Loading...
HomeMy WebLinkAboutWQ0009772_NOV-2019-LV-0054 Response_20190409Strickland, Bev From: Dana Hill <Dana.Hill @caroli nawaterservicenc.com> Sent: Tuesday, April 09, 2019 8:40 AM To: Toppen, Sarah A Cc: Jonathan Bryce Mendenhall; Robert Adam James; Eddie Baldwin Subject: [External] NOD-2019-LV-0054 Follow Up Flag: Follow up Flag Status: Flagged rnal email. Do not click links or open attachments unless you verify. Send all suspicious email as an attachment to nc. ov Good Morning Sarah, I just wanted to touch base with an explanation for NOD-2019-LV-0054 issued to Monterey Shores WWTP (permit WQ009772). During the months of October through December 2018, one of our air actuator valves and control software became inoperable so that Dissolved Oxygen levels in the aeration basin could not be completely controlled through the PLC. Operators regulated air flow manually, but with relatively low, off-season flows and erratic temperatures, maintaining a steady DO level was challenging. As a result, we were not able to consistently foster conditions so that complete nitrification could take place. All necessary repairs have been made to the control system and the actuator valve has been replaced, and Total Nitrogen results are now consistently below permit limits. Respectfully, Carallna Water Seri ice Dana Hill Regional Manager Central / Coastal NC (704) 319-0503 office (252) 269-2540 cell dana.hill@carolinawaterservicenc.com www.carolinawaterservicenc.com 1