Loading...
HomeMy WebLinkAboutNC0021628_NOV2019PC0197_20190314ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER NORTH CAROLINA Director Environmental Quality 14 March 2019 CERTIFIED MAIL #7017 2620 0000 6788 4743 Return Receipt Requested Mr. Ray Allen, Interim Town Administrator Town of Norwood Post Office Box 679 Norwood, NC 28128 SUBJECT: Notice of Violation NOV-2019-PC-0197 Compliance Evaluation Inspection Norwood WWTP NPDES Permit NCO021628 Stanly County, NC Dear Mr. Allen: On March 6, 2019, Roberto Scheller of this Office conducted a compliance inspection at the subject facility. This inspection was conducted as a Compliance Evaluation Inspection (CEI) to insure compliance with permit requirements and conditions. It was noted during the subject inspection that the subject facility had numerous issues related to maintenance of treatment equipment. Please be advised that in accordance with your NPDES Permit NC0021628, Part II, Section C, Item 2. "Proper Operation and Maintenance", "The Permittee shall at all times provide the operation and maintenance resources necessary to operate the existing facilities at optimum efficiency." In order to achieve full compliance with the permit condition noted above, the following must be completed: • The #1 aeration basin clean -out project must be completed; • Both surface aerators in #1 aeration basin returned to full operation; • The #2 aeration basin surface aerator that was not functional during the inspection must also be repaired and placed back in full operation; • Bar screen at headworks must be repaired or replaced to ensure proper screening and removal of debris prior to wastewater flow entering aeration basin. You are requested to respond to this Notice, in writing, regarding the above noted violations, within fifteen (15) days of receipt. The response should include all remedial actions including the specific activities to prevent the recurrence of these violations. Failure to respond and/or failure to resolve the violations could subject you to further action by the Division of Water Resources. D Q North Carolina Department of Environmental Quality I Division of Water Resources Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115 NORTH CAROHNA � o.namremor �w.c�giuuei� /`� 704.663.1699 We wish to thank the operating staff for assistance regarding this inspection. The enclosed report should be self-explanatory; however, should you have any questions, please do not hesitate to contact myself or Roberto Scheller at (704) 235-2204 or roberto.scheller(aD_ncdenr.gov. Sincerely, DocuSigned by: A14CC681AF27425... W. Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ Enclosure: CEI Report United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 15 I 3 I NCO021628 111 12 I 19/03/06 I17 18 I S I 19 I G I 201 I 211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 671 70 I2 71 I tyI 72 I r I 73 I I 174 751 I I I I I I I80 uI I I i Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 10:58AM 19/03/06 14/02/01 Norwood WWTP 6896 US Hwy 52 Exit Time/Date Permit Expiration Date Norwood INC 28128 12:48PM 19/03/06 19/01/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Todd Franklin Robinson/ORC/704-881-4598/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Dwight Smith,PO Box 679 Norwood NC 28128/Town Adminstrator/704-474-3416/7044743201 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date DocuSigned by: Roberto Scheller MRO WQ//252-946-6481/ 3/13/2019 91C2A007838943E... Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger Division of Water Quality//704-2' EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. DocuSigned by: 3/14/2019 AlaccsalAFvazs... Page# NPDES yr/mo/day Inspection Type (Cont.) NCO021628 111 121 19/03/06 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Compliance history FY of 2018 show 2 NOV's issued (March, November 2018) for exceeded Fecal Coliform and NOD issued December 2018 for Flow exceeded. Review of flow records indicate treatment plant has I&I issues during rain events. Bypasss of treatment was reported in April, September, and October 2018. Bypass of treatment was reported January, Fberuary, and March 2019. Mechanical screen and grit removal worn out and not operating properly. One of two aeration basins has been down for 16 months to remove grit and solids. Only one of two surface aerators in operation allowing solids to settling out in aeration basin. Page# Permit: NCO021628 Owner - Facility: Norwood WWTP Inspection Date: 03/06/2019 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new 0 ❑ ❑ ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? M ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: Current NPDES Permit #NC0021628 expired on January 31, 2019. Permit is for the operation of an existing 0.75 MGD wastewater treatment plant. Special Order by Consent (SOC) is under review for subject facility (EMC SOC WQ S18-011). Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ Comment: All records reviewed at time of inspection were current and available for review. Operations & Maintenance Yes No NA NE Page# 3 Permit: NCO021628 Owner - Facility: Norwood WWTP Inspection Date: 03/06/2019 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: It was noted that only one of two surface aerators were in ODeration at time of insDection Solids were begining to settle -out in aeration basin. Only one of two aeration basins was in operation at time of inspection. It was noted in the last compliance inspection, conducted on October 24, 2017, that aeration basin was down for maintenance. 16 months have passed and soilds in aeration basin have not been cleaned out. Mechanical screen was not removing debris from waste stream. Sweeps on screw conveyor are worn -off and bottom bearing worn-out rendering mechanical screen useless. Mechanical screen was in manual bypass at time of inspection. Grit removal system not opeating at time of inspection. The result of the barscreen and grit removal equipment not being properly maintained has allowed solids to accumulate in aeration basins. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: Facility contracts Statesville Analytical Certification #440 and has Field Certification #5212 to perform field analyses. Type of bar screen a.Manual b.Mechanical Are the bars adequately screening debris? Is the screen free of excessive debris? Is disposal of screening in compliance? Is the unit in good condition? Comment: Mechanical screen in poor condition not removing any debris. Grit Removal Type of grit removal Yes No NA NE ■ ❑ ❑ ❑ ❑ ■ ❑ ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ ❑ Yes No NA NE Page# 4 Permit: NCO021628 Inspection Date: 03/06/2019 Owner - Facility: Norwood WWTP Inspection Type: Compliance Evaluation Grit Removal Yes No NA NE a.Manual ❑ b.Mechanical Is the grit free of excessive organic matter? ❑ ❑ 0 ❑ Is the grit free of excessive odor? ❑ ❑ 0 ❑ # Is disposal of grit in compliance? ❑ ❑ 0 ❑ Comment: Grit removal not removinq qrit. Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Surface Is the basin free of dead spots? ❑ 0 ❑ ❑ Are surface aerators and mixers operational? ❑ 0 ❑ ❑ Are the diffusers operational? ❑ ❑ 0 ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑ Comment: At time of inspection only one of two surface aerators in operation. Solids were starting to floc and settle in aeration basin. Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) Comment: Both secondary clarifiers were in operation at time of insepction. Yes No NA NE ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Page# 5 Permit: NCO021628 Inspection Date: 03/06/2019 Owner - Facility: Norwood WWTP Inspection Type: Compliance Evaluation Pumps-RAS-WAS Yes No NA NE Are pumps in place? 0 ❑ ❑ ❑ Are pumps operational? 0 ❑ ❑ ❑ Are there adequate spare parts and supplies on site? ❑ ❑ ❑ Comment: Two RAS-WAS pumps have a third backup pump. Disinfection -Gas Yes No NA NE Are cylinders secured adequately? 0 ❑ ❑ ❑ Are cylinders protected from direct sunlight? 0 ❑ ❑ ❑ Is there adequate reserve supply of disinfectant? 0 ❑ ❑ ❑ Is the level of chlorine residual acceptable? 0 ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? 0 ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ 0 ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ 0 ❑ If yes, then what is the EPA twelve digit ID Number? (1000- If yes, then when was the RMP last updated? Comment: De -chlorination Yes No NA NE Type of system ? Liquid Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ Is storage appropriate for cylinders? ❑ ❑ 0 ❑ # Is de -chlorination substance stored away from chlorine containers? 0 ❑ ❑ ❑ Comment: Are the tablets the proper size and type? ❑ ❑ 0 ❑ Are tablet de -chlorinators operational? ❑ ❑ 0 ❑ Number of tubes in use? Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ Page# 6 Permit: NCO021628 Inspection Date: 03/06/2019 Flow Measurement - Effluent Owner - Facility: Norwood WWTP Inspection Type: Compliance Evaluation (If units are separated) Does the chart recorder match the flow meter? Yes No NA NE ■ ❑ ❑ ❑ Comment: Flow meter last calibrated on June 5. 2018. Flow records were reviewed for 2018. Flow recording charts show sharp Mumps in flow during rain events that peg -out the chart recorder. Reported flows for January 2018 show 3.2% of reported flows were greater that or equal to 80% of permitted flow. High flow incress during 2018 to December when 65% of reported flows were greater than 80% indicating Inflow and Infiltration (M) in collection system. Total average yearly flow was caculated at 0.252 MGD. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: Drying Beds Yes No NA NE Is there adequate drying bed space? 0 ❑ ❑ ❑ Is the sludge distribution on drying beds appropriate? M ❑ ❑ ❑ Are the drying beds free of vegetation? 0 ❑ ❑ ❑ # Is the site free of dry sludge remaining in beds? ❑ ❑ ❑ Is the site free of stockpiled sludge? ❑ ❑ ❑ Is the filtrate from sludge drying beds returned to the front of the plant? 0 ❑ ❑ ❑ # Is the sludge disposed of through county landfill? 0 ❑ ❑ ❑ # Is the sludge land applied? ❑ ❑ 0 ❑ (Vacuum filters) Is polymer mixing adequate? ❑ ❑ 0 ❑ Comment: Standby Power Yes No NA NE Is automatically activated standby power available? 0 ❑ ❑ ❑ Is the generator tested by interrupting primary power source? 0 ❑ ❑ ❑ Is the generator tested under load? ❑ ❑ ❑ Was generator tested & operational during the inspection? ❑ ❑ ❑ Do the generator(s) have adequate capacity to operate the entire wastewater site? 0 ❑ ❑ ❑ Is there an emergency agreement with a fuel vendor for extended run on back-up power? 0 ❑ ❑ ❑ Is the generator fuel level monitored? 0 ❑ ❑ ❑ Comment: Page# 7 Permit: NC0021628 Inspection Date: 03/06/2019 Standbv Power Owner - Facility: Norwood WWTP Inspection Type: Compliance Evaluation Yes No NA NE Page#