25 February 2019
Mr. Bill Willis, Mayor
Town of Grover
P.O. Box 189
Grover, NC28073
Subject: Notice of Violation and Recommendation for Enforcement
Compliance Evaluation Inspection
NOV-2019-PC-0099
Grover WWTP
NPDES Permit No. NCO065242
Cleveland County
Dear Mr. Willis:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on February 14, 2019, by Ori Tuvia. The cooperation of James Davis during
the site visit was much appreciated. Please advise the staff involved with this NPDES Permit by
forwarding a copy of the enclosed report.
The following areas of concern were observed during the inspection:
1) The facility has no source of standby power. This is a continuing violation that was noted
on the previous inspection report (dated December 20, 2017). Part II, Section C (7) of
NPDES Permit No.NC0065242 dated September 1, 2018, states: Power Failures "The
Permittee is responsible for maintaining adequate safeguards to prevent the discharge of
untreated or inadequately treated wastewater during power failures by means of alternate
power sources, standby generators or retention of inadequately treated effluent".
2) At the time of the inspection, the bar screen appeared too coarse, undersized, and
insufficient to catch the debris in the influent flow. Rags, paper products and other debris
were observed in downstream treatment units including at the effluent (see pictures below).
Debris was evident at the facility effluent pipe into Jakes Branch.
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office 1 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115
704 663 1699
3) As a reminder, the effluent sampler should be maintained such that the tubing and/or the
sample container do not freeze in the winter months and that the sample is maintained at
a temperature of no more than 6°C.
Picture 1. Coarse bar screen
Picture 2. Rags at the effluent
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
NORTH CAROLINA
EhWronmerttaf Quality
Please be advised that this correspondence is being issued as a Notice of Violation with a
Recommendation for Enforcement Action. You are requested to respond to this Notice, in writing,
regarding the above noted violations, within fifteen (15) days of receipt. The response should
include all remedial actions, including the specific activities to prevent the recurrence of these
violations. Failure to respond and/or failure to resolve the violations could subject you to further
action by the Division of Water Resources. Please be advised that pursuant to G.S. 143-215.6A, a
civil penalty of not more than twenty-five thousand dollars ($25,000.00) per day, per violation and
may be assessed against any person who violates or fails to act in accordance with the terms,
conditions, or requirements of any permit issued pursuant to G.S. 143-215.1.
Should you have any questions concerning this Notice, please do not hesitate to contact
Ori Tuvia at (704) 235-2190/ori.tuviagncdenr.gov or me at (704) 235-2194
corey.basinizernncdenr. gov
Sincerely,
DocuSigned by:
A14CC681 AF27425...
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
Cc: NPDES, MRO Files (Laserfiche)
James Davis (E-copy)
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office 1 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115
704 663 1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NC0065242 111 12 I 19/02/14 I17 18 I S I 19 I G I 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70 71 [.. I 72 73 L_LJ74 751 I I I I I I I80
I —I u
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:OOAM 19/02/14
18/09/01
Grover WWTP
1229 Bethlehem Church Rd
Exit Time/Date
Permit Expiration Date
Grover NC 28073
11:10AM 19/02/14
23/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
James Lester Davis/ORC/704-813-9342/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Bill Willis,PO Box 189 Grover NC 280730189//704-937-9986/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
eo-DocuSigned by:
OriATuvia ,--Eli MROWQ//704-663-1699/ 2/25/2019
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger Division of Water Quality//704-2;
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
eyj 2/25/2019
A14CC681AF27425...
Page#
NPDES yr/mo/day Inspection Type
NCO065242 I11 121 19/02/14 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO065242 Owner - Facility: Grover WWTP
Inspection Date: 02/14/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The subject permit expires on 8/31/2023.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: Records reviewed during the inspection were well maintained. DMRs, COCs Calibration
logs and ORC logs were reviewed for October 2018 through January 2019.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑
Page# 3
Permit: NCO065242 Owner - Facility: Grover WWTP
Inspection Date: 02/14/2019 Inspection Type: Compliance Evaluation
Laboratory
Yes No NA NE
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: On -site analvses of TRC. DH. and temDerature are Derformed under field laborator
certification #5497 (Grover WWTP). The permittee has also contracted Gel Labs (mercury)
and Water Tech Labs, Inc. (laboratory certification #50) to provide the remaining testing
requirements. The field instrumentation used on site was being checked/calibrated before
daily use.
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
❑
❑
❑
Comment:
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
❑
❑
0
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
0
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: At the time of the inspection the temperature in the composite sampler was -2 degrees. Asa
reminder, the effluent sampler should be maintained such that the tubing and/or the sample
container do not freeze in the winter months and that the sample is maintained at a
temperature of no more than 6°C.
Operations & Maintenance
Yes No NA NE
Page# 4
Permit: NCO065242 Owner - Facility: Grover WWTP
Inspection Date: 02/14/2019 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ 0 ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: At the time of the inspection the followina maintenance issues were observed:
1) The facility has no source of standby power.
2) At the time of the inspection the temperature in the composite sampler was -2 degrees.
As a reminder, the effluent sampler should be maintained such that the tubing and/or the
sample container do not freeze in the winter months and that the sample is maintained at a
temperature of no more than 6°C.
3) At the time of the inspection, the bar screen appeared too coarse, undersized, and
insufficient to catch the debris of the influent flow. Rags, paper products and other debris
was observed in downstream treatment units including at the effluent
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
❑
0
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
❑
0
❑
❑
Comment: At the time of the inspection, the bar screen appeared too coarse, undersized, and
insufficient to catch the debris of the influent flow. Rags, paper products and other debris
was observed in downstream treatment units includina at the effluent
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Yes No NA NE
Ext. Air
Diffused
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
Comment: Both Blowers were operational. At the time of the inspection it was evident that the aeration
basin had excessive amount of debris. Aeration basin debris should be removed.
Page# 5
Permit: NC0065242
Inspection Date: 02/14/2019
Owner - Facility: Grover WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes No NA NE
■
❑
❑
❑
❑
❑
■
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
■
❑
❑
■
❑
❑
❑
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Comment: Since the last inspection a new clarifier skimmer was installed, however floating sludge was
still evident suggesting am additional skimmer might be needed.
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
M
❑
❑
❑
Number of tubes in use?
5
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑
❑
❑
Is storage appropriate for cylinders?
❑
❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑
0
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Comment: The disinfection and dechlorination tablets are stored in closed containers in the same
location
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 6
Comment:
Page# 6
Permit: NCO065242
Inspection Date: 02/14/2019
De -chlorination
Owner - Facility: Grover WWTP
Inspection Type: Compliance Evaluation
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: The Flow meter was calibrated on 1/28/2019.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Yes No NA NE
■
❑
❑
❑
❑
■
❑
❑
❑
❑
■
❑
Comment: At the time of the inspection the effluent appeared clear however rags were evident in the
effluent discharge location.
Drying Beds
Yes No NA NE
Is there adequate drying bed space?
0
❑
❑
❑
Is the sludge distribution on drying beds appropriate?
0
❑
❑
❑
Are the drying beds free of vegetation?
0
❑
❑
❑
# Is the site free of dry sludge remaining in beds?
0
❑
❑
❑
Is the site free of stockpiled sludge?
0
❑
❑
❑
Is the filtrate from sludge drying beds returned to the front of the plant?
0
❑
❑
❑
# Is the sludge disposed of through county landfill?
0
❑
❑
❑
# Is the sludge land applied?
❑
0
❑
❑
(Vacuum filters) Is polymer mixing adequate?
❑
❑
0
❑
Comment:
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Page# 7
Permit: NC0065242
Inspection Date: 02/14/2019
Aerobic Digester
Owner - Facility: Grover WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: Waste sludge is pumped from the digester to the drying beds with the filtrate returning to the
head of the plant. Residual cake is placed in the Republic Services covered dumpster on
site