HomeMy WebLinkAboutNC0006564_WWTP CEI Baxter_20190222DocuSign Envelope ID: C6B98CBF-EAB9-4054-AA87-37C353A9E7BF
A � SiAl
k 7
ROY COOPER
Governor ��
MICHAEL S. REGAN �..
Seerekrry
LINDA CULPEPPER NORTH CAROL INA
oirrrtar Environmental Qualfry
February 22, 2019
Corey Carpentier
Baxter Healthcare Corporation
65 Pitts Station Rd
Marion, NC 28752
SUBJECT: Compliance Inspection Report
Baxter Healthcare Corporation
NPDES WW Permit No. NC0006564
McDowell County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Baxter Healthcare
Corporation on 2/14/2019. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0006564. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
The new plant appeared well operated and maintained. There were no significant issues or findings
noted during the inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Timothy Heim with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
Sincerely,
DocuSigned by:
7E617A38285848C...
G. Landon Davidson, P.G., Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Ec: WQS-ARO Server
LF
G:\WR\WQ\Mcdowell\Wastewater\Industrial\Baxter 06564\2018 Inspection\20190222_NC006564_CEI Ltr.Docx
NorthCaroiinaDepartroentofEnvironmentalQuslBy 1 0MsionofWateTResod rres
Ashevil ie Regonal Office 1 2090U.5.70ffgiyway I Sw nsmos. North CamZn 2S77SS
Q
32S 29C-0500
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NC0006564 111 12 I 19/02/14 I17
18 I S J 19 L G j 201
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I
I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 CA
---------------------- Reserved -------------------
671
70 IJ 71 Ij 72 u L n �
73 L_LJ74 751 I I I I I I I80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09:OOAM 19/02/14
16/09/01
Baxter Healthcare Corporation
65 Pitts Sta Rd
Exit Time/Date
Permit Expiration Date
Marion NC 287527925
12:OOPM 19/02/14
20/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Stephen Douglas Gouge/ORC/828-756-6618/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Anita Jensen,
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenance 0 Effluent/Receiving Waters 0 Other
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers
Date
Daniel J Boss DocuSigned by: ARO WQ//828-296-4658/
tl'%A I fkU� ARO WQ//828-296-4665/
Timothy H Heim E1082131
2/22/2019
105A3CA418...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers
Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0006564 I11 121 19/02/14 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim and Dan Boss of the Asheville Regional Office performed a Compliance Evaluation
Inspection of the facility on February 15, 2019. Stephen Gouge (Baxter EH&S), Brian Valiquette (ORC)
and Corey Carpentier (Environmental Engineer) were present at the time of the inspection.
The new facility appeared well maintained and operated at the time of the inspection, and in
compliance with Permit NC0006564.
Page#
Permit: NC0006564
Inspection Date: 02/14/2019
Other
Owner - Facility: Baxter Healthcare Corporation
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The was the first routine compliance inspection performed on the newly constructed WWTP
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility is new, and housekeeping and maintenance are excellent. Process control
parameters include COD (Influent autosampler), pH, FC, Ammonia, Phosphate,
Conductivity, TSS, membrane pressure, LIV transmittance and DO.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Equalization Basins
Yes No NA NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
0
❑
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment: This facility includes a high COD and low COD EQ basin with surface mixers, the two
basins are blended to maintain a consistent COD strength in the aeration basins.
Aeration Basins
Mode of operation
Yes No NA NE
Ext. Air
Page# 3
Permit: NC0006564
Inspection Date: 02/14/2019
Aeration Basins
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Owner - Facility: Baxter Healthcare Corporation
Inspection Type: Compliance Evaluation
Yes No NA NE
Diffused
■
❑
❑
❑
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
Comment: The aeration basins include the capability of pH stabilization and nutrient dosing. The ORC
reports that the DO is typically maintained at --4.5 mq/L and MLSS --6500 mq/L.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment: Backup generator has been able to run entire facility during area wide power loss.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
❑
❑
■
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
Page# 4
Permit: NC0006564
Inspection Date: 02/14/2019
Effluent Pipe
Comment:
Owner - Facility: Baxter Healthcare Corporation
Inspection Type: Compliance Evaluation
Yes No NA NE
Page#