HomeMy WebLinkAboutWQ0018755_Add Info Letter_20190415ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
NORTH CAROLINA
Environmental Quality
April 15, 2019
AMANDA BERGER — ENVIRONMENTAL COMPLIANCE MANAGER
AQUA NORTH CAROLINA, INC.
202 MACKENNON COURT
CARY, NORTH CAROLINA 27511-6447
Subject: Application No. WQ0018755
Additional Information Request
Castle Bay WWTP
Reclaimed Water Generation and
Dedicated Utilization
Pender County
Dear Ms. Berger:
Division of Water Resources' Central and Regional staff has reviewed the application package
received January 16, 2019. However, additional information is required before the review may be
completed. Please address the items on the attached pages no later than the close of business on May 15,
2019.
Please be aware that you are responsible for meeting all requirements set forth in North Carolina
rules and regulations. Any oversights that occurred in the review of the subject application package are
still the Applicant's responsibility. hi addition, any omissions made in responding to the outstanding items,
or failure to provide the additional information on or before the above requested date may result in your
application being returned as incomplete.
Please reference the subject application number when providing the requested information. All
revised and/or additional documentation shall be signed, sealed and dated (where needed), with two paper
copies and one electronic copy.
If you have any questions regarding this request, please do not hesitate to contact me at (919) 707-
3660 or tessa.monday@ncdenr.gov. Thank you for your cooperation.
Sincerely,
/tom f, jw '
Tessa Monday, Environmental Engineer
Division of Water Resources
cc: Wilmington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Permit Application File WQ0018755
D EQ �� North Carolina Department of Environmental Quality Division of Water Resources
512 North Salisbury Street 1 1617 Mail Service Center I Raleigh, North Carolina 27699-1617
NORTH CAROLINA
DepadmamofEnmron—WQuality
/� 919.707.9000
Ms. Amanda Berger
April 15, 2019
Page 2 of 3
A. Application (15A NCAC 02T .0105):
1. Provide the permit number(s) for the collection system and reclaimed water distribution lines.
2. The provided easement between Randy Blanton and Aqua references a plat map (Book 40, Page
32). Provide a copy of the plat.
3. It appears the irrigation fields are located on Castle Bay Corp. property. Provide an easement. Per
15A NCAC 02L .0107(f), an easement shall be executed and filed in the Register of Deeds in the
county in which the land is located, an easement running with the land which:
i. Contain notice of the permit, including the permit number, a description of the type of
permit, and the name, address and telephone number of the permitting agency or a reference
to a notice of the permit with book and page number of its recordation.
ii. Prohibit the construction and operation of water supply wells within the compliance
boundary.
iii. Reserve the right to the permittee and the State to enter on such property within the
compliance boundary for groundwater monitoring and remediation purposes.
4. To ensure the Division's records are correct, please verify the following in regards to the upset
pond and effluent storage pond:
a. Effective storage capacity
b. Liner type
c. Designed freeboard
d. Approximate date built
B. Site Map: The provided maps are incomplete. Provide a site map showing:
1. Distance measurements verifying all setbacks are being met (or minimum distance per setback waiver)
2. Stormwater drainage controls (ditches, stormwater drains, etc.)
3. Location and ownership of property boundaries within the disposal area (including road/rail right-of-ways
within 100 feet)
4. All facility -related structures and fences within the treatment, storage, and disposal areas
5. All habitable residences and places of assembly within 500 feet of all treatment, storage, and disposal sites
6. Location of all wells, streams (ephemeral, intermittent, and perennial), springs, lakes, ponds, ditches, and
other surface drainage features within 500 feet of all waste treatment, storage, and disposal site(s)
7. Location and identification of each monitoring well (identify any background/upgradient wells)
8. Latitude and longitude coordinates of all monitoring wells (decimal degrees to 6 digits)
9. Location and identification of major components of the waste disposal system
10. Identification of all storage or treatment earthen structures that are part of the permit
11. The wetted perimeter of all irrigation/infiltration fields with field names (named according to the approved
permit)
12. 100-year floodplain (if applicable)
Ms. Amanda Berger
April 15, 2019
Page 3 of 3
C. Setbacks
1. Ensure all setback are met or have a setback waiver. The facility was originally permitted in 2001
and is required to meet the following setbacks:
a. Irrigation sites:
i. Surface waters classified SA:
100 feet
ii. Surface waters not classified SA:
25 feet
iii. Each water supply well:
100 feet
iv. Each non -potable well:
10 feet
v. Each swimming pool:
25 feet
b. Treatment and storage facilities:
i.
Each habitable residence or place of assembly under
100 feet
separate ownership:
ii.
Each private or public water supply source:
100 feet
iii.
Surface waters:
50 feet
iv.
Each well with exception of monitoring wells:
100 feet
v.
Each property line:
50 feet
vi.
Each on -property residential unit if the unit is to be sold:
10 feet
vii.
Nitrification field:
20 feet
A Compliance
1. Per Tom Tharrington, the regional inspector, the irrigation equipment calibration records were not
available at the time of inspection. Per 15A NCAC 02U .0801(h), the dates of calibration irrigation
equipment must be kept in a maintenance log at this facility. Provide a status on the plan to install
a flowmeter from the effluent storage pond to the golf course irrigation system.
E. Groundwater
1. Provide location (same as requested for the site map), construction information, and completed
depth for all monitoring wells.
2. The ammonia levels for MW-2 have been exceeding the 15A NCAC 02L groundwater standards
and have steadily increased over time. Provide a groundwater analysis report to address these
exceedances. Per 15A NCAC 02L .0108, when the concentration of any substance exceeds the
standard at the review boundary, the permittee shall take action in accordance with the provisions
of Rule .0106. The permittee is recommended to schedule a meeting/phone conference with the
Central Office and Regional Office staff to discuss.