HomeMy WebLinkAboutNC0069523_Compliance Evaluation Inspection_20190416Roy COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mr. Andrew Neff, P.E.
Water and Wastewater Division Director
4600 Gold Mine Road
Monroe, NC 28110
Dear Mr. Neff:
NORTH CAROLINA
Environmental Quality
April 16, 2019
SUBJECT: Compliance Sampling Inspection
Tallwood Estates WWTP
NPDES Permit NC00069523
Union County, NC
On April 3, 2019, Roberto Scheller of this Office conducted a compliance inspection at the subject
facility. This inspection was conducted as a Compliance Evaluation Inspection (CEI) to insure
compliance with permit requirements and conditions.
We wish to thank the operating staff for assistance regarding this inspection. The enclosed report
should be self-explanatory; however, should you have any questions, please do not hesitate to
contact myself or Roberto Scheller at (704) 235-2204 or roberto.schellerCcDncdenr.gov.
Sincerely,
DocuSigned by:
A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: CEI Report
cc: Danny Smith, ORC, email: danny.smith@unioncountync.gov
D Q North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NORTH CAROHNA �
o.namremor �w.c�giuuei� /`� 704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCO069523 111 12 I 19/04/03 I17 18 I S i 19 i G i 201 I
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70 I g 71 I tyI 72 I r I 73 I I 174 751 I I I I I I I80
uI I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
12:38PM 19/04/03
18/11/01
Tallwood Estates WWTP
4988 Brief Rd
Exit Time/Date
Permit Expiration Date
Indian Trail NC 28079
01:27PM 19/04/03
23/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Danny L Smith/ORC//
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Edward Goscicki,500 N Main St -Ste 500 Monroe NC 281124730/Public Works
Director/704-296-4212/7042964232 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Roberto Scheller MRO WQ//252-946-6481/ 4/16/2019
91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger Division of Water Quality//704-2,
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
e� 4/16/2019
AlaccsalAFvazs... Page#
NPDES yr/mo/day Inspection Type
NCO069523 I11 121 19/04/03 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO069523 Owner - Facility: Tallwood Estates WWTP
Inspection Date: 04/03/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
M
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Current permit was issued on November 1, 2018 and expires on October 31,2023.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: Records and reports are stored at Crooked Creek WWTP.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Page# 3
Permit: NCO069523 Owner - Facility: Tallwood Estates WWTP
Inspection Date: 04/03/2019 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
❑
Comment:
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: Debris is disposed of in dumpster at Crooked Creek WWTP.
Equalization Basins
Yes No NA NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
❑
❑
❑
Are audible and visual alarms operable?
❑
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Page# 4
Permit: NCO069523
Inspection Date: 04/03/2019
Equalization Basins
Owner - Facility: Tallwood Estates WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: Facility has EQ basin and aerobic sludge holding
tank. Sludge is removed to Crooked
Creek and final disposal by land application under
permit W00007486 and #ND0089004
land application in South Carolina.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
0
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Comment:
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
❑
❑
❑
Comment:
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Page# 5
Permit: NCO069523 Owner - Facility: Tallwood Estates WWTP
Inspection Date: 04/03/2019 Inspection Type: Compliance Evaluation
Pumps-RAS-WAS Yes No NA NE
Comment:
Filtration (High Rate Tertiary)
Yes No NA NE
Type of operation:
Cross flow
Is the filter media present?
❑
❑
❑
Is the filter surface free of clogging?
❑ ❑
❑
Is the filter free of growth?
❑ ❑
❑
Is the air scour operational?
❑
❑
❑
Is the scouring acceptable?
❑ ❑
❑
Is the clear well free of excessive solids and filter media?
❑
❑
❑
Comment:
Disinfection - UV
Yes No NA NE
Are extra UV bulbs available on site?
❑
❑
❑
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
0
❑
❑
❑
Is transmittance at or above designed level?
0
❑
❑
❑
Is there a backup system on site?
0
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment: Effluent from UV was clear with no visible suspended solids.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: At time of inspection effluent sampler was recorded at 4.3 degrees Celsius.
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? 0 ❑ ❑ ❑
Page# 6
Permit: NCO069523 Owner - Facility:
Inspection Date: 04/03/2019 Inspection Type:
Tallwood Estates WWTP
Compliance Evaluation
Flow Measurement - Effluent
Yes No NA NE
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Comment: flow meter was last calibrated on 2/27/2019 by CITI, LLC.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: at point of discharge effluent was clear with no visible solids or foam at
point of discharge.
Standby Power
Yes No NA NE
Is automatically activated standby power available?
0
❑
❑
❑
Is the generator tested by interrupting primary power source?
0
❑
❑
❑
Is the generator tested under load?
0
❑
❑
❑
Was generator tested & operational during the inspection?
❑
❑
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
0
❑
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
0
❑
❑
❑
Is the generator fuel level monitored?
0
❑
❑
❑
Comment:
Page# 7