high critical alarm was set at 7 feet, comparing it to the elevation at which the sensor was installed; this set point would not be reached during a high flow/level situation. • After the tests were completed, Jeff reconfigured the over -torque setting to its original set point and Dale changed the critical high level alarm to 6.5 feet. In addition, after discussion with Operations, the 5-minute timer to maintain the gates open after a screen failure was increased to 8 hours. • It was confirmed that all the over -torque alarms were generated at the LCP panels. Jeff could not identify the reason why screens 2 and 1 failed in over -torque, and the behavior of the gates on February 26 was not possible to replicate. • The logic of PLC14 with respect to the influent and effluent gates was not modified as it worked as expected and the gates did not close immediately after the LCP panel torque over -torque alarms were generated. Since thepost testing did not duplicate the over torque situation experiences on February 26, 2019, MSD has undertaken operational controls to eliminate the likelihood of another by-pass from the fine screens. This is as follows; • All flow control gates, influent and effluent, are maintained in the open position • All PLC set points are set so operational control must be manually changed by an operator • The washing of fine screens is controlled by flow differential from influent side of fine screen to effluent side of side of fine screen. This is the only, somewhat, automatic operation of the fine screens in place. MSD believes the actions taken prior to the bypass of the fine screens were within industry standard for startup of new equipment. The followup of the bypass was detailed and complete even though the over torque was not re -creatable. Furthermore, MSD believes the operational changes to the fine screens will prevent another bypass barring any extraordinary operating conditions. Respectfully, Peter C. Weed Director of Operations, MSD Cc: Thomas E. Hartye, General Manager; MSD File