HomeMy WebLinkAboutNC0034304_Compliance Evaluation Inspection_20190401ROY COOPER
G&vcrr1ar
K41CHAEL S. REGAN
Secretary
LINDA CULPEPPER
arwfar
Gary Kuykendall
Young Life Ministries
120 Coles Cove Rd
Weaverville, NC 28787
NORTH CAROUNA
Environmental Qual"
April 1, 2019
SUBJECT: Compliance Inspection Report
Windy Gap Camp WWTP
NPDES WW Permit No. NCO034304
Buncombe County
Dear Mr. Kuykendall:
The North Carolina Division of Water Resources conducted an inspection of the Windy Gap Camp WWTP on
3/27/2019. This inspection was conducted to follow up and verify that the facility is operating in compliance
with the conditions and limitations specified in NPDES WW Permit No. NC0034304. Your attention to the items
in the previous inspection are appreciated. The findings and comments noted during this inspection are
provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report".
If you should have any questions, please do not hesitate to contact me at 828-296-4500 or via email at
linda.wiggs@ncdenr.gov.
Sincerely,
DocuSigned by:
6C38CDE2B5CF449...
Linda Wiggs
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS — Inspection Report
Ec: ARO Server, LF
G:\WR\WQ\Buncombe\Wastewater\Minors\Young Life Windy Gap 34304\Inspections\3-27-2019 Insp\20190401_NC0034304_CEI.rtf
NorthCaro:!ra Departn,entof Erv:rorrnentE�.-�uairty I Diuistnof Water Resources
Ash.--v;;:e Regnna:Off:ce j 2090 U.S. 70 F?glm-sy I Swannsmos, North Caro:m 23773
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NC0034304 111 12 I 19/03/27 I17 18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I 73 I I 174 751 I I I I I I I80
u I� I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:OOAM 19/03/27
16/02/01
Windy Gap Camp WWTP
2000 Lowery St
Exit Time/Date
Permit Expiration Date
Weaverville NC 28787
12:30PM 19/03/27
20/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Gary D Kuykendall,120 Coles Cove Rd Weaverville NC 28787/Maintenace
Tech/828-645-7187/ Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Linda S Wiggs Ds ARO WQ//828-296-4500 Ext.4653/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NC0034304 I11 121 19/03/27 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The inspector, Linda Wiggs, met with the ORC Gary Kuykendall.
All items noted in the previous inspection have been addressed.
A new sampler has been installed. Sampling is occurring after all treatment units. The flow meter has
been calibrated and setup properly with the new sampler. Flow concerns have been addressed by
pump management at the EQ and the flow readings appear to have been incorrect due to previous
calibration. Solids management at the plant is much improved and now appears affective.
Page#
Permit: NCO034304 Owner - Facility: Windy Gap Camp WWTP
Inspection Date: 03/27/2019 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: settleable solids, sludge judge, DO
Grease balls were noted in the plant; continued conversation with kitchen staff is warranted.
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
rims ►[•7►/_m►1M
■ ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Functions like a surge tank. Low/normal flow goes directly into the aeration basins; at this
time the malority is directed to the concrete plant.
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
■ ❑ ❑ ❑
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 3
Permit: NCO034304
Inspection Date: 03/27/2019
Aeration Basins
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Owner - Facility: Windy Gap Camp WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: There are a few diffusers that may need work: the ORC stated he will be Dullina those and
repairing where needed.
The ORC has been monitoring the DO and level of solids since the last inspection and has
gotten the system operating much better. It is the off season for the camp; the ORC has
made appropriate operational changes to compensate for less flow/food.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
0
❑
❑
❑
Comment: Steel plant blanket 178' liquid.
Concrete plant blanket 2712' liquid.
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑ ❑
0
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 1
Comment:
Page# 4
Permit: NCO034304
Inspection Date: 03/27/2019
Owner - Facility: Windy Gap Camp WWTP
Inspection Type: Compliance Evaluation
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
3
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: 3/13/2019 calibrated by Clearwater while they set up the new sampler system.
This calibration corrected previous calibrations' flows. The previous calibration appears
to
have overestimated flows.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0 ❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0 ❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑ ❑
0
❑
Comment:
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: New sampler installed. Setup on 3/13/2019, the first set of samples obtained this week.
Also noted, Clearwater technician educated the ORC on how to properly use the sampler for
proper flow proportional sampling; one important item is the need to correct for increased
summer flows by resetting the pulses/gallons.
Page# 5
Permit: NCO034304
Inspection Date: 03/27/2019
Effluent Sampling
Owner - Facility: Windy Gap Camp WWTP
Inspection Type: Compliance Evaluation
Upstream / Downstream Sampling
Is the facility sampling performed as required by the permit (frequency, sampling type, and
sampling location)?
Comment:
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Yes No NA NE
Yes No NA NE
■ ❑ ❑ ❑
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
Comment: The ORC installed new plumbing allowing him to waste and return solids when needed. For
example, the steel plant has dual hopper clarifiers; only one of the clarifiers had plumbing to
waste, now the ORC can waste from both.
Page# 6