Loading...
HomeMy WebLinkAboutNC0006564_WWTP CEI Baxter_20190222DocuSign Envelope ID: C6B98CBF-EAB9-4054-AA87-37C353A9E7BF A � SiAl k 7 ROY COOPER Governor �� MICHAEL S. REGAN �.. Seerekrry LINDA CULPEPPER NORTH CAROL INA oirrrtar Environmental Qualfry February 22, 2019 Corey Carpentier Baxter Healthcare Corporation 65 Pitts Station Rd Marion, NC 28752 SUBJECT: Compliance Inspection Report Baxter Healthcare Corporation NPDES WW Permit No. NC0006564 McDowell County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Baxter Healthcare Corporation on 2/14/2019. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0006564. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". The new plant appeared well operated and maintained. There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact Timothy Heim with the Water Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at tim.heim@ncdenr.gov. Sincerely, DocuSigned by: 7E617A38285848C... G. Landon Davidson, P.G., Regional Supervisor Water Quality Regional Operations Section Asheville Regional Office Division of Water Resources, NCDEQ ATTACHMENTS Ec: WQS-ARO Server LF G:\WR\WQ\Mcdowell\Wastewater\Industrial\Baxter 06564\2018 Inspection\20190222_NC006564_CEI Ltr.Docx NorthCaroiinaDepartroentofEnvironmentalQuslBy 1 0MsionofWateTResod rres Ashevil ie Regonal Office 1 2090U.5.70ffgiyway I Sw nsmos. North CamZn 2S77SS Q 32S 29C-0500 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 15 I 3 I NC0006564 111 12 I 19/02/14 I17 18 I S J 19 L G j 201 211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 CA ---------------------- Reserved ------------------- 671 70 IJ 71 Ij 72 u L n � 73 L_LJ74 751 I I I I I I I80 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES Dermit Number) 09:OOAM 19/02/14 16/09/01 Baxter Healthcare Corporation 65 Pitts Sta Rd Exit Time/Date Permit Expiration Date Marion NC 287527925 12:OOPM 19/02/14 20/01/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Stephen Douglas Gouge/ORC/828-756-6618/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Anita Jensen, Yes Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Operations & Maintenance 0 Effluent/Receiving Waters 0 Other Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Daniel J Boss DocuSigned by: ARO WQ//828-296-4658/ tl'%A I fkU� ARO WQ//828-296-4665/ Timothy H Heim E1082131 2/22/2019 105A3CA418... Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NC0006564 I11 121 19/02/14 117 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Tim Heim and Dan Boss of the Asheville Regional Office performed a Compliance Evaluation Inspection of the facility on February 15, 2019. Stephen Gouge (Baxter EH&S), Brian Valiquette (ORC) and Corey Carpentier (Environmental Engineer) were present at the time of the inspection. The new facility appeared well maintained and operated at the time of the inspection, and in compliance with Permit NC0006564. Page# Permit: NC0006564 Inspection Date: 02/14/2019 Other Owner - Facility: Baxter Healthcare Corporation Inspection Type: Compliance Evaluation Yes No NA NE Comment: The was the first routine compliance inspection performed on the newly constructed WWTP Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The facility is new, and housekeeping and maintenance are excellent. Process control parameters include COD (Influent autosampler), pH, FC, Ammonia, Phosphate, Conductivity, TSS, membrane pressure, LIV transmittance and DO. Bar Screens Yes No NA NE Type of bar screen a.Manual ❑ b.Mechanical Are the bars adequately screening debris? 0 ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screening in compliance? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: Equalization Basins Yes No NA NE Is the basin aerated? 0 ❑ ❑ ❑ Is the basin free of bypass lines or structures to the natural environment? 0 ❑ ❑ ❑ Is the basin free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? 0 ❑ ❑ ❑ Are all pumps operable? 0 ❑ ❑ ❑ Are float controls operable? 0 ❑ ❑ ❑ Are audible and visual alarms operable? 0 ❑ ❑ ❑ # Is basin size/volume adequate? 0 ❑ ❑ ❑ Comment: This facility includes a high COD and low COD EQ basin with surface mixers, the two basins are blended to maintain a consistent COD strength in the aeration basins. Aeration Basins Mode of operation Yes No NA NE Ext. Air Page# 3 Permit: NC0006564 Inspection Date: 02/14/2019 Aeration Basins Type of aeration system Is the basin free of dead spots? Are surface aerators and mixers operational? Are the diffusers operational? Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Is the DO level acceptable?(1.0 to 3.0 mg/1) Owner - Facility: Baxter Healthcare Corporation Inspection Type: Compliance Evaluation Yes No NA NE Diffused ■ ❑ ❑ ❑ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment: The aeration basins include the capability of pH stabilization and nutrient dosing. The ORC reports that the DO is typically maintained at --4.5 mq/L and MLSS --6500 mq/L. Disinfection - UV Are extra UV bulbs available on site? Are UV bulbs clean? Is UV intensity adequate? Is transmittance at or above designed level? Is there a backup system on site? Is effluent clear and free of solids? Comment: Standby Power Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Comment: Backup generator has been able to run entire facility during area wide power loss. Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ ■ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ Page# 4 Permit: NC0006564 Inspection Date: 02/14/2019 Effluent Pipe Comment: Owner - Facility: Baxter Healthcare Corporation Inspection Type: Compliance Evaluation Yes No NA NE Page#